1989-09-28 Septic System Design Report
S-P TL S TING, 951 KATYDID LANE ST. MICHAEL. MN 55376 497-,,566 Steven B. Sphirmers . September 28, 1989 Whitney MacMillan 1560 Fox Street Existing House Parcel 3000 -- r; � �r. -71 Orono, Henn. Co., MN This system is Designed for a Type 1, five bedroom home and in accordance with the Minnesota Pollution Control Agency Chapter 7080 and local ordinances. The soils on this site are typical of SCS soils mapped - KkC - Kilkenny loam. A seasonally high-water table was located at 20", 22" & 26" (mottled soil). Due to the seasonally high water table, a pressurized mound system will need to be installed. The bottom of the rock lied must be located at least 3' above the seasonally high water t81,ie. This site has an existing system located east of the house which is functioning adequately at this time. A new site was tested for future expansion if needed. The soils at a depth of 12" & 18" have a percolation rate averaging 13.9 min/inch and are adequate for treating septic effluent. A pumping chamber -will need to be installed to lift the effluent to the treatment area. . The manifold and supply line pipe must have back drainage to the pumping chamber. The distribution pipes shall have their ends capped. Be sure the rock and sand fill material are clean. The sod layer below the entire mounded area must be turned over, just break up the sod, be sure not to over work. The power supply and switches must be located outside the manhole and pumping chamber in a weather proof enclosure. A warning device must be installed with a light and sound device, this is in case of a pump failure. (Mercury floats are a good method). The existing tanks may be used upon approval by the local Inspector. All neighboring wells are located more than 100' away from the proposed treatment area. Soil and Percolation Tests CONT' D Septic System Design Keep all heavy equipment off of the proposed treatment area before and after construction as much as possible. The treatment area should be marked off before construction. With proper installation and maintenance, th3• {stem should have no problem in treating septic effluent effectil Recommend to pump the septic tank every year if there is only 1 tank & every 2 years if there are 2 tanks. Q Steven B. Schirmers of SBS/ds O 3 O• Z A (-1 fJ -1 ,N v c � 2 fi Illn` < I� 41 T. N C ��' .L• *� n R .0 l i m u .r 0„ 7 t� n CD.�'� 10 li LA 7 s 6 Is ° N o• r1 � n Q A r�p0 �( U U. 1 M• O 1 1. i1 = Xi ` 1� a �• i In ♦ N O .* T O � 11 � Ir pk ` o fV �I• w ►� Q u, ` \ 7 0 �C a `; ,�.� � ice, rZw= T .�• n C 6 * 1 u n IA b 0 4 1� t O is 77 "a 9' Q x S I � N i F c N 1 D M r_ N M _ 3 � c x x n N 'fir A O,O N �; u f Qryv y L •e T 1 0 N IO rr -• v y � 1) T Y'- T m 3 ,rl V 1 C e r ui n rn { _I _4 -1 -4 �! r fTl f+l M M MS � ,��o rn x ^ 0.0 '� o VIP I 9 If f` ` y� h 1F W J� 1 L x L4vs s �c n �e it w z CER:'IFICATION • 00627 Logs of Soil Borings Location or Project Whitney MacMillant1560 Fox St., Existing house, Orono Borings made by S-FTesting, Inc. Steve Schirmers Date 9-21-89 Classifiction System: AASHU USDA-SCS X Unified Other Auger used (check two): Hand X or Power , Flight_, or Bucket X Depth, Boring number 1 Depth, Boring number 2 in in ' feet Surface elevation 986.8 feet 1 Surface