Loading...
HomeMy WebLinkAboutProject summary e SECTION 01000-PROJECT SUNIlVIARY A. SUNIIVIARY OF WORK 1. Furnish all technical and pmfessional services,supervision,materials and equipment other than materials and equipment specified as furnished by others)and perform aU opera ons necessary and required to prepare land sites and existing building sites for installation of Personal Communications Services(PCS)Base Transmission Stations(BTS). 2. The Scope of work includes the installation of PCS antennas on the side of the White ear Lake Water Tower located on Centerville Road.A Base Transmission Station will be loca d inside the tower on the south west portion of the floor.Coaxial cable will be run from the transmission equipment to antennas located in pairs at specific locations on the side o the tower about 95 feet above the ground.Electrical service will be supplied to the ission equipment from an existing pad mounted transformer located outside and west of the wer.Tl lines will also be connected to the equipment. END OF SECTION CNS/US WEST COMMUNICATIONS 01000-1 PROJECT UMMARY SMMA NO.96419.16 17 DEC.% SECTION 02050-DEMOLITION � A. PROJECT INCLUDES 1. Existing Structure Demolition where shown to be removed: a. Demolition of identified s�tructiues. b. Demolition of paving to a minimum necessary depth to avoid conflict with new construction. c. Protection of adjacent site work and existing structures. d. Disconnection,rerouting,capping,and removal of identified or conflicting exi ' g utilities. e. Pollution control during demolition. f. Removal and legal disposal of materials. END OF SECTION � CNS/[TS WEST COMMUNICATIONS DEMO ITION SMMA NO.96419.16 02050-1 17 EC. % SECTION 03300-CAST-IN-PLACE CONCRETE A. PROJECT INCLUDES 1. Plant-Mixed Cast-In-Place Concrete: a Paving base and pads. B. QUALITY ASSURANCE 1. Standards: ACI 318,Building Code Requirements for Reinforced Concrete,and CRS Manual of Standard Practice. � 2. Testing: Independeat testing laboratory when required by Contractor or by local juris ictions. Concrete compressive strengths to be provided from Ready Mix supplier standard m' design and verified by batch plant ticket from delivery truck. 3. Pad Flamess: � a. pad surface shall comply with: ASTM E 1155,floor flamess(F fl of 15,floor le lness (Fl)of 13. 4. Special Inspections: As required by local jurisdictions. C. PRODUCTS 1. Concrete Design Mixes,ASTM C 94,28 Day Minimum Compressive Strength: a Slabs on Grade and Paving Base:4,000 psi. 2. Formwork: Plywood or metal panel formwork sufficient for structural and visual req irements. 3. Reinforcing Materials: a Reinforcing Bars: ASTM A 615,Grade 60,deformed. 4. Concrete Materials: ASTM C 150,Type I,Portland cement;ASTM C 33 normal wei t aggregates;potable water. 5. Concrete Admixtures: Containing less than 0.1 percent chloride ions. a, Air-Entraining Admixture: ASTM C 260,for exterior exposed concrete and fo dations • exposed to freeze-thaw shall contain from 4 to 7 percent total air. b. Water-Reducing Admixture: ASTM C 494,Type A,for placement and workabi ity. c. Water-Reducing,Accelerating Admixture: ASTM C 494,Type E,for placemen and workability. CNS/[JS WEST COMMUNICATIONS CAST-IN-PLACE ONCRETE SMMA NO.96419.16 03300-1 17 DEC.96 d. Water-Reducing,Retarding Admixture: ASTM C 494,Type D,for placement d workability. � 6. Auxiliary Materials: a. Liquid Membrane-Forming Curing Compound: ASTM C 309,Type 1,Class A. b. Water-Based Acrylic Membrane Curing Compound: ASTM C 309,Type 1,Cl s B. 7. Concrete Finishes For Formed Surfaces: a. Surfaces Exposed To View: Smooth form finish. 8. Concrete Finishes for Monolithic Slabs or as shown on site-specific drawings: a. Tmwel finish for surfaces to be exposed to view. END OF SECTION CNS/US WEST COMMiJNICATIONS CAST-IN-PLACE C NC1tETE SIvIIu1A NO.96419.16 03300-2 7 DEC.96 SECTION 05500-METAL FABRICATIONS A. PROJECT INCLUDES 1. Metal Fabrications: a Miscellaneous steel framing and related accessories for equipment and antenna. b. Steel shapes and plates embedded or secured to building. c. Steel connections including welding. d. Shop prime coat. e. Shop drawings as recluested on the drawings B. QUALITY ASSURANCE 1. Design Engineering: By Registered CiviUStructural Engineer.. C. PRODUCTS . 1. Ferrous Materials: a Steel Plates,Shapes and Bars: ASTM A 36. b. Steel Tubing: ASTM A 500 or A 501 c. Steel Pipe,Galvanized Finish: ASTM A 53. d. Brackets,Flanges,and Anchors: Cast or formed metal. e. Welding Rods and Bare Electrodes: AWS specifications . - f. Zinc-Coating: Hot-dip galvanized coating for materials in exterior assemblies, ASTM A 123 and G90 finish. 