HomeMy WebLinkAbout2008-00409 - mechanical CITY OF ORONO PERMIT NO.: 2008-00409
� 2750 KELLEY PARKWAY
ORONO, MN 55356- DATE IssuED: 1 U14/2008
� 952 249-4600 FAX: 952 249-4616
ADDRESS : 1845 LAKEVIEW TER
P�N : 27-118-23-42-0016
LEGAL DESC : LONG LAKE COUNTRY CLUB ADDN
: LOT 004 BLOCK 002
PERMIT TYPE : MECHANICAL(>$500)
PROPERTY TYPE : RESIDENTIAL
CONSTRUCTION TYPE : HEATING SYSTEMS
VALUATION : $ 4,143.00
`._
APPLICANT MECHAN[CAL 51.79
DITTER INC. STATE SURCHARGE MECH (VALUATION) 2.07
820 TOWER DRIVE
MEDINA, MN 55340 MAIL-[N FEE 1.50
(763)478-9558 TOTAL 55.36
OWNER
JONES,CELAYNE
1845 LAKEVIEW TER
LONG LAKE, MN 55356
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed according to
the approved plans and specifications,applicable City approvals,and the
State E3uilding Code. This permit is for only the work described and does
not grant permission for additional or related work which requires separate
permits. All provisions of laws and ordinances goveming this type of work
shall be compied wi[h whether or not specitied herein.This permit will �
expire and become null and void if construction authorized is not
commenced within 180 days of the date of issuance,or if construction is �� � Q�
suspended for a period of 180 days at any time after work has commenced. �v
The applicant is responsible for assuring all required inspections are � n �� �-
requested in conformance with the State Building Code.This permit may be �,��"
revoked at an y time for due cause. •
(�,� 19-E,1� / / �� �I ��'�
Applicant Permitee ignature Date ��� � ���� / /
Issued By Si nature Date
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRIBED ABOVE.
CITY OF ORONO PERMIT NO.: 2oos-oo3ss
' 2750 KELL Y PARKWAY
. � OR O, MN 55356- DATE ISSUEn: 1U14/2008
' � 952 24 600 FAX: 952 249-4616
ADDRESS : 3534 IVY PL � `,
� � �
PIN : 20-117-23 -0019 �`t' � ��•
LEGAL DESC : TAY S SUBD OF SPRING PARK LO �� (�.
: LO 000 BLOCK 000 a�
PERMIT TYPE . ECHANICAL(>$500) �
PROPERTY TYPE : RESIDENTIAL
CONSTRiJCTION TYPE : HEATING SYSTEMS
VALUATION : $ 4,143.00
NOTE:
1 LENNOX GAS FURNACE
APPLICANT MECHANICAL 51.79
DITTER INC. STATE SURCHARGE MECH(VALUATION) 2.07
820 TOWER DRIVE
DINA, MN 55340 MAIL-IN FEE 1.50
( 2)478-9558 TOTAL 55.36
✓'��
OWNER
DANBERRY
3534 IVY PL
WAYZATA, MN 55391-
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed according to
the approved plans and specifications,applicable City approvals,and the
State Building Code. This permit is for only the work described and does
not grant permission for additional or related work which requires separate
permits. All provisions of laws and ordinances governing this type of work
shall oe compied with whether or not specified herein.This permit will
expire and become null and void if construction authorized is not
commenced within 180 days of the date of issuance,or if construction is
suspended for a period of 180 days at any time after work has commenced.
The applicant is responsible for assuring all required inspections are
requested in conformance with the State Building Code.This permit may be
revoked at any time for due caase.
�,� � / / �c�' / /
Applicant Permitee Signature Date Issued ignature Date
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRI D ABOVE.
� � ; FOR CTTY USE QNL.Y
� I �.' �,i� City of Orono
�` `r P.O.Box 66 D�e Receiveti:' Permit#
• ' `A-, � 2750 Kelley Pazkway . "
4 Crystal Bay,MN 55323 Agproved By: Amount$:
� ti ' �''r � (952)249-4600 �
CITY OF ORONO—MECHANICAL PERMIT
(All Commercial permits must be approved by the Building Official or Inspector and/or Fire Marshall)
GENERAL INFORMATI4N �
1. You may apply for mechanical permits by mail or in person at the City offices. Applications will
be reviewed and a permit will be issued within two working days.
2. Permit cards will be sent by return mail after a review is completed. PERMITS ARE NOT
VALID UNTIL YOU RECEIVE A PERMIT. WORK MUST NOT BEGIN UNTIL THE
PERMIT CARD IS POSTED ON THE JOB SITE.
