Loading...
HomeMy WebLinkAboutventilation test report MAR, 4. 2005 11 ; 41AM GILBERT MECHANICAL, N0. 9880 P, 2 VENTILATION TEST REPORT JOB NA,ME: St.Edward5 church �(�� �-P�'•�d�I� Page: l TESTED BY: Russell Miller Date: 3/4/OS AREp OPENTNG TC RE UIRED PREY�TMT�IARY FINAL SERV�D NO- S1Z8 PACTOR VEL. C.F.1w. VEL. C.F.M. 'VEL. C.F.M. VEL, C.F.M. VAV-1 Sacris 113 1 8" 200 225 205 Stora e 014 l 12x4 200 125 190 Kitchen 016 1 10" 265 200 255 2 10" 265 200 260 3 10" 265 200 265 VAV-2 Garherin 007 1 10'' 350 200 345 2 10" 350 225 360 3 10" 35� 225 355 4 10" 350 2S0 350 VAV-3 Mee�in Room 012 1 8" 250 160 235 Meetin Room U11 1 S" 250 220 240 Meetin Room O10) 1 6" 250 200 255 VAV-4 Meeti Roox►�, 009 l 8" 250 150 245 Men's(003 ] 8" 125 175 130 Wom�n's 002 1 8" l25 150 130 Meetan Room 001 1 8" 250 150 255 VAV-5 Gatherin 007 1 10" 350 300 345 2 10" 350 310 350 3 10" 350 300 350 4 l0" 350 � 305 360 MAR. 4. 2005 11 :41AM GILBERT MECHANICAL N0. 9880 P, 3 VENTYLATZON TEST REPORT JOB NAME: St. Edwards Church page: 2 TESTED $`Y: Russell Miller Date: 3/4/os AREA OPEI�IING K RE UIRED PRELIM�NARY FINAL SERVED NO. 51zE FACTOR VEC.. C.F.M. VEL, C,F.M. VEI�. C.F.M. 'VL•L. C.F.M. VAV-6 Nave 110 1 24x14 980 480 1,OOQ Z 24x14 980 600 975 3 24x14 980 600 980 4 24x14 980 670 985 5 24x14 980 735 975 VAV-7 Gatherin 103 1 ]4x10 300 310 305 2 14x10 300 275 300 3 14x10 300 Z00 280 VAV-$ Meetin Roox� 108 1 S" 200 150 190 2 8" 200 100 200 Secretarial 107 1 6" 135 100 140 O�ce 1 p6 1 8" l 65 100 l 55 EF�l 1 Hood 1,700 1,700 1,700 EF-Z 1 8" 150 150 150 EF-3 ] fi" l50 150 150 EF-4 1 8" l50 l50 150 EF-5 1 8" l5� 150 150 EF�G � 3ox12 4,050 4,050 4,050 2 30x12 4,050 4,050 4,050 MUA-] 1 16x12 b00 6l0 610 2 16x12 600 605 605 3 16x12 600 580 580