elevation 987.0 0 - I 0 - Topsoil dark brown loam opsoi dark brown loam 0 - 10" 0 - 8" Gray brown loam , 1 - 1 - Gray 10" - 1'4" mn 8" - 114" Brown clay loam Brown clay loam 114" - 1'10"-MOTTLING 2 _ 1'4" - 2'2"-MOTTLINC 2 - Olive brown clay loam stronc Rusty olive brown 2'2" - 2110" clay loan strong Olive Crown loam 3 - 3 _ 2-10" - 3'4" Olive 314" - 3'8"si�Wnlo m 1110" - 3110" Rusty olive brown 4 - Rusty olive ,rown 4 - loam loam w/traces of coarse 3110" - 4'10" sand 5 _ 3' 4" -- 5' 5 _ Rusty olive brown sandy Rusty olive brown 5' - 518" loam loam Rusty olive brown loam 6 - 508' - 6' 6 - 4'10" - 6' 7 - 7 - 8 - 8 - End of boring at 6' feet. Standing water table: present at feet of depth, hours after boring. Not present in hole X Mottled soil: Observed at 2'2" feet of depth. Not present in hole Comments: End of boring at 6' feet. Standing water table: present at feet of depth, hours after boring. Not present in hole X Mottled soil: Observed at 1'10" feet of depth. Not present in hole . Comments: CLR IF.ICATiUN 4 UUbl/ Loas ut aui, aorinyb Location.or Project Whitney MacMillan,' 1560 Fox St.,Existing house,Orono Borings made by S-P Testing, Inc. Steve Schirmers Date 9-21-Li Classifiction System: AASHU ; USDA -SCS X Unified Other Auger used i^heck two?: Hand X or Power , Flight , or Bucket X Depth, Boring number 3 Depth, Boring number in in feet Surface elevation 987.9 feet I Surface elevation 6 7 8 Topsoil dark brown loam 0 - 10" Brown clay loam 10" - 1'8"-MOTTLING Olive 1'B" - 2'2" brow ;�oS Rusty olive brown clay loam 2'2" - 3-1/2' Rusty olive brown loam -1/2' - 6' End of boring at 6' feet. Standing water table: present at feet of depth, hours after boring. Not present in hole X Mottled soil: Observed at 1'8" feet of depth. Not present in hole . Comments: 0 - Y1 2 - 3 - 6 - 7 - 8 - End of boring at feet. Standing water table: present at feet of depth, hours after boring. Not present in hole • Mottled soil: Observed at feet of depth. Not present in hole • Comments: .4 2 CERT.#60627 PERCOLATION' TEST DATA SIiEET Percolation test rcadingsrnadcby S—P Testing. Inc_?_ —On 9-22— 89 startingat 1:31 z—R. , ", 1560 Fox.St.#Existing ho " rc)n0 i 9-21-89 Test ho:c locatu,n Iu�c fturii r , Datcitole was ptcpamt Depth a� hot: lrttom 18 inches, Diameter of hole 6 inches Sail 4'ata from te%t ho:c: Dvmh. inches 0 - 10" 10" - 16" Soil texture Topsoil dark brown loam Gray brown loara " Brown clay loam Method of scra:chinb sidewall i<nife 2 Depth of gravel in bottom of hole inches Date and hour of initial water filling9-2 1-89. Death of initial water`tilin�;_ 12 inches above hole bottom Method used to maintain at !cast apt 4 hour-, 12 inches of water depth in hole for ahour-,Automatic siphon ..Maximum water depth above hole bottom during its, 6 inches , Time I Percolation Time ! intcrvil. Measurement, I Drop in water ( :ate, i Remarks minutes inches I levcl.inches minutes per i inch 1:11 prefill i 6 i 1.31 2.01 I 3 j 10.0 i 30 min 2:02 2:32 " 2-7/8 10.4 2:37 3:07 i 2-11/16 11.2 I" t 0 • I f a .. i t - Pcno:anon rate - 10.5 minute- per :nch. CERT.400627 0 PERCOLATION TE.c%'v DATA SHEET Prrrolation test readings made by S—P Testing, : nc . _o" 9 —22 —89 startinY a, 1:30 �_p.m.