4. Fasteners: a. High Strength Bolts: ASTM A 325.Nuts ASTM A 194 or A 563.Washers AS F 436. b. Drilled-In Expansion�Anchors: FS FF-S-325. c. Exterior Use: All fasteners in exterior assemblies or exterior walls shall be hot ipped galvanized ASTM A153 or stainless steel. 5. Auxiliary Materials: a. Shop Primer.. Alkyd primer,FS TT-P-645. b. Galvanizing Repau'Pain� SSPC-Paint 20. . c. Zinc Chromate Primer: FS TT-P-645. D. EXECUT'ION 1. Fabrication and erection shall be in accordance with the applicable sections of the SC Code of Standard Practice,AISC Specification for Structural Steel Buildings,AWS and 1 cal,state and federal regulations. END OF SECTION CNS/US WEST COMMUNICATIONS 05500-1 METAL F RICATIONS 17 DEC.96 SMMA NO.96419.16 SECTION 09900-PAIlVTING A. PROJECT INCLUDES 1, paiating and surface preparation for exterior and interior surfaces. 2. Field-painting and surface preparation of exposed telecommunication equipment an electrical work,including conduit,supports,accessories,and antenna equipmen� 3. Repainting and surfa�e PreParat�on at areas of remodeling. 4, proper storage of painting materials away from heat,moisture,dust and other con inants,in fire-safe containers and enclosures. 5, proper disposal of all rags,debris,solvents and paints to environmentally-approved ites. g. QUALITY ASSURANCE . 1. Regulations: Compliance with VOC and environmental regulations. 2. Storage,handling,mixing,thinning,aPPlication,surface preparation,environmen conditions, etc.,shall comply with manufactu�'er's printed directions and subject to verification inspections. � C. PRODUCTS 1. First-line commercial-quality products for all coating systems,manufa°tur�d by K ppers Paint Co.for the metal surfaces including the tank,Sherwine-Williams,Glidden or Fulle O'Brien for other materials 2 All painting products shall be from single manufachuer in original unoPened label containers D. EXTERIOR PAINT SCHEDULE 1. Fermus Metal and Galvanized Ferrous Metal to Receive: primer-One coat of Koppers 654 Epoxy Primer a�plCl�eS tof 1.5 mi11s.85 �,g,per gallon to produce a muumum dry fi1m Intermediate-One coat of Koppers 107 Epoxy intermediate applied at a rate of 2 sq.ft.per gallon per coat to produce a dry film thickness of 2.0 mils. ' Finish-One coat of Koppers 1122BRS Linear Polyurethane in anti9ue ivory color 378 applied at a rate of 540 sq.ft.per gallon per coat to produce a dry film thickness of 1.0 mill per coat.This coat must be applied by spray method only ppINTING CNS/US WEST COMMUNICATIONS ��-1 17 DEC.96 SMMA NO.96419.16 Total dry fi1m thickness to be 4.5 mils. 2. Fiberglass Faced Antenna Panels to Receive Low Luster Urethane Finish color to ma h the tanlc. F. PREPARATION 1. Prior to coating application,clean all surfaces of oil,grease,dirt,rust and incomparibl matter. Power tool clean ferrous metals,treat galvanized metal for primer adhesion,sand fibe glass surfaces lightly,all in strict accordance with coating manufacturer's printed directio G. EXECUTION � 1, painting work shall be performed by experienced journeymen painters,capable of p ucing first quality industry standard work,uniform in color and film thickness,free of b maz'1cs, runs,sags and blemishes. Surfaces shall be prepared and paints shall be mixed,thinn d and applied in strict accordance with manufacturer's printed instructions.Protect all surf es not to receive paint against paint spatter,overspray or damage,and remedy such damage to atch new or existing finishes and conditions. END OF SECTION ppINTING CNS/[JS WEST COMMUNICATIONS 09000-2 »DEC.96 SMMA NO.96419.16 SECTION 16000-ELEC1'ItICAL MATERIALS AND METHODS - A. PROJECT INCLUDES 1. Generally,the extent of electrical work is shown on the drawings and in the specificati ns. Include all labor,materials,tools,equipment,transportation,supervision and inciden items essential for proper installation and operation,even though not specifically mentioned r indicated on the drawings. 2. Give necessary notices,obtain permits,pay governmental taxes,fees and other costs as required for the electrical work,and to file for necessary approvals with the jurisdiction under 'ch the work is to be performed. Obtain Certificate of Inspection for the electrical work;this rtificate is a prerequisite to final acceptance of and final payment for the electrical work. B. QUALITY ASSURANCE 1. National Electrical Code`2iFPA 70" 2. Electrical Sweep Testing of Coaxial Cables � C. PRODUCTS 1. Products and materials are specified in other sections and herein. D. EXECUTION 1. Submittal of bid indicates sub-contractor is cognizant of all site conditions and work to be erformed under this contract. 