HomeMy WebLinkAbout1989-04-25 Inspection Report, Fire SprinklerEAGLE FIRE PROTECTION CO. 2335 NEVADA AVE. NO. MINNEAPOLIS, MN. 55427 PH. 546-2335 REPORT OF INSPECTION INSPECTION CONTRACT NO. 14033 REPORT T0: MACMILL AN TENNIS BUILDING/ LOCATION: STREET: 170 FOX STREET INSPECTOR: DALE BISTODEAU CITY/STATE: WAYZATA, MN ZIP:55391 DATE: APRIL 25, 1989 -------------------------------------------------------------------------------- OWNER'S SECTION (TO BE ANSWERED BY OWNER OR OCCUPANT) A. Explain any occupancy hazard changes since the previous inspection. B. Describe fire protection modifications made since last inspection. C. Describe any fires since last inspection. D. When was the system piping last checked for stoppage, corrosion or foreign material?. E. When was the dry -piping system last checked for proper pitch? F. Are dry valves adequately protected from freezing? Signature: Title: Date: ------------------------------------------------------------------------------- INSPECTOR'S SECTION (ALL RESPONSES REFERENCE CURRENT INSPECTION) NA - NOT APPLICABLE 1. General a. Is the building occupied? YES b. Are all systems in service? YES c. Is there a minimum of 18 in. 1457 mm) clearance between the top of the storage and the sprinkler deflectors? YES d. Does all electrical heat tape appear tote satisfactory? e. Does the rand hose on the sprinkler system(s) appear to be satisfactory? N/A 2. Contr—ol Valves (See Item a. Are all spr. , kler system control valves and all other valves in the appropriate open or closed position? YES o. Are all control valves in the opeci posi ur, locked, sealer or equippf d with tamper switch? YES 3. Water Supplies (See Item 16.) a. Was a water flow test of main drain made at the sprinkler riser(s):' YES 4. Tanks, Pumps, Fire Department Connections a. Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained? YES b. Are fire department connections in satisfactory condition, couplings free, caps in place, and check valves tight? YES Are they accessible and visible? YES EN Inspection Report No.14033 Eagle Fire Protection Co. Page 2 Report To:MACMILLAN TENNIS -------------------------------------------------------------------------------- 5. Wet Systems a. Are cold weather valves (O.S.& Y.) in the appropriate open or closed position? b. Have antifreeze syscam solutions been tested? N/A c. Were the antifreeze test results satisfactory? _N7A d. In areas protected by wet system (s) , does the building appear to be properly heated in all areas, including blind attics and perimeter areas where accessible? YES Do all e-terior openings appear to be protected against freezing? YES 6. Dry Systems (See Items 11 to 13.) a. Are dry valve(s) in service? YES b. Are the air pressures and priming water levels in accordance with the manufacturer's instructions? YES c. Has the operation of the air or nitrogen supplies been tested? YES d. Were low points drained during this inspection? YES e. Did quick -opening devices operate satisfactorily? f. Did the dry valve(s) trip properly during the trip pressure test? YES g. Did the heating equipment in the dry -pipe valve room(s) operate at tTie time •f inspection? YES 7. Special S�, . L;ems a. Did the deluge or pre -action valves operate properly during testing? b. Did the heat-respons�:e devices operate properly during testing? N/A C. Did the supervisory devices operate during testing? N/A 8 . Alarms a. Did water motor(s) and gong(s) test satisfactorily? b. Did electric alarm(s) test satisfactorily? YES C. Did supervisory alarm service test satisfact-o-r-lly? YES 9. Sprinklers a. Are all sprinklers free from corrosion, loading or obstruction to spray discharge? YES b. Are sprinklers less than 50 years old? YES c. Is stock of spare sprinklers available? NO d. Does the exterior condition of sprinkler system appear to be satisfactory? YES e. Are sprinklers improper temperature ratings for their locations? YES 10. Explain any "NO" answers and/or co c;.ta:fi0 HEAD COX 11. Date dry pipe valve trip tested (control valve partially open) 4/25/89 (See Trip Test Table attached.) 12. Date dry pipe valve trip tested (control valve fully open) (See Trip Test Table attached.) 13. Date quick -opening device tested N/A (See Trip Test Table attached.) 