HomeMy WebLinkAboutLA21-000076, 1720 Bohns Pt Rd, VAR, Exhibit B Engineering Report
April 25, 2022
Christian Harker
1720 Bohns Point Road
Wayzata, MN 55391
Submitted by email: christianharker@yahoo.com
Re: Retaining Wall Evaluation
Project Location: 1720 Bohns Point Road, Wayzata, Minnesota
Criterium File No.: 22-6174
Dear Mr. Harker:
At your request, a visual inspection of the retaining wall at the above property has been completed. The
report that follows has been prepared based on that inspection. This inspection was performed by Paul
Schimnowski, PE.
My work includes the following:
1. Visual observations during a site visit on April 20, 2022.
2. Observe factors influencing the performance of the structure.
3. Provide a written report containing the following:
a. Scope of services.
b. Observations, site characteristics, and data deemed pertinent by me.
c. Discussion of structural factors influencing the performance of this wall.
d. Conclusions and any recommendations for further investigation and remedial or
preventative measures.
e. You asked me to pay special attention to the forward movement of the wall, horizontal
gaps in the face of the wall, deteriorated block at the top of the wall, and erosion at the
base of the wall
SUMMARY
In my professional opinion, the overall structural condition of this concrete masonry unit (CMU) retaining
wall is considered to be poor when compared to others of similar age and construction type. The wall is
failing and is reaching the end of its expected useful life. Due to its deteriorated condition, options for
repairs to re-establish structural stability of the wall are limited and may not be cost-effective in extending
the life of the wall. Replacement should be anticipated in the next few years.
SPECIFIC ITEMS NOTED & ASSOCIATED RECOMMENDATIONS:
1. The top of the wall is displaced outward by about 2 to 3 inches near the center and north
sections of the wall.
2. Horizontal gaps have developed at the wall face due to wall displacement and settlement.
3. Some of the cap units, block, and mortar are deteriorated due to freeze-thaw damage.
4. The cores of some of the blocks are exposed. This will allow water to infiltrate and further
deteriorate the block.
5. Structurally significant erosion has occurred at the base of the wall which has exposed the
footing. For a wall of this type, the bottom of the footing should be at least 42-inches below
1720 Bohns Point Road, Wayzata, Minnesota
April 25, 2022
Page | 2
grade. In order to establish proper frost protection of the footings and structural stability of the
wall, several feet of fill will need to be added at the front of the wall, and/or the wall will need
to be underpinned with helical piers or a similar method.
6. The footing of the wall has been exposed and undermined from wildlife burrowing activity.
See Item 5 above for recommended repairs.
7. Refer to the attached photos for additional notes and observations.
OPTIONS FOR REPLACEMENT
1. For this location, a rock/boulder wall similar to the newer wall at the north end of the failing
wall could be considered. Alternatively, a segmental block (i.e. Versa-Lok, Anchor) retaining
wall could be designed and installed. These types of walls do not require frost-depth footings.
They are constructed on aggregate leveling pads 1 to 2 feet below grade.
Figure 1: Existing, nearby stone retaining wall
2. Replacing the wall with a similar CMU wall would require construction of a concrete footing at
least 42-inches below grade. The front-to-back width of the footing could exceed 6-feet.
Generally, these types of walls will disturb more area than rock or segmental block walls
discussed in Item 1 above.
DESCRIPTION OF TERMS
Terms used in this report to describe the condition of observable components and systems are listed and
defined below. It should be noted that a term applied to an overall system does not preclude that a part
or a section of the system or component may be in different condition:
Excellent- Component or system is in “as new” condition, requiring no rehabilitation, and should
perform in full accordance with expected performance.
Good- Component or system is sound and performing its function. Although it may show signs of
normal wear and tear, some minor rehabilitation work may be required.
Fair- Component or system falls into one or more of the following categories: a) Evidence of
previous repairs not in compliance with commonly accepted standards, b) Workmanship not
in compliance with commonly accepted standards, c) Component or system is obsolete, d)
Component or system approaching end of expected performance. Repair or replacement is
required to prevent further deterioration or to prolong expected life.