2, perform all verification,observations,test,and examination of work prior to the ordering f the electrical equipment aad actual construction. Sub-contractor shall issue a written notice o all findings to the Contractor listing all malfunctions,faulty equipment and discrepancies. 3. Heights shall be verified with Contractor prior to installation. 4. Drawings are diagrammatic oaly,follow as closely as possible. 5. Electrical Service:208VAC,or 240VAC,single phase,3 wire 100 amp service. 6. Each conductor of every system shall be permanently tagged in each panelboard,pullbox, 'unction box,switch box,etc. 7. All materials and equipment shall be new and in perfect condition when installed and shal be of the best grade and of the same manufact�u�er throughout for each class or group of equipment.Materials shall meet with approval of the division of industrial safety and all governing bodies hav' g jurisdiction.Materials shall be manufactured in accordance with applicable standards e lished by ANSI,NEM�►,and NBFU. • 8. All conduit installed maybe surface mounted unless otherwise noted. 9. Sub-contractor shall cairy out his work in accordance with all governing state,county,an local codes and OSHA and NEC. 10. Sub-contractor shall secure all necessary building permits and pay all required fees. CNS/C1S WEST COMMUNICATIONS ELECTRICAL MATERIALS METHODS SMMA NO.96419.16 16000-1 17 DEC.96 11. Complete job shall be guaranteed for a pe�riod of one year after date of job acceptance by owner.Any work,material or equipment found to be Eaulty during that period shall be corrected at once upon written notification,at the expense of the ;5ub-contractor. 12. All conduit only(C.O.)shall have a pull v��ire or rope. 13. All work shall be per installation drawing:;and details.Provide Contractor with one set of complete electrical"as installed"mazkups at the completion of the job showing actual dimensions,routings and circuits. 14. All brochures,operating manuals, catalogs, shop drawings, etc.,shall be tumed over to the Contractor at job completion. 15. Use t-tap connections on all multi-circuits with common neutral conductor for lighting fixtures. 16. All conductors shall be copper. 17. All circuit breakers,fuses and electrical equipment shall have a minimum interrupting short circuit rating of 10,000 A.I.C. Sub-contractor shall verify the Site requirements. 18. The entire electrical installation shall be gr.ounded as required by all applicable codes and NEC. 19. Patch,repair,and paint any area that has been damaged in the course of the electrical work. 20. Penetrations in fire rated walls shall be sea�led in accordance with applicable codes. 21. Power wire and cable conductors shall be��opper#12 AWG minimum unless specifically noted otherwise on drawings. 22. Grounding conductors shall be tinned cop��er,annealed, and solid or stranded and sized as shown on drawings. . . 23. Meter socket amperes,voltage,number of phases shall be as noted on the drawings,Manufactured by"Square D Company"or approved equa�l. 24. All materials shall be UL listed. 25. Conduit Rigid conduit shall be IJL labeled galvaniz;ed zinc coated with zinc interior and shall be used when installed in or under concrete slabs in cont3ct with the earth,under public roadways, in masonry walls or exposed on building exterior.Rigid conduit in contact with earth shall be %2 lap wrapped with Hunts wrap process No.3.Flexible metallic conduit shall have IJL listed label and may be used where permitted by code.Fittings shall be `jake"or"squeeze"type;seal tight flexible conduit.All conduit shall have full size equipment ground wire. Conduit runs shall be surface mounted in ceilings or walls unless indicated otherwise. Conduit indicated shall run parallel or at right angles to the ceiling,floor,or beams.Verify e�cact rout'vig of all exposed conduit with the Owner prior to installing.No horizontal conduits shall be lbelow 7'-6"Above Finish Floor(A.F.F).No BX or ROMEX cable is permitted.All underground conduit shall be PVC schedule 40(unless noted otherwisel at a minimum depth of 30"below grade or 6"below frost line. 26. All electrical equipment shall be labeled with permanent engraved plastic labels. 