HomeMy WebLinkAboutBoulder wall info � � CIVIL DESIGN � � ��� �= � } t. � ." b � «�"� �_ i Ll; I� MEMORANDUM CITY OF ORONO DATE: July 22, 2011 TO: Jim Lillesve—Charles Cudd De Novo, Inc. FROM: Tim Hatten—Civil Design Professionals RE: 3315 Graham Hill Road Boulder Retaining Wall (1 1-110) Orono, Minnesota Design Assumptions: Boulder Wall, Minimum 15° Wall Batter Safety Factors Coulomb Earth Pressure Design Analysis Live Load: 150 PSF (Driveway) Slidin 1.50 Dead: Load: None Overturnin 1.50 Toe Slope: None Bearin 2.00 Back Slope: None Soil Design Properties: � y c Retained Soil 26° 120 PCF 0 (Onsite Soils) Foundation Soil 26° 120 PCF 0 (Onsite Soils) Notes: Soils information was provided by Jim Lillesve of Charles Cudd De Novo, Inc. for this preliminary design. The onsite material is assumed to be a Clayey Sand with an internal friction angle of 26°. Where unsuitable soils are found, a subcut may be required and structural fill shall be placed and compacted to provide an adequate bearing foundation. CDP shall be contacted if the above soil strength parameters can not be met and a redesign may be required Wall layouts and elevations obtained fram Certificate of Survey prepared by Acre Land Surveying dated 7.6.201 l. See project specifications for additional information and reguirements. We appreciate the opportunity of providing services to you. If you have any questions or comments regarding this project, please feel free to contact us. Civil Design Professionals • 8609 Lyndale Ave. S., Suite 200 Bloomington, MN 55420 • Ofiice 612-284-3696 • www.cdp-us.com � � CIVIL DESIGN . ;,��� � i �U 12 �' �. a � E � � � c� � �. �. s CITY OF ORONO DESIGN CALCULATIONS FOR 3315 GRAHAM HILL ROAD ORONO, MINNESOTA (PROJECT # 11-110) SUBM�TTED BY: Tim Hatten July 22, 2011 I HEREBY CERTIFY THAT THIS PLAN, SPECIFICATION, OR REPORT WAS PREPARED BY ME OR UNDER MY DIRECT SUPERVI N AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDE WS OF TA OF MINNESOTA DATE• �Ia�/ �I TIS J. CHS,P.E. LICENSE NO.48216 Civ!!Deslgn Professiona/s • 8609 Lynda/e Ave.5.,Suite 200 B/oomington,MN 55420 • Office 612-284-3696 • www.cdp-us.com 1`ii�� � ' �` ' � � ' ' { � ;� (�.I�7I.L DESIGN ::�� � . � _ _ . _ _ , ,a � ti_ � ��, � t� > > PROJECT: 3315 GRAHAM HILL ROAD PROJECT NO: 11-110 SHI:F,T: 1 OF 3 NO BACK SLOPE, 150 PSF MAXIMUM LIVE LOAD LOCATION: ORONO, MINNESOTA BY: TPH DATE: 7/22/2011 A.GE�ERAL DESIG\DATA Boulder.p= 140 pcf Wall Batter,i= 15.0 degrees Design Height,H= 8.0 ft(design height+embedment) Backslope,(3= 0.0 degrees Surcharge,q= 150.0 psf FS Sliding> 1.5 FS Overturning> 1.5 Bearing> 2.0 B.SOIL PARA�IETERS