3. Mechanical Desi�ns—Complete calculations,details and specifications are required for each
heating,ventilation,humidification-dehumidification,and air conditioning installation including
heat loss/heat gain calculation,design temperatures,equipment ratings and identification as to
type,manufacturer and model. Data shall be presented on form provided.
4. When any new construction or remodeling is involved,a separate building permit must be
obtained.
5. All work must be done in accordance with the Uniform Mechanical Code/State Building Code
requirements.
6. All work must be inspected(rough-in and final). Call(952)249-4600.
(24-48 hour notice required)
7, House Heating Test Record must be submitted before final.
TYPE OF PERMI
Check All That A 1
�Residential ❑Commercial(Approval Required)
❑New ❑Additional ❑Repairs [�R place
Job Site I Owner Tnformation:
LaL�v�c�.J
Site Address: /8NS ,� I-t•rR�,c
Owner: C'�`�7*-�- S•�.ss Mailing Address: ��+M--�
City: L.N.y �►Gt Zip: SS3sG
Home Phone: G12' ��5'��L�— Alternate Phone: 'vvz-�
Contractor Inforrnation:
Contractor: 'i'��itact Person: ���-�- ���Kl-t�
Address: ����'�a e Bond#:
820 Tower rive• mel� MN 55340
City: (763�.4�78-9558 Expiration Date:
��r.�
Phone: Alternate Phone:
� ❑ Insurance—Current: �"✓P�r`�` �
1
. ` : ..
HEATING SYSTEMS
Quantity: �
Make: �K'"'x
Model: G ?1►"�►/�3Gc-sfo
Fuel: �✓Gt�''� �0
Flue Size: G��� Z��P✓�
Input BTUs: !��Op O
Output BTUs: �s,5a D
CFM: ��� 34�0�
COOLING SYSTEMS
r.—
Quantity:
Make:
..�
Model:
Tons:
H.Power �
FIREPLACES
❑ Gas Factory Fireplace
❑ Wood Burning Fireplace
❑ Wood Stove
❑ Wood Stove With Flue
Brand Name: Model No.:
VENTILATION
❑ No. Kitchen Exhaust duct recirculating cfm
❑ No. Bath Exhaust(must have duct outside) cfm
❑ No. Other Fans: Locations cfm
FUEL STORAGE(MUST BE APPROVED BY FIRE MARSHALL)
❑ Installation ❑ Removal
Fuel Oil: gallons ❑ Underground ❑Inside ❑Outside
LP Gas: gallons
Other:
GAS LINE ONLY
❑ Outdoor Grill ❑ Other/List What&Where:
2
'..
, � • �' �,.
�;,
❑ Yes,this section applies
The replacement of a Residential fixture or appliance that meets all three of the following requirements:
1. Does not require modification to electrical or gas service.
2. Has a total cost of$500.00 or less;excludine the cost of the fixture or appliance:and
3. Is improved,installed or replaced by the homeowner or licensed contractor.
Skip next section,if this applies; Cost of Permit $ 15.00
State Surcharge $ .50
Mail-In Fee(If Applicable) $ 1.50
Total Permit Fee $
If above does not apply;follow guidelines below:
1. CONTRACT PRICE * is 1.25%of contract price with a(Minimum Fee of$35.00)
��i�l3 X.oi2s $ s�-�q
(contract price) (minimum$35.00)
2. STATE SURCHARGE ** Add the State Bldg Code Div. Surcharge(Minimum Fee ofS.50)
'� �-{1�13 z.o7
x.0005 $
(contract price) (minimum$ .50)
3. POSTAGE&HANDLING(Only on Mail-In Applications) $ 1.50
4. TOTAL PERMIT FEE(Add Lines 1-3 Above) $ SS• 36
■ * CONTRACT PRICE or JOB COST means the actual or estimated dollar amount charged for the
permitted work including materials, labor, profit,and other fixed costs. It is the amount to be charged
to the customer for the work done. If any material, equipment, labor or installations are furnished by
the owner,tenant or any other party, the reasonable market value of such items must be added to the
estimated cost or contract price for permit fee purposes. In the event that there is a dispute on the
amount of the job cost, the City may request the submission of a signed copy of the actual contract.
■ **The STATE SURCHARGE is.0005 of the Building Department at(952)249-4600 for the price.
�
The undersigned hereby applies to the City for issuance of a Mechanical Permit, agrees to do all
work in strict accordance with the ordinances of the City and the regulations of the State of
Minnesota, and certifies that all statements made on this application aze complete, true and
correct.
ApplicanYs Signature: ...� `� u Date: / � e
.