Poor- Component or system has either failed or cannot be relied upon to continue performing its
original function as a result of having exceeded its expected performance, excessive
1720 Bohns Point Road, Wayzata, Minnesota
April 25, 2022
Page | 3
deferred maintenance, or state of disrepair. Present condition could contribute or cause the
deterioration of other adjoining elements or systems. Repair or replacement is required.
SCOPE OF SERVICES and LIMITATIONS
The report is not to be considered a guarantee of condition and no warranty is implied.
Our observations are non-destructive, and limited to those portions of the site/wall that could be visually
examined without excavation, removing surface finishes, disassembling equipment, or removing finishes,
furnishings and equipment.
Our scope of services did not include an exhaustive technical investigation. No material sampling,
analytic tests, precise measurements or engineering calculations were performed. This includes but is not
limited to: compaction testing, soil sampling, global stability calculations.
We did not determine whether the wall and its operation or use conform to any city codes, or regulations,
or restrictions that may be enforced within the jurisdiction.
As Professional Engineers, it is our responsibility to evaluate available evidence relevant to the purpose
of this inspection. We are not, however, responsible for conditions that could not be seen or were not
within the scope of our service at the time of the inspection.
DESCRIPTION OF WALL/SITE:
This wall is a single tier, concrete masonry unit (CMU) retaining wall approximately 100-feet in length with
a maximum exposed height of about 7.5-feet. The wall is located on the eastern shore of Bohns Point.
DOCUMENT/INFORMATION REVIEW
No documents were provided.
CONCLUSION
In summary, I consider the structural condition of this retaining wall to be poor when compared to others
of similar age and construction type. The wall is reaching the end of its expected useful life. Replacement
should be anticipated in the next few years.
This professional opinion is based on the information that you provided (verbal, photos, documentation)
and my non-destructive observations at the site. Keep in mind that without invasive investigation, such as
described above in scope of service, not everything about the condition of the existing retaining wall can
be known. Further, improper water control, flood events, or extensive soil saturation can quickly change
the condition of a retaining wall.
Opinions and recommendations in this report are limited to the scope of work. This report has been
prepared in strict confidence with you as our client. Reliance upon our report by other parties is strictly
prohibited. If you choose to share our report, you agree to indemnify, defend and hold harmless the
Engineer from any third-party action. No reproduction or re-use is permitted without express written
consent. Further, we will not release this report to anyone without your permission.
If additional documentation or information is made available for review, I reserve the right to amend or
add to the opinions and observations presented in this report.
1720 Bohns Point Road, Wayzata, Minnesota
April 25, 2022
Page | 4
Please call with any additional questions you may have. Thank you for the opportunity to be of
assistance to you.
Sincerely,
Paul Schimnowski, P.E.
MN #40126
I hereby certify that this plan, specification, or report was prepared
by me or under my direct supervision and that I am a duly Licensed
Professional Engineer under the laws of the State of Minnesota.
Paul Schimnowski, P.E.
Date: April 25, 2022 License #: 40126 (MN)
Location
1720 Bohns Point Road,
Wayzata, MN
Photos Taken by:
Paul D Schimnowski, P.E.
Inspection Date:
April 20, 2022
1 View along top of wall. Outward displacement
noted.
2 View along top of wall. Outward displacement
and deteriorated block noted.
3 View along front of wall. Outward displacement
noted.
4 View along front of wall. Outward displacement
at top of wall noted.
5 View along wall. Outward displacement and
deteriorated CMU noted.
6 Measurement photo of wall displacement at
corner.
Location
1720 Bohns Point Road,
Wayzata, MN
Photos Taken by:
Paul D Schimnowski, P.E.
Inspection Date:
April 20, 2022
7 Deteriorated block at top of wall.8 Horizontal gaps at wall due to outward wall
displacement.
9 Erosion and undermining at front of wall.10 Erosion and undermining at front of wall.
11 Undermined footing at front of wall.12 Undermined footing at front of wall.