14. Date deluge or preaction valve tested N/A (See Trip Test Table attached.) Inspection Report No.14033 •:gle Fire Protection Co. Page 3 Report 'TO:MACMILLAN TENNIS ---•;------------------------------------------------- 15. See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE _'ABLE CONTROL VALVES NO. TYPE OPEN City Conn. Control Tank Control Pump Control Sectional Control System Control 2 0 . S . Y YES Other Control 16. Water Flow Test at Sprinkler Riser WATER SUPPLY SOURCE: CITY DATE TEST PIPE LOCATION List Water Flow Test This Water Flow Test 4/ 25/ 89 RISER 17. Explain a% "NO" answers and comments: EXPLAIN ABNORMAL SECURED CLOSED SIGNS CONDITION NO NO YES TANK PUMP SIZE OF STATIC RESIDUAL TEST PIPE PRESSURE PRESSURE 2 " 80 80 18. Adjustments or corrections made during this inspection: 19. Althe these comments are not the result of an engineering review, the foll, g desirable improvements are recommended: WIRE AIR SWITCH ON PRESSIG,,,E TANK TO CENTRAL STATION. WIRE ALARM SWITCH ON DRY VALVE. INSTALL LOW AIR SWITCH ON DRY VALVE. Inspector's Signature: Date: Form 10.17 Rev 1-58 RoprintSfl 1.72 DRY PIPE VALVE TRIP TEST REPORT BY FOR MacMillan Tennis INSPECTION NO. STREET 1700 Fox Street CITY Wa�,'zata STATE MN —_ CONTRACT NO. DATE OF TRIP TEST 4- 2 5- 89 INSPECTION DAY WORK NO. 14033 NOTE: BEFORE ANY ORY PIPE VALVE IS TRIP TESTED, THE WATER SUPPLY LINE TO IT $MOULD BE THOROUGHLY •I THE TWO INCH DRigAIN BELOW THE VALVE SHOULD BE OPENED WIDE, AND WATER AT FULL PRESSURE SHOULD BE DISCHARO DLONG ENOUGH TO CLEAR THE PIPE OF ANY ACCUMULATION OF SCALE OR FOREIGN MATERIAL. IF THERE IS A HYDRANT ON THE SUPPLY LIME, THIS HYDPANT SHOULD BE FLUSHED BEFORE THE TWO INCH DRAIN IS OPENED. THE DRIP VALVE ON THE DRY PIPE VALVE SHOULDBE CHECKED BEFORE TRIPPING THE DRY PIPE VALVE, TO SEE THAT IT IS IN OPERATING CONDITION. DRY PIPE VALVES SYSTEM NO. ( I ) SYSTEM NO. ( ) SYSTEM NO. ( ) SYSTEM NO. ( ) VALVE SERIAL NUMBER 12072-2 MANUFACTURER INANE) Reliable VALVE "ti:-XL D VALA Slit ILOCAT!ON) CONTROLLING SPRINKLE (NUMBER) 4 INCH INCH INCH INCH �•~ � 1 60 IAPPROA) IAPPROAI (APPROA) CAP►ROXI DATE LAST TRIP TESTED? 4-21-88 DATE LAST OPERATED? PRESSURE BEFORE TEST AIR 32 LES LBSTER LM WA _LOS 80 LOS LOS LES LBS SIZE AND LOCATION OF TEST VALVE 1 'nd Flr. WAS GAT[ VALVE BLOW DRY 1 TT (IF NOT. NOW VALVE OPEN MANY T RN 1 3 turns VALVE TRIPPED AT AIR PRESSUIRC LBs LOS LOS LBS WATER PRESSURE 80 LOS LOS LOS LOS TIME MIN 20 sac MIN sac MIN /[C MIN SEC IF SYSTEM FLOODED, LIST TIME WATER R A N TEST O► NIN YIN f[C MIN SEC MIN SEC MIN S(C_ PERFORMANCE good VALVE CONDITION INTERIOR OF BODY good MOVING PARTS good RUBBER FACING gu-A SEATS good RESETT good DID ALARMS OPERATE AT TRIP TEST? supervised cnly, not local ALL LOW POINT DRAINS BLOWN OUT? yes -—__ WATER CONTROL VALVE LEFT IN AIR Si yes 11k O EN AND S[AL[O1LV'i-LEFT T V@5 -- — — QUICK OPENING DEVICES SYSTEM NO. ( ) SYSTEM NO. ( ) SYSTEM NO. ( ) SYSTEM NO. ( 3 DEVICE SERIAL NUMBER N/A MANUFACTURER (NAME) _ TYPE AND MODEL AIR PRESSURE IN UPPER CHAMBER LES LBS LBS LBE QUICK OPENING DEV:CE TRIPPED AT sac LOS SEC LES sic LBO sac LBO PERFORMANCE ING DEVICE LEFT IN SERVICE NO CONTROL C,PEN AND SEALEOT LIST ANY UNSATISFACTORY CONDITIONS: Alarm sw h nc)t wirecl O ')ll S i dc- hell - REMARKS: DRY PIPE rPERATING TEST DELUGE 6 PREACTION VALVES Eaqle Fire Protection Compong i Nesada Avenue Notth * '•'inneapolis, Alinnesota 55427 it- (612) 546.2335 #14033 MacMillan Tennis 1700 Fox Street Wayzata, MN DRY VALVE 1'I%1P IT61 TABLE c O n MAKE MODEL SERIAL NO, MAKE MODEL SERIAL NO Reliable D 12072-B Time to Trip Thru Test Pipe Water Pressure A., Pics:ure Trip Puint Art Pressure Time Water •=iCacl;•d Test Outlet Alarm Operated Property MIN SEC. PSI PSI MIN SEC YES NO Wrlhoul a.O.D. 20 80 35 11 X with La. D.D. — — TRIP TEST TABLE Operation ` PNEUMATIC p ELECTRIC 0 HYDRAULIC Piping Supervised t'7. YES Q NO Detecting meO,a supervised -_'YES DNO Does valve operate from the manual trip and/or remote control stations 'YES ENO Is there .n accessible facility in each circuit for lest.ng '.Ielhod of Icstrny-c'rcwls E:'YES ONO DOC1 eJCh circuit Operate Does CaCh Cul.url-5-1—im time 10 t.t;.KE MODEL —, vl r•; , lots arJrrn one+str valve retrase O•i�•,ate relra:r