27. Coordinate the electrical service with the local utility company. CNS/US WEST COMMUNICATIONS ELECTRICAL MATERIALS AND METHODS SMMA NO.96419.16 16000-2 17 DEC.96 28. Upon completion of work,conduct continuity,short circuit and fall of potential ground te for approval.Submit test reports to the Contractor.Clean premises of all debris resulting from ork and _ leave work in a complete and undamaged condition. 29. Sub-contractor shall coordinate with the utility company for connection of temporary and p rmanent power to the site.The temporary power and all hookup costs to be paid by Sub-contractor. 30. IEEE Fall of Potential Tests: Ground tests shall be performed as indicated on drawings.A iddle ground ohmer or the method of using two auxiliary ground rods(as described in IEEE stan d no. 81-1983,part 1)may be used.The IEEE method requires the use of an ac test cun�en�The uxiliary test rods must be sufficiently far away from the rod under test so that the regions in which eir resistaace is localized do not overlap. Sub-contractor shall submit a ground resistance test the Contra�tor for review and approval.After all the external ground rings are tied together but efore the - equipment cabinet is tied down,a megger check of the ground system should be done.All orts shall be made to achieve a 5 OHMS to ground resistance reading.The maximum allowable resistance is 10 OHMS to ground.Where this is not achievable,inform Contractor in writin . 31. Grounding Resistance Test Report:Upon completion of the testing for each site,a test repo showing resistance in OHMS with auxiliary potential electrodes at 5 feet and 10 feet interv s until the average resistance starts increasing and also note t6at 10.15 photos must be taken to p f entire external ground ring system before backfill or notify Contractor no less than 48 hours in ad ance of backfill.Testing shall be completed by Sub-contractor and two(2)sets of test documents to be bound and submitted within one week of work completion. 32. Coaxial Cable Installation: Coaxial cable size shall be installed as shown on the drawings. e _ minimum bending radius for the 7/8"aad 15/8"cable is two feet(2').Coaxial cable suppo .The coaxial cable shall be run in covered cable trays.For short distaaces the coaxial cable may e on bare - nu�s with supports every four feet(4').in horizontal nins,and every three feet(3').in verti 1 nms. The coaxial cable shall be run inside the monopole and supported from Kellum Grips with' the monopole.From the monopole to the Primary Radio Cabinet,the cable shall be supported' covered cable trays.The coaxial cable shall be supported on open waveguides on structural towers. e coaxial cables shall be sealed where the cables penetrate any rooftop,bulkheads,monopole ,and walls. _ . 33. Coaxial cable gounding:The coaxiat cables shall be gounded to a grounding bar at the ante as using the grounding kits as specified on the drawings.The coaxial cables shall be gounded a grounding bar at the Radio cabinet using the grounding kits as specified on the drawings. e coaxial cables shall be gounded to.a grounding bar at the top and bottom of the monopole using the grounding kits as specified on the drawings.The coaxial cables shall be grouaded to a gro d baz at the bulkheads using the grounding kits as spec�ed on the drawings. 34. Coaxial cable sweep testing:After the installation of the antenna system,the coaxial cables coaxial cables shall be sweep tested up to 2000 Mhz.to determine the acceptability of system re loss,the reflection coefficient,and the VSWR. 35. Grounding Electrode System � Grouading Connections a. All underground(below grade)grounding connections shall be made by the"cadweld" cess. Connections shall include all cable to cable splices,Tees,Xs,etc.All cable connections o ground CNS/[TS WEST COMMUNICATIONS ELECTRICAL MATERIALS AND ODS SMMA NO.96419.16 16000-3 17 DEC.96 rods,ground rod splices,and lightning protection system as indicated,All materials used(molds, welding metal,tools,etc.)shall be by"cadweld"and installed per manufacturer's recommendation and procedures: b. All above grade or interior grounding and bonding conductors shall be reconnected by o e hole crimp type(compression)connections for#6 AWG bare copper conductor,and two hole rimp type(compression)connections for #2 AWG bare copper conductor and larger.Mechan cal connections,fitting or connections that depend solely on solder