. � �E4:�' . . .
3
JONES
HVAC LOAD ANALYSIS
for
Celayne Jones
Long Lake, Mn
���� R��ID�NTIAt,
� HVAG I,o��
Prepared By:
Doug Bjork
Ditter Cooling and Heating
820 Tower Drive
Medina,MN.55340
(763)-478-8558
11/11/08
RHVAC-Residential 8 Light Commercial HVAC Loads Program � Elite Software Development,Inc.
Ditter,Inc. Jones
Hamel,MN 55340-9691 11N 1/OS Page 2
• �PYoject Summary
Project: Jones Company: Ditter Cooling and Heating
Client: Celayne Jones Representative: Doug Bjork
Address: Address: 820 Tower Drive
City: Long Lake, Mn City: Medina, MN. 55340
Phone: Phone: (763)-478-8558
Fax: Fax: (763)-478-2426
Comment:
Design Data
Project Name: Jones
Reference City: Minneapolis, Minnesota
Daily Temperature Range: Medium
Latitude: 44 Degrees
Elevation: 834 Feet
Elevation Sensible Adj. Factor: 1.000
Elevation Total Adj. Factor: 1.000
Outdoor Outdoor Indoor Indoor Grains
Drv Bulb Wet Bulb Rel.Hum. Drv Bulb Difference
Winter: -20 N/A N/A 72 N/A
Summer: 95 75 50% 72 42
Check Figures
Total Building Supply CFM: 1000 CFM per square foot: 0.251
Square feet of room area: 3,978 Square feet per ton: 1,143.324
Building Loads
Total heating required with outside air: 69,065 Btuh 69.065 MBH
Total sensible gain: 32,149 Btuh 88 %
Total latent gain: 4,265 Btuh 12 %
Total cooling required with outside air: 36,414 Btuh 3.034 Tons(based on sensible+ latent)
3.479 Tons(based on 77%sensible capacity)
Notes
Calculations are based on 7th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
Monday,November 10,2008
RHVAC-Residentlal 8 Light Commerctal HVAC loads Program Elite Software Development,Inc.
Ditter,Inc. Jones
Hamel,MN 55340-9691 11/11/08 Page 3
• Tbtal Building Summary Loads
Component Area Sen. Lat. Sen. Total
Description Quan Loss Gain Gain Gain
3E Window Double Pane Low Emit TIM Frame 419 15,380 0 14,227 14,227
8M Glass Door pouble Clear Glass Wood Frame 78 3,953 0 3,635 3,635
12D Wall R-11 + 1/2"Asphlt Board(R-1.3) 1,990 14,647 0 4,234 4,234
12H Wall R-19+ 1/2"Gypsum Board(R-0.5) 1,613 8,904 0 2,573 2,573
161 Ceiling R-44 Insulation 1,989 4,209 0 2,150 2,150
21A Basemt Floor 2'or More Below Grade 1,989 4,392 0 0 0
Subtotals for structure: 8,078 51,485 0 26,819 26,819
Active People: 4 0 920 1,200 2,120
Inactive People: 0 0 0 0 0
Appliances: 0 0 0 1,200 1,200
Lighting: 0 0 0
Ductwork: 0 0 0 0 0
Infiltration:Winter CFM: 179.1, Summer CFM: 119.4 497 17,580 3,345 2,930 6,275
Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0
Sensible Gain Total: 32,149
Temperature Swing Multiplier: X1.00
Building Load Totals: 69,065 4 265 32 149 36,414
Check Figures
Total Building Supply CFM: 1000 CFM per square foot: 0.251
Square feet of room area: 3,978 Square feet per ton: 1,143.324
Building Loads
Total heating required with outside air: 69,065 Btuh 69.065 MBH
Total sensible gain: 32,149 Btuh 88 %
Total latent gain: 4,265 Btuh 12 %
Total cooling required with outside air: 36,414 Btuh 3.034 Tons(based on sensible+ latent)
3.479 Tons (based on 77%sensible capacity)
Notes
Calculations are based on 7th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
Monday,November 10,2008
RHVAC-Residential&Light Commercial HVAC Loads Program � Elite Software Development,Inc.