cb(deg) c(ps� y(pc� Retained Soil 26 0 120 Foundation Soil 26 0 120 C.GEOVIETRIC PARA3IETERS cb= 26 degrees a= 105 degrees(90°+i) �3= 0.0 degrees S= 17.3 degrees(2/3*�) D.COL'LO�iB EARTH PRESSURE CALCULATIONS ka= 0.25 s in'(a +�) � �� 2 Pa= 0.5 H k �� ) ��_�) � Pa= 966 a lbs/ft sinZa •sin(a —S) �+ sin +S sin sin(a —6)sin(a +Q) Pq= qHka Pq= 302 Ibs/ft E.EXTER\AL STABILITY � 1.OVERTURNING Overturning Moment Wn,1 8/�`lER . Mo= Pa(H/3)+Pq(H/2) ^'� � Mo= 3784 ft lbs Resisting Moment ,-- H=Design Height(ft) � D=Depth of Boulder(ft) � L=Distance from overturning __l_._ _..�__ __. point to centroid(ft) � ...__........__y.__.._..._"_� Figure 1�External 5tabiliry Diagram 8609 Lyndale Avenue S, Suite Z00� Bloomington,MN 55420 Office: 612-284-3696 Website:www.cdp-us.com ,.:, �' , � ' �IVIL DESIGN I � � �� �� _. ' .. . ::' � �' �w � � 1a � ' � �b i PROJECT: 3315 GRAHAM HILL ROAD PROJECT NO: 11-ll0 SHEET: 2 OF 3 NO BACK SLOPE, 150 PSF MAXIMUM LIVE LOAD LOCATION: ORONO, MINNESOTA BY: TPH DATE: 7/22/2011 Boulder H D L p MR Wall (ft) (in) (ft) (pc� t s 1 8.00 34.0 2.49 140 7896.7 MR= 7896.7 frlbs FS Overiurning= MR/Mo FS Overturning= 2.09 >1.5 OK 2.SLIDING - Sliding Resistance - Determine Area of Mass B]ockArea= 22.7 sf - Determine Weight of Mass (RF� VF = Boulder Area*p VF = 3173 lbs/ft RF =VFTan(33)+109(Lab Testing) RF = 2170 lbs/ft FS Sliding= RF/(Pa+Py) FS Sliding= 1.71 >1.5 OK 3.BEARING PRESSURE - Eccentricity e=D/2-(Mx-Mo)�F e= 0.12 e < D/6 - Applied Bearing Pressure(under bottom boulder) qm�= for non-eccentric footing-VFlD qm�= for e<D/6-VF/D*(1+6e/D� 9m�= for e>D/6-4*VF/(3*(D-2*e)) qm�= 1406.3 psf 8609 Lyndale Avenue S, Suite 200� Bloomington,MN 55420 Office: 612-284-3696 Website:www.cdp-us.com ���`} ' " ��-' �IVII.DESIGN ��- � � � - , ,; A � , E� � . � ,�—' i � , , �_{- �.� �� } ��? � � : ., ,, PROJECT: 3315 GRAHAM HILL ROAD PROJECT NO: 11-110 SHEET: 3 OF 3 NO BACK SLOPE, 150 PSF MAXIMUM LIVE LOAD LOCATION: ORONO, MINNESOTA BY: TPH DATE: 7/22/2011 4.BEARING CAPACITY(Terzaghi Bearing Capacity-under bottom boulder) q'=cN�+qNq+O.SyDN� where: N�= 27.09 Nq= 14.21 Ny= 9.84 c= 0.0 psf(cohesion) Df= lA ft(embedment depth) q= 120.0 psf(y*D� D'= 2.6 ft(D-2*e) q'= qw�= 3235.5 psf FS Bearing= q'/qmax FS Bearing= 2.30 >2.0 OK 8609 Lyndale Avenue S,Suite 200 �Bloomington,MN 55420 Office:612-284-3696 Website:www.cdp-us.com .�{.� � , t_ , , ,_ _; ; �IVIL DESIGN Fr, , � � ; ��1 1_ _ � ��' �:' ��3 ,~� � �.