shall not be used.AC se ice electrical ground shall be sized per the NEC with#2 AWG solid tinned copper wire m' ' um. Service ground wire shall be continuos run in an unbroken manner. c: Ground Rods - All ground rods shall be 5/8"diameter x 10'-0"long Copperweld"or approved equal,and s all be of the number aad at locations indicated on the drawings.Ground rods shall be driven full len vertical in undisturbed earth.All ground rods to be 8' apart unless otherwise noted. d. Ground Bars All ground bars shall be '/."thick bare copper plate and of size indicated on drawings. e. Cables All ground cable shall be standard tinned copper and of size indicated on drawings.The type of cable shall be as follows: ' ' Cable Size Cable Type Use of Cable #2/0 AWG Stranded To main ground,i.e.,building steel,cold water pipe,or existing ground rod,and for ' all lightning protection #6 AWG Stranded Grounding of Antenna Cables #2 AWG Stranded Green Insulated Indoor Halo Ring #2 AWG Solid Solid Outdoor Ring Grounds, and all equipment,poles and towers f. Cable Tray Ground all sections of the cable tray as indicated on the drawings. END OF SECTION CNS/[JS WEST COMMUNICATIONS ELECTRICAL MATERIALS AND THODS SIvIMA NO.96419.16 16000-4 17 DEC.96 SECTION 16110-RACEWAYS,CABLE TRAYS,AND gpXES A. PROJECT INCLUDES 1. Electrical conduit,tubing,surface raceways,wireways,cable trays,boxes,and cabine for electrical power and signal distribution. B. QUAI,ITY ASSURANCE 1. National Electric Code NFPA 70. C. PRODUCTS . 1. Wiring Methods: a Exposed Indoor Wiring: Electrical metallic tubing or rigid nonmetallic conduit 6 eet or more above finished floor,galvanized steel conduit below 6 feet above finished fl r. b. Concealed Indoor Wiring: Electrical metallic tubing,electrical nonmetallic tubin or rigid nonmetallic conduit c. Exposed Outdoor Wiring: Intermediate steel condui� d. Concealed Outdoor Wiring: Intermediate steel conduit. e. Underground Wiring,Single Run: Rigid noninetallic conduit. f. Underground Wiring,Grouped: Rigid nonmetallic condui� � g. Connection to Vibrating Equipment: Flexible Metal conduit,liquidtight at exterio 2. Metal Conduit and Tubing: a. Rigid Aluminum Conduit: ANSI C80.5. b. Rigid Steel Condui� ANSI C80.1. c. Intermediate Steel Conduit UL 1242. d. PVC Externally Coated Rigid Steel Conduit and Fittings: ANSI C80.1 and NEMA 1. e. Electrical Metallic Tubing(EM T)and Fittings: ANSI C80.3. f. PVC ExternallyCoated Electrical Metallic Tubing and Fittings: ANSI C80.3 and RN 1. g. Flexible Metal Conduit: iJL 1 zinc-coated steel, h. Liquidtight Flexible Metal Conduit and Fittings: UL 360. . 3. Nonmetallic Conduit and Ducts:' a Electrical Nonmetallic Tubing(E1VT�: NEIVI�,TC 13. b. Rigid Nonmetallic Conduit(RNC): NEMA TC 2 and UL 651,Schedule 40 or 80 P C. c. Underground PVC and ABS Plastic Utilities Duct: NEMA TC 6,Type I for encase burial in concrete,Type II for direct burial. . d. PVC and ABS Plastic Utilities Duct Fittings: NEMA TC 9. e. Liquidtight Flexible Nonmetallic Conduit and Fittings: UL 1660. CNS/US WEST COMMLJMCATIONS RACEWAYS,CABLE TRAYS AND B XES - SMMA NO.96419.16 16110-1 17 D C.96 4. Raceway Accessory Materials: a Conduit Bodies: NEC requirements. b. Wireways: NEC requirements. c. Surface Raceways,Metallic: Galvanized steel,with snap-on covers. d. Surface Raceways,Nonmetallic: Rigid PVC,UL 94. 5. Cable Trays: a Materials:Hot-dip galvanized after fabrication steel. b. Configuration: Ladder type,trough-type,solid-bottom type,channel type. c. Covers: �Solid type, louvered type,and ventilated-hat type. 6. Boxes and Fittings: a. Cabinet Boxes: LTL S0,sheet steel,NEMA 1. b. Pull and Junction Boxes: LTL 50,steel boxes. c. Metal Outlet,Device and Small Wiring Boxes: IJL 514A and OS 1. d. Nonmetallic Outlet,Device and Small Wiring Boxes: NEMA OS 2. END OF SECTION CNS/US WEST COMMUIJICATIONS RACEWAYS,CABLE TRAYS BOXES SMMA NO.96419.16 16110-2 1 DEC.96 SECITON 16119-UNDERGROUND DUCTS AND UTII,TI'y STRUCTi1RES A. PROJECT INCLUDES 1. Underground conduits and ducts,duct banks,pull boxes and handholes,manholes, d other underground utility structures. B. QUALITY ASSURANCE 1. National Electric Code NFPA 70. C. PRODUCTS 1. Underground Duct Applications: a Electrical Feeders: Direct buried rigid plastic conduit. 