Ditter,Inc. Jones
Hamel,MN 55340-9691 11/11/08 Page 4
• System#1 Summary Loads
Component Area Sen. Lat. Sen. Total
Description Quan Loss Gain Gain Gain
3E Window Double Pane Low Emit TIM Frame 419 15,380 0 14,227 14,227
8M Glass Door pouble Clear Glass Wood Frame 78 3,953 0 3,635 3,635
12D Wall R-11 + 1/2"Asphlt Board(R-1.3) 1,990 14,647 0 4,234 4,234
12H Wall R-19+ 1/2" Gypsum Board(R-0.5) 1,613 8,904 0 2,573 2,573
161 Ceiling R-44 Insulation 1,989 4,209 0 2,150 2,150
21A Basemt Floor 2'or More Below Grade 1,989 4,392 0 0 0
Subtotals for structure: 8,078 51,485 0 26,819 26,819
Active People: 4 0 920 1,200 2,120
Inactive People: 0 0 0 0 0
Appliances: 0 0 0 1,200 1,200
Lighting: 0 0 0
Ductwork: 0 0 0 0 0
Infiltration: Winter CFM: 179.1, Summer CFM: 119.4 497 17,580 3,345 2,930 6,275
Ventilation:Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0
Sensible Gain Total: 32,149
Temperature Swing Multiplier: X1.00
System Load Totals: 69 065 4,265 32,149 36,414
Check Figures
Supply CFM: 1,000 CFM per square foot: 0.251
Square feet of room area: 3,978 Square feet per ton: 1,143.324
System Loads
Total heating required with outside air: 69,065 Btuh 69.065 MBH
Total sensible gain: 32,149 Btuh 88 %
Total latent gain: 4,265 Btuh 12 %
Total cooling required with outside air: 36,414 Btuh 3.034 Tons(based on sensible+ latent)
3.479 Tons(based on 77%sensible capacity)
Notes
Calculations are based on 7th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
Monday,November 10,2008
RHVAC-Residential&Light Commercial HVAC Loads Program � Elite Software Development,Inc.
Ditter,Inc. Jones
Hamel,MN 55340-9691 11l11/08 Page 5
• System#1 Zone#1 Summary Loads
Component Area Sen. Lat. Sen. Total
Description Quan Loss Gain Gain Gain
3E Window Double Pane Low Emit TIM Frame 419 15,380 0 14,227 14,227
8M Glass Door pouble Clear Glass Wood Frame 78 3,953 0 3,635 3,635
12D Wall R-11 + 1/2"Asphlt Board(R-1.3) 1,990 14,647 0 4,234 4,234
12H Wall R-19+ 1/2" Gypsum Board(R-0.5) 1,613 8,904 0 2,573 2,573
161 Ceiling R-44 Insulation 1,989 4,209 0 2,150 2,150
21A Basemt Floor 2'or More Below Grade 1,989 4,392 0 0 0
Subtotals for structure: 8,078 51,485 0 26,819 26,819
Active People: 4 0 920 1,200 2,120
Inactive People: 0 0 0 0 0
Appliances: 0 0 0 1,200 1,200
Lighting: 0 0 0
Ducfinrork: 0 0 0 0 0
Infiltration:Winter CFM: 179.1, Summer CFM: 119.4 497 17,580 3,345 2,930 6,275
' Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 n/a n/a n/a n/a
Sensible Gain Total: 32,149
Temperature Swing Multiplier: X1.00
Zone Load Totals: 69,065 4,265 32,149 36,414
Check Figures
Supply CFM: 1,000 CFM per square foot: 0.251
Square feet of room area: 3,978 Square feet per ton: 1,143.324
Zone Loads
Total heating required with outside air: 69,065 Btuh 69.065 MBH
Total sensible gain: 32,149 Btuh 88 %
Total latent gain: 4,265 Btuh 12 %
Total cooling required with outside air: 36,414 Btuh 3.034 Tons(based on sensible+ latent)
3.479 Tons(based on 77% sensible capacity)
Monday,November 10,2008
RHVAC-Residential&Light Commercial HVAC Loads Program Elite Software Development,Inc.
Ditter,Inc. Jones
HameI,�MN 55340-9691 11N 1/08 Page 6
• � hbom Load Summary Reports
System#1 Room Load Summary
Htg Htg Run Run Cig Clg Cig Zone Clg Air
Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys
No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM
---Zone 1---
1 Main Level 1989 45,702 662 6-6 633 23,985 3,401 746 1.00 1,124 746
2 Basement 1989 23,363 338 3-5 621 8,164 864 254 1.25 478 254
System 1 Totals 3978 69,065 1,000 32,149 4,265 1,000 1,602 1,000
Main Trunk Size: 16x12 in.
System#1 Cooling System Summary
Cooling Sensible/Latent Sensible Latent Total
Tons Split Btuh Btuh Btuh
Net Required: 3.034 88%/12% 32,149 4,265 36,414
Recommended: 3.479 77°/a/23% 32,149 9,603 41,752
Monday,November 10,2008