HomeMy WebLinkAbout2008-00110 - fire system � , CITY OF ORONO PERMIT NO.: 2oos-oo��o
2750 KELLEY PARKWAY
ORONO, MN 55356- DATE ISSUED: 08/05/2008
952 249-4600 FAX: 952 249-4616
ADDRESS : 2470 COBBLESTONE CT
PIN : 33-118-23-11-0080
LEGAL DESC : STONEBAY SIXTH ADDITION
: LOT 002 BLOCK 001
PERMIT TYPE : FIRE SYSTEMS
PROPERTY TYPE : RESIDENTIAL
CONSTRUCTION TYPE : SPRINKLER SYSTEM
NOTE: INSPECTIONS ARE DONE BY FIRE MARSHALL,BILL MEYER.
PLEASE CALL BILL MEYER DIRECTLY AT:(612)490-2307
ENTER THE VALUTATION 3000
APPLICANT FIRE SPRINKLER-RESIDENTIAL 37.50
LIFESAVER FIRE PROTECTION, INC. STATE SURCHARGE VAL OTHER 1.50
15405 9TH AVE.N
PLYMOUTH, MN 55447 MAIL-IN FEE 1.50
(� TOTAL 40.50
Minnesota State License#: C040
OWNER
O.T. Development, LLC
LLC,O.T. DEVELOPMENT,
2670 KELLEY PKWY
ORONO, MN 55356
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed according to
the approved plans and specifications,applicable City approvals,and the
State Building Code. This permit is for only the work described and does
not grant permission for additional or related work which requires sepazate
permits. All provisions of laws and ordinances governing this type of work
shall be compied with whether or not specified herein.This permit will
expire and become null and void if construction authorized is not
commenced within 180 days of the date of issuance,or if construction is
suspended for a period of 180 days at any time after work has commenced.
The applicant is responsible for assuring all required inspections are
requcsted in conformance with the State Building Code.This permit may be
revoked at any time for due cause.
� � l,� / / ���� {�`
� � �� L'� / IG1 � (�l � l CC�
Applican� t Permitee Signature Date
Issued By Signature Date
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRIBED ABOVE.
O.¢,p,�O City of Orono Fo c�T �L�sE o:�LY
1 P.O.Box 66 Date Received: � Permu ,
�a ���,�, �� 2750 Kelley Parkway
\'p�, NL..1�.�'L,. Crystal Bay,MN 55323 Amount: ��_.J�
�ssxog�'� (952)249-4600 �� '
ApprovedBy: !.3_+�.����' 7�/t��dQ3
,
! Recommends, A roval Denial ❑
CITY OF ORONO—AUTOMATIC FIRE SPRIlVKLER/GENERAL PERMIT
(All permi[s must be approved by the Fire M;�rs}��II and/or Building Official)
1. Permits are iequired for all fire sprinkler installation and repair. All work shall be done by a licensed
fire sprinkler contractor. Two sets of plans, specification data sheets, fire flow tests and hydraulic
calculation sheets shall be submitted to the Orono Fire Marshal a minimum of 7 davs before start of
work.
2. Permits can be applied for by mail at PO box 66,Orono, MN, 55323 or in person at,
2750 Kelly Parkway ;phone: (952) 249-4600. Permits are also available online at:
www.ci.orono.mn.us
3. All systems shall be designed,installed and maintained to N.F.P.A.-13,N.F.P.A.-25, Minnesota State
Building Code, Minnesota State Fire Code and Standards. All attic systems are to be spaced at a
maximum 130 square foot coverage. Plastic pipe will not be allowed at any time in attic spaces.
4. All equipment installed shall be U.L. or F.M. approved for fire protection service. Water flow test
shall be completed on all new systems. Water flow test reports shall be submitted to the Orono Fire
Marshal along with plan submittal.
5. Yard or wall post indicator valves are required. All indicating and control values installed shall be
provided with tamper protection. On dry systems, the control valve to service the pressure switch(air)
shall be supervised.
6. Inspectors test valve shall be installed on each floor level or zone of system. All systems shall have
main drain and inspectors test valves piped to the outside.
7. No water is to be introduced into the sprinkler system until main has been thoroughly flushed. 200#
air test and flushing shall be witnessed by the City of Orono Water Department.
8. An approved audible/visual device wired to main flow switch shall be installed above F.D.
connection and in areas normally occupied by tenants.
9. EXISTING SYSTEMS: If any changes in the hydraulically most demanding area, change in
occupancy classification or an addition of 20 or more heads,hydraulic calculations and flow test will
be required.
10. The Orono Fire Marshal shall witness all final flow or trip tests. Appointments can be made by
calling (952)473-0234, 8:00-4:00 p.m. Monday-Friday. 24-hours notice is requested.
1 1. When required, (30 foot building height) stairwell standpipe's shall have 2 '/z gate valves installed
with 2 '/z x 1 '/z caps.
6/1/2004
. ��,.� _��������`a °...�n����.�:��,�CT�'�.���C-F�RE SPRINKLER.PE�tMI3'S; :::�h..,, . �
���Please Checic�One: m ,�, � �,_ � �
� New ❑ Addition ❑ Remodel ❑ Replace
; Job Site/Owner Information:
Site Address: �l����-u� � � J � � �.e'"'`''72SZ � ,-.
`� � y '� C � � ( t
Owner: � - � � Mailing Address:
City: Zip:
Home Phone: Alternate Phone:
� Contractor/Applicant Information:
Contractor/App.:L��y�vF P� �!�� � Contact Person: �� � ��
r�
Address: �/�y� �� �� - �d � � State License#: C �G ��
�vt1 ,-,_
City: � � ; ,�
Zip: -� � y� 7 Expiration Date: � (_�,�[ � ��
Phone: �� Z�� ��� � ���� Alternate Phone:
f�.� ����,� �
�.�r��.F..�,�;h� r�-�,��,���r����,��a;. �'�.,�?ES OF�T+lRE SP•ItTNKLER PERMITS ;�i:'
❑ Commercial—Fire S rp inkler ❑ Residential—Fire Sprinkler
Fire Systems Permit Fire Systems Permit
*Base Price=Contract Price: $�� x .0125 =$ (Minimum$35.00)
*Surcharge=Contract Price: $ x .0005 =$ (Minimum $ .50)
* Mail-In Fee(Only On Mail In Applications) _$ 1.50
*Total Cost of Permit: _$ �- v
����� �-f��/I.0 /� ,( / ,��J �� � ! j/t
The undersigned herby applies to the City for issuance of a Sprinkler Systems Permit. Applicant agrees
that all systems shall be designed, installed and maintained to N.F.P.A.-13,N.F.P.A.-25, Minnesota State
Building Code,Minnesota State Fire Code and Standards,and certifies that all statements made on this
application are complete,true and correct.
� � �� ' - ��� -�= �
Applicant Date
� :� � ,��� � � :
�p�'�4�� Reset Form ,� �-
. /
�� '�(���- �,