2. Conduit and Duct: a. Rigid Steel Condui� ANSI C80.1,gaIvanized. b. Plastic-Coated Rigid Steel Conduit and Fittings: NEMA RN 1, c. Rigid Plastic Conduit: NEMA TC 2, Schedule 40 PVC. d. PVC Conduit and Tubing Fittings: NEMA TC 3. e. Rigid Plastic Underground Condui� iJL 651A,Type A PVC. f. Plastic Communication Duct and Fittings: NEMA TC 10. ' 3. Pull Boxes and Handholes a. Cast Metal Boxes: Cast aluminum�,�ri��keted cover with nonskid fmish. b. Fiberglass Handholes: Molded fiberglass with weatherproof cover with nonsk d fmish. 4. Accessories: � a Duct Supports: Rigid PVC. b. Frames and Covers: Cast iron with cast-in legend. c. Sump Frame and�Grate: FS RR F-621,Type VII for frame.and Type I for cov r. d. Components: Pulling eyes in walls,pulling and lifting irons in floor,cable chions, arms and cable support insulators,ladder. END OF SECTION CNS/US WEST COMMUMCATIONS UNDERGROUND DUCTS AND UTILITY UCTURES SMMA NO.96419.16 16119-1 17 DEC.% SECTION 16120-WIRES AND CABLES A. PROJECT iNCLUDES 1. Wires,cables,and connectors for power,lighting,signal,control and related system rated 600 volts and less. B. QUALITY ASSURANCE 1. Compliance: National Electrical Code;UL 4, 83,486A,486B, 854;NEMA/ICEA C-S,WC- 7, WC-8;IEEE 82. C. PRODUCTS . 1. Wire Components: a. Conductors for Power and Lighting Circuits: Solid conductors for No. 10 AW and smaller,stranded conductors for No. 8 AWG and larger. b. Conductor Material: Copper. � c. Insulation: TI�-IN/THyVN for conductors size SOOMCM and larger and No. 8 WG and smaller;THW,TI�IN/THWN or X�II3W insul$bon for other sizes based on 1 'on. d. Jackets: Factory-applied nylon or PVC. 2. Cables: a. Nonmetallio-Sheathed Cable for Lighting Wiring: UL Type NM and NMC. b. Aboveground Service Entrance Cable: LJL Type SE. c. Underground Service Entrance Cable: IJL Type USE. d Underground Feeder aad Braach-Circuit Cable: UL Type UF. e. ControUSignal Transmission Media: Single conductor coaxial type with polye ylene core;twisted pair,direct.burial,aerial,plenum and video types. 3. Connectors: UL listed solderless metal connectors with appropriate temperature rat' . END OF SECTION CNS/US WEST COMMiJNICATIONS WIRES CABLES SMMA NO.96419.16 16120-1 17 DEC.96 SECTION 16140-WIItING DEVICES A. PROJECT INCLUDES 1. Wiring devices for electrical service. B. QUALITY ASSURANCE 1. Compliance: National Electrical Code,NEMA WD 1,LJI,, END OF SECTION - CNS/tTS WEST COMMUNICATIONS WIRING EVICES SMMA NO.96419.16 16140-1 1 DEC.% SECTION 16400-SERVICE AND DLSTRIBUTION A. PROJECT INCLUDES � 1. Electrical service and distribution including service entrance,switchboards,low-vol ge power switchgear,grounding,transformers,busways,panelboards,overcurrent protective vices. 2. Service and Distribution Requirements: The incoming service shall be rated at 100 ps, single phase,3 wire,either 208 VAC or 240 VAC. B. PRODUCTS 1. Service Entrance: a. Circuit Breakers shall be rated for a minimum interrupting capacity of 10,000 I.C. b. Fuses: Time-delay,fast-acting,cun�ent-limiting types. c. Meter Sockets: Acceptable to local utility company. d. Switches: Heavy-duty safety switches with NEMA Type 1 enclosure. 2. Grounding: a Grounding Equipment: UL 467;copper conductors;NEC Table 8 wire and cabl conductors;connectors. b. Gmunding Electrodes: Copper-clad steel ground rods;copper plate electrodes. END OF SECTION CNS/C1S WEST COMMUNICATIONS SERVICE AND DIS UTTON SIvflvIA NO.96419.16 16400-1 1 DEC.% SECTION 16452-GROUNDING A. PROJECT INCLUDES 1. Submittals: Submit report of field tests and observations. 2. Electrical Component Standard: NFPA 70, 'Tiational Electrical Code" for compone and installation. 3. LTL Standard: tTL Standard 467, "Grounding and Bonding Equipment." B. PRODUCTS 1. Manufacturers: Subject to compliance with requirements,provide products by the fol owing: a. Anixter Bros.Inc. b. Bashlin Industries,Inc. c. Buckingham Mfg.Co. d. Cam-Lok,Inc. e. A.B.Chance Co. f. Dossert Corp. g. Engineered Products Co. h. Erico Products,Inc. i. Galvan Industries,Inc. � . j. GB Electrical,Inc. k. General Machine Products Co.,Inc. 1. Hastings Fiber Glass Products,Inc. m. Ideal Industries,Inc. n. Kearney-National. o. McGill Mfg. . p. O-ZJGedney Co. • q. Raco,Inc. r. Thomas&Betts Corp. s. Utilco Co. � W.H.Salisbury&Co. 2. Crounding and Bonding Products: Types as indicated. Where types, sizes, rati gs, and quantities indicated differ from NEC requirements, the more stringent requirements and the greater size,rating,and quantity indications govern. 3. Conductor Materials: Copper. . a Where aluminum conductors are used for power wiring, use aluminum for unding system conductors(except provide copper for those insulated and uninsulated co ductors in direct contact with earth,concrete,or crushed stone). CNS/tJS WEST COMMUI�IICATIONS GRO ING SNIINA NO.96419.16 16452-1 17 EC.