�l 'Awl Test holelocatiorL560 FOXSt.,ExiStinghou —1YkOurnc cr 2 ,Date'holewasprepared 9-21-89 Depth of hole hotto12 inches. Diameter of hole 6 inches Soil data from test ho;c: Depth. inches Soil texture 0 - 8" Topsoil dark brown loam ' 8" - 12" Gray brown loam Mcthcx!ofs%:ratchinrsidcwa;l Knife 2 Depth of gravel in hotwrn of hole irr'.�� 9-21-89 12 Date and hour of initial water ""ing . Death of initial water filling inches above hole bottom Method used to maintain at least I?, inches of water depth in hole for at least 4 hours Automatic siphon ..Maximum water depth above hole bottom during tcsL 6 inches Time ; I Percolation Time I interval, Measurement, i Drop in water rate. Remarks i minutes inches level, inches i minutes per inch 1:11 prefill 6 1:30 2:00 ; 1-7/16 20.9 30 min 2:03 2:33 1 " 2 : 3 6 3:06 "• I " w w w Perco!ation rate - 20.9 T:nutes per inch. M CEF T. N00627 PERCOLATION TEST DATA SHEET S-P Testing, Inc. 9-22-89 ' 1:29 a.m. Percolation test readings made by o" gaming Test -o'e location 1560 Fox St . Existing hoVoge,ngk6po 3 Date'hole was prcpaned� 84 • 12 6 Depth of hole bottu inches, Diameter of hole inches Soil data from test hole: Depth, :-. , •s 0 — ion 10" - 12" Soil texture Topsoil dark brown loam Brown clay loam Method of secaching sidewall Knife Depth of gr::s-el ,n bottom of hul2c- 2 inches 1� 9-21-89 Uatc and hour of initial water fi%inf , De; th of initial water fillin; inches above hole bottom htcthtxl used to maintain at least I: inches ofwaxrdcpth in hole for least hours Automatic siphon , Maximum water depth above hole bottom during te+t 6 inches ' TimePercolation Time in:ervr:. i Mcrwretttcnt. Drop in water i minutes inches Ieve:, inches I t rrte. minutes per inch Remarks :11 I pref ill 6 29 i 1 : 5 9 3 10.0 30 min i 2:34 l " 2-7/8 I 10.4 " ! 35 I 3.05 " 2-3/4 10.9 I i I 10 PM-ointion rate - . 4 minutes per inch. SANDY LOAM LAYER OF STRAW OR MARSH HAY COVERED WITH RED ROSIN PAPER -PERFORATED TM_ LATERALS SOIL `• ..� '_�. ��'• •.,,•.•,,.. __ _.. •.. ` t ` �v: 'RBI •; rp or IF PIPE FROM PUMP— ':'• ,�;�. Jf to CLtAN2'f OCK -- -r.• t,r ,i• .0 �/ DIVERSION FOR • - - / �' NOTES' SURFACE WATER •- r 6' TOPSOIL /- ��j /� 1 SELECT AS LEVEL A SITE AS POLL iOR Tit MOUh& i� y ,•' 2 REM04 EXCESS VLC(TATION. FILM 064 CA MdLHOL TwE SuWWX SM i 004ES OCD. 00 TM' a, . r r T ��liE T IS L[SS Tww TK PLASTIC T 190N IS f f ' s • : / �J; •;; ,' • ;J INTO_ Am I= »�IIEf DDOOiMOf EM�(� T 1• `.r AAMo°")OmIS OFCiL I�T�1TR►[ � � umb _ VV r• MJE �� �.1•� - b �'�_ _ '!' t lj� Lam, ION AOIL I1ASTK CONOI T igACK-T IOSJIt*IXQrT fOIl CaXSTRNCING M Mam SD AS MOT j`j.►/ ��I i; rJ ^ nCs► �.�/ 3 1D CbMPA[T THE ANAL SOIL.,N� �p�/� 't �� ',� 6' �' 7 l�f• sYi~'`� A. T.IQ+E�IwStN S��wi> 2 M�iMItM ORMIpI�Li roe fu T►.L�M S' MINUTES PER 11 WJDW IA�r TIE�a' CLEAN 1MO TRNL� �O r� • I S TIE 12 INCH 1 qi (��/1 Syy; �S yQ 1QN y CLEAN ^^ _• IS CO►p�I�OpCRfDI�«I�JJT�NR IT CAN 1MS31i_ C i f f�R- Tf3T fD� EOMCRk7[ Sw. �Ea L0pE J ~ `: - ~�.� +.`� �.. •+_ K' A OONSiiRKTfO LEVEL. SAM LA"A AMA TILE lt>/ QT M IbOL !O MIT INS SAN '� O N ti -e, �•� }��1 - 1! OtSTR eollCIN APES ARE 14I6 ICM DIIMETfR y" AO IMCM��M {�M�U f , �� so o _ {' J �:y._ .'%' • : �//1.�1!D CO►+NEC,EO , 11DL0Iofts*�E C[lN�iL�AQOtArIT��!OCn OW. PMlS IWY L �� - `t `• Ifs R ►HEW DRILL SIT Ta�1/ 1 oL11MIS INSIfi 7.� rIR. !