� i-, n`°� �� :�; PROJECT: 3315 GRAHAM HILL ROAD PROJECT NO: 11-110 SHEET: 1 OF 3 NO BACK SLOPE, 150 PS1=MAXIMUM LIVE LOAD LOCATION: ORONO, MINNESOTA BY: TPH DATE: 7/22/2011 A.GENERAL DESIG'�DATA Boulder,p= 140 pcf Wall Batter,i= 15.0 degrees Design Height,H= 7A ft(design height+embedment) Backslope,(3= 0.0 degrees Surcharge,q= 150.0 psf FS Sliding> 1.5 FS Overturning> 1.5 Bearing> 2.0 B.SOIL PARAMETERS cn(deg) c(ps� y(pc� Retained Soil 26 0 120 Foundation Soil 26 0 120 C.GEOMETRIC PARA�IETERS d�= 26 degrees a= 105 degrees(90°+i) (�= 0.0 degrees S= 17.3 degrees(2/3*d�) D.COULOMB EARTH PRESStiRE CALCULATIONS ka= 0.25 sin'(u +�) k, _ Pa= O.SyH`ka sin�a •sin(a —fi)• �+ sin(�+d)sin(�—�i) Pa= 740 lbs/ft � sin(a -8)sin(a +Q)� Pq= qHka Pq= 264 lbs/ft E.EXTER�AL STABILITI' — 1.OVERTURNING Overturning Moment WA�_l 8A'lFR Mo= Pa(H/3)+Pq(H/2) ^'� Mo= 2651 fr lbs � -- Resisting Momen[ � -- H= Design Height(ft) � � � D= Depth of Boulder(ft) � � — � L= Distance from overtuming _l__. � __ _________ point to centroid(ft) �� �� � Figure l:External Stability Diagram 8609 Lyndale Avenue S, Suite 200� Bloomington,MN 55420 Office:612-284-3696 Website:www.cdp-us.com ( ' �`� .2 . '--� r ' ; , ; �IVIL DESI�N : ' � 1l7I � .. � .. ._. . _ . `� , ��ri �." J � i, �. �; �� �> � t a�' . �_ f:= PROJECT: 3315 GRAHAM HILL ROAD PROJECT NO: 11-110 SHEET: 2 OF 3 NO BACK SLOPE, 150 PSF MAXIMUM LIVE LOAD LOCATION: ORONQ MINNESOTA BY: TPH DATE: 7/22/20ll Boulder H D L p MR Wall (ft) (in) (ft) (pcfl t� s 1 7.00 31.0 2.23 140 5644.3 MR= 5644.3 ft�lbs FS Overturning= MR/Mo FS Overturning= 2.13 >1.5 OK 2.SLIDING - Sliding Resistance - Determine Area of Mass Block Area= 18.1 sf - Determine Weight of Mass (RF� VF = Boulder Area*p VF = 2532 lbs/ft RF =VFTan(33)+109(Lab Testing) RF = 1753 lbs/ft FS Sliding= RF/(Pa+Pq) FS Sliding= 1.75 >1.5 OK 3.BEARING PRESSURE - F,ccentricity e=D/2-�Mx-Mo)�e e= 0.11 e < D/6 - Applied Bearing Pressure(under bottom boulder) qm�= for non-eccentric footing-VF/D qm�= far e<D/6-VF/D*(1+6e/D� 9,„�= for e>D/6-4*VF/(3*(D-2*e)) qm3= 1228.6 psf 8609 Lyndale Avenue S, Suite 200� Bloomington,MN 55420 Office: 612-284-3696 Website:www.cdp-us.com T31_� � � j ... _, ; __ �_�: �IVIL DESIGN � � , � . — ��-� �-�� �� �� � ( a� - �<, � � .��,�` � ��. �. .,�,..i..f_i 1 I _IJ ` v P-ti �5 F�� §_. .ro . s. .. . _ �. PROJECT: 3315 GRAHAM HILL ROAD PROJECT NO: 11-110 SHEET: 3 OF 3 NO BACK SLOPE, 150 PSF MAXIMUM LIVE LOAD I,OCATION: ORONO, MINNESOTA BY: TPH DATE: 7/22/2011 4.BEARING CAPACITI'(Terzaghi Bearing Capacity-under bottom boulder) q'=cN�+qNq+O.SyDN� where: N�= 27.09 Nq= 14.21 NY= 9.84 c= 0.0 psf(cohesion) D�= 1 A ft(embedment depth) q= 120.0 psf(y*D� D'= 2.4 ft(D-2*e) 4'= q„i�= 3101.5 psf FS Bearing= q'/qmax FS Bearing= 2.52 >2.0 OK 8609 Lyndale Avenue S,Suite 200� Bloomington,MN 55420 Office:612-284-3696 Website:www.cdp-us.com � GENERAL