% 4. Wire and Cable Conductors: Comply with Divisiott 16 Section "Wires and Cables." Conform _ to NEC Table 8,except as otherwise indicated,for conductor properties,including ding. 5• Equipment Grounding Conductor. Green insulated. 6. Grounding Electrode Conductor: Stranded cable. 7• Bare Copper Conductors: Conform to the following: a Solid Conductors: ASTM B-3. b. Assembly of Stranded Conductors: ASTM B-8. c. Tinned Conductors: ASTM B-33. 8. Ground Bus: Bare annealed copper bars of rectangular cross-section. 9. Braided Bondiag Jumpers: Copper tape, braided from No. 30-gage bare copper ire and terminated with copper ferrules. 10. Bonding Strap Conductor/Connectors: Soft copper, 0.05 inch thick and 2 inches wid , except as indicated. 11. Connector Products: Listed and labeled as groundirig coanectors for the materials wi which used. 12. Pressure Connectors: High-conductivity plated units. 13. Bolted Clamps: Heavy-duty units listed for the application. 14. Exothermic Welded Connections: Provided in kit form and selected for the specifi types, sizes,and combinations of conductors and other items to be connected. 15. Aluminum-TaCopper Connections: Bimetallic type, conforming to UL 96, "L ghtning � Protection Components,"or_UL 467. 16. Ground Rods: Copper-clad steel,3/4 inch by 10 feet,minimum. 17. Plate Electrodes: Copper plates,minimum 0.10 inch thick,size as indicated. C. EXECUTTON 1. Equipment Grounding Conductor Application: Comply with NEC Article 250 for si s and quantidw uf equipment grounding conductors, except where lazger sizes or more con uctors are indicated. Apply equipment ground conductors in accordance with the following: a. Install separate insulated equipment grounding conductors with circuit conductors where indicated in addition to those locations where required by Code: CNS/tJS WEST COMMIJI�TICATIONS GRO ING SMMA NO.96419.16 16452-2 17 C.96 b. Busway Circuits: Install separate insulated equipment ground conductor from the ground bus to the equipment ground bar terminal on the busway. c. Nonmetallic Raceways: Instail an insulated equipment grounding con uctor in nonmetallic raceways except as otherwise indicated or unless they are desi ated for telephone or data cables. d. Metal Piping Equipment Circuits: Install a separate insulated equipment ounding conductor to electrical devices conne�ted to metallic piping systems aad opera ' g at 120 V and above, including pumps, heaters,heat tracing,and surface aatifrost hea g cable. Bond the cottductor to each such unit and to the piping. 2. Underground Conductors: Bare,tinned,stranded copper except as otherwise indicated 3. Signal and Communications: For telephone, alarm, and communication systems, pro ide a#4 AWG minimum green insulated copper conductor in racevvay from the grounding lectrode system to each terminai cabinet or central equipment location. 4. Separately derived systems required by NEC to be grounded shall be grounded as app oved by the authority having jurisdiction. 5. Installation, General: Ground electrical systems and equipment in accordance w NEC except where grounding in excess of NEC requirements is iadicated. 6. Electrical Grouad Bus: Size, location, and amangement as indicated. Space 1 inch m wall and support from wa116 inches above finished floor,except as otherwise indicated.. �• Cn'°und Rods: Locate a minimum of one-rod length from each other and at least e same distance from any other grounding electrode. Interconnect grouad rods with bare co ductors buried at least 24 inches below grade. Connect bare-cable ground conductors to gro d rods by means of exothermic welds except as otherwise indicated. Make these connections 'thout damaging the copper coating or exposing the steel. Drive rods until tops are 6 inche below finished floor or final grade except as otherwise indicated. 8. Grounding Electrode Conductor. Provide insulated copper conductor, sized as indic ted, in conduit Bond the ground conductor conduit to the conductor at each end Where a di lectric fittiag is installed in the main metallic water service pipe, connect tlie ground conducto to the street side of the fitting. Do not install a grounding jumper around dielectric fittings. B nd the ground conductor conduit to the conductor at each end. 9. Braided-Type Bonding Jumpers; Install to connect grouad clamps on water meter pi ing to electrically bypass water meters. Use elsewhere for flexible bonding and gto ding connections. I0. Route grounding and bonding conductors using the shortest and straightest paths ssible . without obstcucting access or placing conductors where they may be subjected to in, impact,or damage,except as indicated. CNS/US QVEST COMMUMCATIONS GRO iNG S1�91�lA NO.96419.16 16452-3 17 D C.