/TIME NIMMMMp ©ROkEI'AYER _ = � '~��� .s NINE INCHES Cf RQCIe AR( RACED �JNaER TK /( LAT~ Am : Up - , E INCHES AltOr[ A TOTAL ROCIs OEP1H IS IMC THE ROCK IS rWKT COVIL WITH A LATER M�►_� s1 t1! '�M (�� a... COvEItEO WITH A LArLA Oi IEO RI1 ill u1Pr� • wPP • • Iu �,� IMEDA r art5 oP LOIIMr SAHO SHOULD BE KAM DRIP THE TOP OT TK 6 R Rq ER Rqi E I I A G INCH LAYER Or TOP SOIL •ouLO PLACED oyu THE atwE MONmO so LAYEC THAT A (mSs COVER CAN BE I�LS17Akilm O TER '{12 6 INCHES 0 Wit CC" ABOVE T ! NCK LA ER SO AT THHAT HEJIV RAN WILL RLIM OTr.� M MaNO is SIDE ; 11 OO S SANDY THE EONS ES SHOULD K MO STEEPER T. " 41 00 CLW SOIL •. 1A OMAP86*0116.A; ac cw c, 4MLAOM LAtIER.Oi1U0 OII M AMOMT WOW' SEWAGE-fWW 11tt OruE1 15 MAXiMwM EFFLUENT DOSE pER hump CYCLE SHOULD BE MO MOW THE TART VALUES 15 MINIMUM PUMPING. RpAMTE( I(S� SHOWN IN TR.'ILE PUMP" KAD T fAOROUAPENo�TE�f LRATEAALSEvATION OKrEREIICE. fRKt10M LAff i'nL+ �-- Grass Corer Yoptoil 01 Layer of Geotext Loamy Sand Layer of lay or straw rosin Celt- ile I abric• (or layer covered with -red I�erfor tee La -eras --Perforation Drilled 11, I J. ccvc0<-r.' C. 1'TLC• <<CL. C into Ca Neor To/RFC P P ft�Drain Field Rock :_. Clsaii Sand Lave,- ---� --/fit Least < ` of Rock, '.�Ct •Cf4r forat ions Located at Bto. •m of Lateral Original Soil Properly Scarified Before Placing Sand Layer Horizontally 12" to Edge Layer ale �AYour oi: i'r:I�FCRA1 Cu FIFE LATERALSror1 PRESSURE DISTRIBUTION IIJ r.40Ur:U - FERFOPATED PLASI IC PIPE \ _ SFAC' r f-f:KfliF;!:� IUi�S r�:C.ro :;:J" (:R -30 ,�� iCtl EUD CIJ CI'IJILR. F RI'CRATIGIJ = P fr,fGfi.4i fill c - VERFORATICNG GN FOI TGI„1 Cl: FLASTIC FIFE _� -- LI JD CAP 4Q LArCpAL of Farr. (ALII-RHATE IOCATICN OF PIPE, FRO 1 PUMP) \� PIPE FROM MPING CHAMBER ;i� 0 WATER TIGHT a LOCKABLE 1:1 LC-I_RIC 13C'X-- 13LUGS OR ELECTRIC CONNLCTICNS - -- - - 2" PVC CGNDUI r SCIIEDUI.L 60 - ~ A- L MANHOLE COVER CHAINED a LOCKI-0 G"SE'_A_CL" '-EA _ED MANHOLI= RINGS } -- REDA1001) (-I_DA� OR 1,r?1=n-TI..D POST 4 x 4 min) Ci I:IC COfvN1=CJ'IONS ivADE INSiL ! f30X LOOP CF FOV, C R COf%U FCIl SET TLEMENT if=1NAl_GRADE- AT I_t= AST 12 11 UNION 1 BELOW GRADE -WIRE* ;OM POWER SUPPLY PIPE' IS I_A10 ON A UNI("OR!'+A SLOPE FROM + FUll/l' S I-ATION UP -I 0 SOIL 'I REAI h��E1d T AREA 1=013 PROPER DRAINBACK SEALED TANK COVER --c�--11= PIPE AT TANK MUST BE LOWER TH N ci UNION TO GET F-t-r ATIONO i'L!>STIC ROPE OR CHAIN :� A 1/4 INCH WEEP HOLE MUST BE USED wi,rli ANCHOR -- --- \ �fl -_ _ , - WCLI livl E AI..AI"%'M FLOAT ON SCRARATEE l_I.FC1131CAL cmcurr-- _ .S_r_Njr LEVEI.-V - --- _J -i- 3' SITU C'_ OEF__LEVI=h l _ PUMP CONTROL FLOA-r--- —--------- - - 0 0 ci NOTES: I= I-L_CI IRICAL. WIRE FROM POWER SUPPLY MUST- NO•r RUN OVER ANY TANKS BUT MUST 13E LAID BESIDE.OFHER TANKS AND MUS'r BE PLACED IN CONDUIT ALONG POS r FI_ECI'13ICA1_ CORDS FROM PUMP AND FI_0AfS MUST BE IlUN THROUGH CONDUIT. WIRL-S CANNOT HAVE GROL-NO CONTACT. METAL COVER CONCRETE NAANHOLF= ,?INS METHODS OF SECURING MANHOL E COVER TO PREVENT UNAUTHC R I ZED ENTRY ,_fi_jVPI:.NCIL MARKS 2d MANHO! 111q]. mj I SCUM UTLET 1-1-VEL SCUM CLEAR SPACE y- 13 7=7 SLUDGE OUTLET v CLEAN OUT TANK WHEN'. 'X IS 37 014 LESS OR "B" IS 12* OR LESS - BLACK COLOR DISTINGUISHES SLUDGE LAYEj FROM LIOUID MEASURE SCUM AND SLUDGE ACCUMULATIONS IN THE SEPTIC TANK