NOTES: GEIdERAL NOTES: DESIGN PROVISIONS: SUGGESTED QUAL.ITY ASSURANCE PROVISIONS: 1. THE FOLLOWING EFFECTNE STRENGTH PARAMEfERS WERE ASSUMED IN THE PREPARATION OF THE STRUCTURAL CALCULATIONS FOR THE 2. THE FOUNDATION SOILS AT THE BASE OF THE WALL SFtALL BE 80ULDER RETAtNING WALL SYSTEM: INSPECTED BY THE GEOTECHNICAL ENGINEER. ANY UNSURABLE SOILS OR IMPROPERLY COMPACTED EMBANKMENT MATERIAL SHALL BE REMOVED AND REPLACED AS DIRECTED 8'Y THE ENGINEER � C 'Y SOIL TYPE CAPACCTY AND M N�MIZE SETT'LEMENT ROViDE ADEQUATE BEARING REfAINED SOIL 26' 0 PSF 120 PCF CLAYEY SAND 3. ALL WALL IXCAVATION AND RETAINED SOILS SHALL BE INSPECTED FOUNDATION SOIL 25 0 PSF 120 PCF CLAYEY SAND FOR GROUNDWATER CONDfTIONS. ANY ADDITIONAL DRAINAGE PROVISIONS REQUIRED IN THE FlELD SHALL BE INCORPORATED INTO THE WALL CONSTRUCTION AS DIRECTED 8Y THE GEOTECHNICAL SOIL lYPES AND DESIGN PROPERTIES SHALL BE CONFlRMED BY ENGINEER. THE SITE GEOTECHNICAL ENGINEER PRIOR TO WALL CONSTRUCTION. S H EET I N D EX 4. WALL BACKFlLL MATERIAL SHALL BE TESfED AND APPROVED BY THE 2. THE WALL IS DESIGNED TO SUPPORT THE FOLLOWING MAXIMUM SHEET DESCRIPTION ENGINEER, MEETING THE MINIMUM REQUIREMENTS OF THE SURCHARGE LOADIN�S: APPROVED DESIGN PIANS OR SPECIFlCATIONS. LIVE LOAD: 150 PSF 1 TITLE SHEET 5. ALL SOIL BACKFlLL SHALL BE TESTED BY THE GEOTECHNICAL DEAD LOAD: NONE 2 SITE PLAN ENGINEER FOR MOISTUR" DENSITY, AND COMPACTION PERIODICALLY BACK SLOPE: NONE 3 TYPICAL WALL SECTION (EVERY 2' VERTICALLY. 100'-200' C/C) MEETING THE MINIMUM SEISMIC: NOT APPLICABLE REQUIREMENTS OF THE APPROVED DESIGN PIANS OR HYDROSTATIC: NOT APPUCAB�E SPECIFlCATIONS. 3. THE FOUNDATlON SOILS AT THE WALL LOCATIONS SHALL BE 6. THE CONTRACTOR SHALL ESTABLJSH AND MAINTAIN QUALITY CAPABLE OF SAFELY SUPPORTING 1,550 PSF WITHOUT FAILURE OR CONTROL FOR THE CONSTRUCTION OF THE WALL TO ASSURE EXCESSIVE SETTL.EMENT. LOCAL BFARING CAPACIIY SHALL BE COMPLUWCE WITH CONTRACT REQUIREMENTS AND MAINTAIN CONFlRMED BY THE SITE GEOTECHNICAL ENGINEER AFfER RECORDS OF RS QUALITY CONTROL FOUNDATION EXCAVATION AND PRIOR TO WALL CONSTRUCTION. 7. ALL WALL EI.EVATIONS, GRADES, AND BACK SLOPE CONDI110NS SUGGESTED QUALITY ASSURANCE PROVISIONS: SHALL BE VERIFlED BY THE ENGINEER IN THE FlELD FOR CONFORMANCE WITH APPROVED DESIGN PLANS. ANY REVISIONS TO 1. WALL CONSTRUCTION SHALL BE SUPERVISED 8Y A QUALIFlED THE STRUCTURE GEOMEIRY OR DESIGN CRITERIA SHALL REQUIRE ENGINEER OR TECNNICIAN TO VERIFY FlELD AND SITE SOIL DESIGN MODIFlCATIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. CONDITIONS. IF THIS WORK IS NOT PERFORMED BY THE SITE GEOTECHNICAL ENGINEER, A QUALIFlED GEOTECHNICAL ENG�NEER/TECHNICIAN SHALL BE CONSULTED IN THOSE MATTERS PERTAINING TO THE SOIL CONDITIONS AND WALL PERFORMANCE. ,_�;�� ;, � �.