% _ 11. UFER Ground; Fabricate with 20 feet of conductor laid lengthwise in exca ation for foundation or footings. Install so conductor is within 2 inches of the bottom of th concrete. Where base of foundation is less than 20 feet in lengt6, coil excess conductor base of foundation. Bond conductor to reinforcing steel at four locations,minimum. Extend nductor below grade and connect to building grounding grid, grounding electrode con uctor, or grounding electrode. 12. Connections: Make connections in such a manner as to minimize possibility of galv ic action or electrolysis. Select connectors, connection hardware, conductors, and connectio methods so metals in direct contact will be galvanically compatible. a. Use electroplated or hot-tin-coated materials to assure high conductivity and m e points of contact closer in order of�lvanic series. b. Make connections with clean bare metal at points of contact c. Aluminum to steel connections shall be with stainless steel separators and m chaaical clamps. d• A1���m to 8alvanized steel connections sha11 be with tin-plated copper j rs and mechanical clamps. � e. Coat and seal connections involving dissimilaz metals with inert material su as red lead paint to prevent penetiration of moisture to contact surfaces. 13. Exothermic Welded Connections: Use for connections to stiuctural steel and for und rground . connections except those at test wells. Install at connections to ground rods d plate � electrodes. Comply with manufacture�s written recommendations. Welds that are p ffed up , or that show convex surfaces indicatiag improper cleaaing are not acceptable. 14. Tighten grounding and bonding connectors and terminals, including screws and lts, in accordance with manufacture�'s published torque dghtening values for connectors bolts. Where manufacturer's torquing requi��ents are not indicated, tightett connections to comply � with tightening torque values specified ia LTI,4g6A and UL 486B. 15. Compression-Type Conne�tions: Use hydraulic compression tools to provide the correct circumferential pressure for compression connectors, LTse tools and dies recommende by the manufacturer of the connectors, provide embossing die code or other standard method make a visible indication that a connector has been adequately compressed on the conductor. 16. Moishue Protection: Where insulated conductors are connected to ground rods or ouad buses, insulate the entire area of the connection and seal against moisture penetration of the insulation and cable. 17. Tests: Subject the completed grounding system to a megger test at each location ere a ma�cimum gruund resisrtance level is specified,at service disconnect enclosure ground te inal, aad at ground test wells. Measure ground resistance without the soil being moistened y any means other than natural precipitation or natural drainage or seepage and without ch mical treatrnent or other artificial means of reducing natural ground resistance. Perform tests y the CNS/US WEST COMMiJNICATTONS GRO ING SMMA NO.96419.16 16452-4 17 D C.% 2-point method in accordance with Section 9.03 of IEEE 81, "Guide for Meas g Earth Resistivity,Ground Impedance and Earth Surface Potentials of a Graunding System." a. Ground/resistance maximum values shall be as follows: 1. Equipment rated 500 kVA aad less: 10 ohms. 2. Equipment rated 500 kVA to 1000 kVA: S ohms. 3. Equipment rated more than 1000 kVA: 3 ohms. 4. Unfenced substations and pad-mounted equipment: 5 ohms. 5. Manhole grounds: 10 ohms. b. Deficiencies: Where ground resistances exceed specified values,and if direc modify the grounding system to reduce resistance values. Where measures are d' d that exceed those indicated the provisions of the Contract,covering changes will app y. c. Report: Prepare test reports, certified by the testing organization, of th ground resistance at each test location. Include observations of weather and other ph nomena that may affect test results. Describe measures taken to improve test results. END OF SECTION CNS/[JS-WEST COMMLTNICATIONS GRO ING SMMA NO.96419.16 16452-5 17 EC.%