HomeMy WebLinkAboutheat loss info LINE-HT.XLS Heat loss Master Residence
Client Name:
Site Address:
�
K�ITH WATERS & ASSOCIATES, INC.
10340 Viking Drivc Bden Prairic,MN 55344 Liccnsc 110001508
'�-���-� . Phonc(6l2)942-1060 I'aa(612)942-1058
Permitted Heat Loss
Area(Sq. Ft.) x U Value = Heat Loss
1 Total exposed wall area: 6382.00 0.11 702.02
2 Total roof/ceiling area: 3355.00 0.03 87.23
Total permitted heat loss: 789•25
Heat Loss Through Wall Segments
Wall Windows 1446.50 0.31 448.41
Doors 55.56 0.19 10.56
Rim Joist 597.00 0.04 23.34
Wall Framing(Average 10%) 428.29 0.11 46.10
Net Insulated Wall 3854.65 0.04 159.75
Foundation Windows 0.00 0.00 0.00
Foundation Wall Above Grade 0.00 0.06 0.00
3 Total heat loss through walls: 688.16
(If item#3 is the same as or less than item#1,
then you have met the intent of SBC(c)2.
Heat Loss Through Roof
Skylight 48.00 0.34 16.32
Roof/Ceiling Framing(Average 10%) 330.70 0.03 9.41
Net Insulated Roof/Ceiling 2976.30 0.02 50.63
4 Total heat loss through roof: 76.37
(If item#4 is the same as or less than item#2,
then you have met the intent of SBC(c)2.
Alternate Building Envelope Design
To utilize the total envelope system method,the values established by the sum of items#3 and#4
shail not be greater than the sum of items#1 and#2.
Permitted Loss Item 1 +Item 2: 702.02 87.23 789.25
Actual Loss Item 3+Item 4: 688.16 76.37 764.53
Heat loss is acceptable
11/9/95 1
.
LINE-HT.XLS Heat loss ' ' ` ' Master Residence
Client Name:
Site Address:
= K�ITH WAT�RS & ASSOCIAT�S, INC.
10340 Viking llrivc Bdcn Prairic,MN 55344 Liccnsc#0001508
-� . Phonc(612)942-1060 Pax(612)942-1058
Permitted Heat Loss
Area(Sq. Ft.) x U Value = Heat Loss
1 Total exposed wall area: 6382.00 0.11 702.02
2 Total roof/ceiling area: 3355.00 0.03 87.23
Total permitted heat loss: 789.25
Heat Loss Through Wall Segments
Wall Windows 1446.50 0.31 448.41
Doors 55.56 0.19 10.56
Rim Joist 597.00 0.04 23.34
Wall Framing(Average 10%) 428.29 0.11 46.10
Net Insulated Wall 3854.65 0.04 159.75
Foundation Windows 0.00 0.00 0.00
Foundation Wall Above Grade 0.00 0.06 0.00
3 Total heat loss through walls: 688.16
(If item#3 is the same as or less than item#1,
then you have met the intent of SBC(c)2.
Heat Loss Through Roof
Skylight 48.00 0.34 16.32
Roof/Ceiling Framing(Average 10%) 330.70 0.03 9.41
Net Insulated Roof/Ceiling 2976.30 0.02 50.63
4 Total heat loss through roof: 76.37
(If item#4 is the same as or less than item#2,
then you have met the intent of SBC(c)2.
Alternate Building Envelope Design
To utilize the total envelope system method,the values established by the sum of items#3 and#4
shall not be greater than the sum of items#1 and#2.
Permitted Loss Item 1 +Item 2: 702.02 87.23 789.25
Actual Loss Item 3+ Item 4: 688.16 76.37 764.53
Heat loss is acceptable
11/9/95 1