� �� CITY OF ORONO conrwcrtr (c> zo„ er crn�o�cN �o�sswwa.s � �_ � �9^� BY• �1� R°�°� NO' I heroby certify that thia plan, apectflcaUon, or report �+�_L;_ No. Dats Revision TpH 48216 was pro arod by me or under diroet superviaion and � J' �IVIL ESIGN � 3315 GRAHAM HII.L ROAD thut I �y ' e P e onoi Eng�neer under F ,1 j �,; ORONO, MINNESOTA �olect No: �a , a �,eo �, 2 t� �� �i�; � RC) �' l1S SI � '`,ti � 1_ S 3 N/A II-IIO . ` 8609 LYNDAI.E AVENUE SOVIH,SU1TE 200 r�' / / BLOOMINGfON,MQ�INESOTA 55420 4 ��' T I T L E S H E E T �� �� Da�a' ��� 1' PHONE:(612)2P4M96 5 22 JULY 2011 I Cll J. DEfiCF10� P.E. WEBSTTE�VJ��W.CDP-liS.COM 6 NOTES: 1. THE SITE PLAN SHOWN IS FOR ILLUSTRATNE PURPOSES ONLY. IT WAS REPRODUCED FROM ACRE LAND SURVEYING � CERTIFlCATE OF SURVEY FOR 3315 GRAiiAM HILL ROAD DATED 0 30 60 90 07-06-2011. 2. THE CONTRACTOR SHALL VERIFY INVERTS OF PROPOSED AND '<OFS/GNppOFE`'�'orpy GRAPHIC SCALE IN FEET EXISTING UT1LffIES TO ENSURE THERE ARE NO CONFUCTS. THE ENGINEER SHALL BE CONTACTED IF CONFUCTS ARISE AND AN ALTERNATNE DESIGN MAY BE REQUIRED. / t,� �� �'o.,.,��o ..... Hi►c�ir•\ °;�g � �j ` : � � 1022.Z ' �': ��:. \ s. ......JO??.PW�E4� ��/ / 102�.E .'•. 1�� � 1Q?6.4 y �,..'(��..• � ��'•. �j, '�% eaoce ' cd'���•� ...� `.4\'': \ .,�o C' � / ++ �ati.� ,,,02'w;.' '� eoxto �, �oz�t Q� � \ 1023.9 ' ` � � x ` ! 80)t4 �1d26.7' � x x ' 1014.9 �' iff�7.9� .' a � 1Q23.9 ., � PINEtO u� �4 ��. •� , �NAP4'«.» �4 �7 � B07Co �•.,. 1027.2 ,r,,,�42� ,! O \ ' '� '•.,\g '�o . �' �' � � \ Cj • 70?23 �4 '�` � � S � jott.e �i. 60�c1{ � �O ..... N 1021.9 � � M 1019.0 ?$•. �P 1022. � � x � 101S.a� ' 1GQ8.6 1�p.p %+.� 10?4.4 o � � x1023.1 1D24.4 � �.. •�0��'....:.: , 101a. � i• � MAP4 . x ` � � , ��...�• _ : .i1� �► �N W �---"""� r,`� '°r► �,�� �F' `'' -D� � � `a' , g, � �,� .. � ���. ''�. -� oJ�� :��� o � . •' o ij. ' �` ��� . � .. x . O �,• ,,• : �3 ,ozs.s �az3.s 1 s ,� ;�� ,.f.- ��...,� .� 1 N�wss � �•ti, .•�� � -_ j g ' �� .:�QZ.�.'..:..,.;:... ��� �_ 2.�� �� � �� . 1 .5 ���" ,.. '••.. `-: �,w�!.Y� � � � ...... .....;��21 I . ., - '�� , iQ21.4 o�s � .� �����....L.tr �%; i� 1QTt.4 o �� �j,�;. .'�'� � .� �..�..�.- ��7.�' ~ x 1021.Q ! �g 4� �0 �., �� $,`� -' "� x10�20�f j �4; •�� , ~.�`�G �8� �� � /'/ 1t1.E80X�'ti..... ..�.. !�" �j, 'op e f020.,Z�••''.� /' l � ••x 101Z.4 ''•.,, ,� ,...... "'N+� ��� •• �ti pr y+ .. �..�.� � 1019.1 �'., 1020.4 w 167Q.5 � ��j X •�~•. �� >: _ �, 1Q1&3 4. / x ����� .... .... l � �'x.trn2o '�1 `''� �'oi 1`� �p�...... •� , s.� . .......... .�o�$� :iCikf.O �j �7 �. '•• xtOf&b.., � '•• _ ' -- � i� � g� ���'•���•.. ........................... ......, ot t�3s ........ , ... � � ,m�.�� �ro ���,� ..k.,�,.p.. x,o,�.4� ...... ;� 16 CITY OF ORONO J,� , •�"''+., �.. .... .....�� ..... '•y COpYRIGffT(c) 2011 BY CIVIL D61GN PROFESSIONALS r7,.,_r_:.,, _.___,-� Daagned By: Projeet Regietratlon No: � PeC P° �+�j�i�-= � No. Date Revi�ion 48216 � hOf° �' that this an, s ification, or re rt CIVIL DESIGN TPH waa p o y me o u diroct aupervi�ion and . .-- �a � 3315 GRAHAM HILL ROAD thct a d ly 'ce se rofe ional Engineer under � � -� �a; ORONO, MINNESOTA Projeet No: �e s of t of inne�o a. "�.L;1�'���a r' I: C� F f: � ti I O ti ,� L ;; 3 r = 3�, ii-iio 86041YNDALEAVENUE SOU'T'F�I,SUffE 200 �a� BLOOMWGfON,MINNESOTA55420 `' °ate� SITE PLAN �"°`"°� �e? � rr�oweteinza+wac 5 22 JULY 2011 NEllSITEWWW.CDP-US.COM 6 CurG J. Deriche, P.E. BOULDER DEPTH SCHEDULE: CONSTRUCTION NOTES: W� HEIGHT (H): MIN1MllM 60U1�ER DEPTH (D): �. THE SECTION SHOWN REPRESENTS TYPICAL CONSTRUCTION FOR THE 9. THE BOULDERS SHALL BE PLACED TO AVOID CONTINUOUS JOINT BOULDER WALL AT 3315 GRAHAM HILL ROAD. THE WALL HEIGHTS, PLANES IN VERTICAL OR LATE�ZAL DIRECTIONS. BOULDERS SHALL BE 0 — 5' ------------- 25" ELEVATIONS, BACK SLOPES, AND TOE SLOPES VARY AS SHOWN ON STAGGERED TO INTERLOCK WITH ADJACENT ROCKS. EACH BOULDER 6� ------------- 28p THE SITE PLAN AND ELEVATIONS PLANS RESPECTIVELY. SHALL BEAR ON AT LEAST TWO ROCKS BELOW IT, WITH GOOD �� _____________ 31" FLAT—TO—FlAT CONTACT. g' ------------- 34" 2. UPON EXCAVATION, WHERE UNSUfTABLE SOILS ARE FOUND, SUBCUT TO DEPTH AS REQUIRED BY THE ONSITE GEOTECHNICAL ENGiNEER AND 10. DO NOT BRING HEAVY COMPACTION OR PAVING EQUIPMENT WITHIN 3' REPLACE WITH SUITABLE COMPACTED STRUCTURAL FILL TO ACHIEVE OF THE BACK OF THE PROPOSED BOULDER REfAINING WALL. THE REQUIRED BEARING CAPACITY. THE STRUCTURAL FlLL SHALL BE COMPACTED TO A MINIMUM 9596 STANDARD PROCTOR DENSITY. 11. THE BOULDER WALL IS DESIGNED AS A GRAVITY WALL: MINIMUM SAFETY FACTOR FOR OVERTURNING 1.5 3. APPROXIMATE LIMITS OF EXCAVATtON VARIES WHERE SUBCUT IS MINIMUM SAFEfY FACTOR FOR SUDING 1.5 DRAINAGE STONE SPECIFICATION: REQUIRED. ACTUAL UMffS, AND SIDE SLOPES TO BE DETERMINED BY MINIMUM SAFEfY FACTOR FOR BEARING 2•� CONTRACTOR AND MATCH FlELD CONDITIONS AND OSHA REGULATIONS. DRAINAGE STONE SHALL CONSIST OF CLEAN 1" MINUS 4. ALL WORK AND MATERWLS SHALL COMPLY WITH ALL STATE, COUNTY, 12. PLACE A 4" DIA CORRUGATED PERFORATED PVC DRAINTILE WfTH SOCK CRUSHED STONE MEEfING THE FOLLOWING GRADATION: AND Clll' REGULATIONS AND CODES AND OSHA STANDARDS. AT THE FINISHED GRADE OF THE WALL AS SHOWN. OUTIET AT LOW SIEVE SIZE: % PASSING POINTS ALONG WALL. �« 100 5. THE WALL SHALL BE CONSTRUCTED WITH BOULDERS THAT ARE SOUND, 3/4" 100-75 NARD, AND DURABLE USING A MINIMUM 15' SETBACK. 13. A GEOTEXTfLE FABRIC SHALL BE PLACED WHERE THE BOULDER WALL No. 4 0-10 ABUTS TO THE HOUSE FOUNDATION AS SHOWN ON THE SITE PLAN No. 50 0_5 6. THE MINIMUM BOULDER DEPTH (D) IS A FUNCTION OF THE OVERALL (SHEET 2). OVERIAP ALL ABUTMENT JOINTS 24" WITH A MINIMUM I WALL HEIGHT AS SHOWN IN THE BOULDER DEPTH SCHEDULE. A 48" WIDE FABRIC TO PREVENT THE COREFlLL AND BACKFlLL FROM SMALLER BOULDER MAY BE USED AS A TOP BOULDER (D/2) FOR MIGRATING THROUGH THE ABUTMENT JOINTS. I� FREE DRAINING SAND IS ALSO ACCEPTABLE FOR THE FlNISHED GRADING PURPOSES. I DRAINAGE MATERIAL. IT MUST HAVE <1095 FlNES 14. CNIL DESIGN PROFESSIONALS SHALL NOT BE LIABLE FOR CONTRACTOR PASSING THE N0. 200 Sl�l/E. ONSITE MATERIAL IS 7, TF{E WALL EMBEDMENT SHALL BE A MINIMUM OF 1.0'. NEGLIGENCE. ACCEPTABLE IF IT MEEfS THIS CRITERIA. 8. THE BACKFlLL MATERIAL SHALL BE PLACED WITH A MAXIMUM OF 8" L1FTS AND COMPACTED TO 95% STANDARO PROCTOR DENSITY. RETAINED BACKFILL SPECIFICATION: � PERMEABLE SOIL DRIVEWAY RETAINED BACKFlLL SHALL BE FREE OF DEBRIS OR �-;:,. e ;, i ; '• ' , ,; • ORGANIC MATERIAL MEETING THE FOLLOWING GRADATION: 12" MIN DRAINAGE ZONE � � �� .� �i� Si7F, % PASSING (1" CRUSHED STONE) ; .`"",.. - APPROXIMATE D(ISTING GRADE 1" 100 = 8 OZ MIN FlLTER FABRIC RETAINED SOIL—� ` _ ._ _ 3/4" 100-75 = - .`�� — — — — � � — — `:.-:.'` > — No. 4 20-100 FlNISHED GRADE _ �5• �;;:-:�::::•;;:'.. / i No. 200 0-50 �"'''� l ' APPROXIMATE UMITS � .� ``' '` ' OF EXCAVATION SEE NOTE 3 .,_,._;, PLASTICITY INDEX (PI)<15 AND LIQUID LIMITS (LL)<30. — — — — — -- � \ , � \\12" MIN /� D---� �\ �/ D 1�\ /�1 1�\ �1 » ,. / � \�/ � - - - - 1 „� � � DRAWING KEY: �SUBCUT (SEE NOTE 2) HI = EXPOSED WALL HEIGHT LOW PERMEABLE SOIL 4" PVC DRAlNTILE WITH H = D(POSED WALL HEIGHT + EMBEDMENT SOCK (SEE NOTE 12) TYPICAL BOULDER WALL SECTION �-'�' �- � " '= CITY OF ORONO ooa,R�crrr c�) �o„ er crv� o�cH Pao�ssiowus __ __ _i Deetgned By: Prokci R°9ist�tion N°' I hereby certify that thia plan, specifieotion, or roport �-��;-,rri i-` r� �' �1�1LDESIGN � � R��on TPH 482�6 was prop red me or under m diroct supervision and � 3315 GRAHAM HILL ROAD t►�ot I du� uc as� nal E�gineer undx � 2 �„ ORONO, MINNESOTA aro�xc Na: thn I the e Mi esota. tl ,__,__r±i�+�-- 1 li �� �' F. ;i S I <) \ A 1. 6 3 N.T.S. II-IIO 8609 LYNDALE AVHNUE SOIf[71,SUTI'E 200 ��� BLOOMR�ICfON,MINNFSOTA55420 `` °ate: TYPICAL WALL SECTION �'°°` "°` ���� �� PHONE:(612)2843696 5 22 JULY 2011 ��� w�si�,WWW.CDP-US.COM 6 3 Curtis . Derieha, P.E