HomeMy WebLinkAbout1978-09-14 Septic System Design Reportr •
*WOO*
545 Indian Mound
Wayzata, Minnesota 55391
September 14, 1978 (612) 473-4224
Mr. David Nitz
David Nitz, Inc.
491 West Ferndale Road
Wayzata, Minnesota 55391
Re: Percolation Test and Systems Design for a Building Permit,
Lot 9, Block 1, Fairview Addition, Orono, Minnesota
Job Number 11-78-49
Dear Mr. Nitz:
Enclosed is information requested in regards to the septic field suit-
e ability of Lot 9, Block 1, Fairview Addition.
The drainfield information is based on percolation tests and soil bor-
ings performed on September 7 and 8, 1978.
The soil found on the site is Lester loam. The soil is mapped in
Figure 1. The percolation rate for the primary field as tested was
• 27.5 Min./inch. The percolation rate for the secondary field as
tested was 23.3 Min./inch. The locations of the percolation test holes,
soil borings, and the proposed drainfield areas are indicated in
Figure 1. Percolation rates and depths to the water table are shown in
Table 1. The soil logs of the soil borings are shown in Table 2.
Because of the acceptable percolation rate and because of the acceptable
depth to the water table, a conventional on -site treatment system is
recommended for the areas shown in Figure 1. I have enclosed plans and
specifications for such a system. Additional copies of the plans and
specifications are available upon request.
Stated percolation rates are averaged for the locations shown, and no
guarantee is implied or exrressed that these conditions exist for the
entire test area.
If you have any questions, please do not hesitate to contact me.
Sincerely,
EUGENE A. HICKOK AND ASSOCIATES
James P. DeBenedet, P.E.
S JPD/jel
Enclosures
•
TAB LE 1
PERCOLATION RATES AND DEPTH TO WATER TABLE
Hole
Percolation Rate
(Minutes Inch)
P1
30.0
P2
30.0
P3
15.0
P4
3.9
P5
34.3
P6
20.0
Sbl
Sb2
Sb3
Depth to Water
Table (Feet)
7.3
7.0
Greater than 8.0
Percolation rate of the primary field (holes 1,2,5,6)
27.5 minutes/inch
Percolation rate of the secondary field (holes 2,3,5)
23.3 minutes/inch
0
TABLE 2
SOIL LOGS
SOIL BORING 1
Depth (Feet) Material
0.0' - 0.5' Brown sandy loam
0.5' - 4.5' Brown sandy clay
4.5' - 8.0' Yellowish brown silty clay, slight
mottling at 7.31.
The water level was recorded at a depth of 6.91, 24 hours
after the hole was augered. However, rain may have
influenced this measurement.
SOIL BORING 2
Depth (Feet) Material
0.0' - 0.5' Grayish brown sandy loam
0.5' - 1.2' Grayish brown sandy clay loam
1.2' - 8.0' Yellowish brown silty clay, mottled
at 7.0'.
The water level was recorded at a depth of 6.51, 24 hours
after the hole was augered. However, rain may have
influenced this measurement.
SOIL BORING 3
Depth (Feet) Material
0.0'
- 0.5'
Grayish brown loam
0.5'
- 1.5'
Dark yellowish brawn
silty clay
1.5'
- 3.0'
Brown silty clay
3.0'
3.5'
- 3.5'
- 5.0'
Yellowish brown sandy
Yellowish brown silt,
clay
w/s fine sand and
pebbles
5.0'
- 6.5'
Yellowish brown silty
clay, w/s
6.5'
- 8.0'
calcareous material
Light yellowish brown
clayey silt, w/s
fine sand
The water level was not recorded within 8.0' of the surface
24 hours after the hole was augered.
P 9
�� I.ESTE�. I,UPt 1
/ 2'rdvo
` bs.c" I
sg- i
Oi NNFI
i Sr3Z ,
>01
l�Il.W Fi EL+.)
i•
I e < 4ci-A, ax,0,1 !(*
I
•� rl%oFcf::Ei'�
t i d EA. HOW 8 ASSOCIATES tiff 11>
HYOROLOGW 3-L k3NEERS
MMEAPOLIS-MNNESOTA
4.-orv1053ww-sl"lodv3NNw
s3.LvrJMV V )0o + •v3 -r- 4-, 'or447VC,
J (�
V cr- I<A
17
FA
IS
8
IN�
rl
•!
4.-orv1053ww-sl"lodv3NNw
s3.LvrJMV V )0o + •v3 -r- 4-, 'or447VC,
J (�
V cr- I<A
17
FA
IS
8
IN�
rl
•!
SPECIFICATIONS FOR PROPOSED ON -SITE SEWAGE DISPOSAL SYSTEM
CONVENTIONAL SYSTEM: DISTRIBUTION THROUGH GRAVITY FLOW
LOCATION: Lot 9, Block 1, Fairview Addition, Orono, Minnesota
Job Number 11-78-49
DATE: September 14, 1978
I. SEWAGE TANK - TWO 1000-gallon LIQUID CAPACITY tanks, IN SERIES,
m;:.nufactured and installed in compliance with the
following specifications. See Figure 1 for location.
1. MATERIALS
A. General
All tanks, regardless of material or method of construction shall
be:
(1) Water tight
• (2) So designed and constructed as to withstand all lateral earth
pressures under saturated soil conditions with the tank empty
(3) So designed and constructed as to withstand a minimum of seven
feet of saturated earth cover above the tank top.
In addition, the following specifications apply to specific mater-
ials as indicated.
B. Precast Concrete Tanks
(1) Precast concrete tanks shall be constructed of at least a
4,000 psi (pounds per square inch) core test, air entrained
concrete mix.
(2) Precast concrete tanks shall be cured to at least a seven-day
strength before .installation.
C. Fiberglass and Plastic Tanks
Fiberglass and plastic: tanks shall be designed and constructed to
meet the requirements in Section I. - A.
�J
/ ,
D. Metal Tanks
Metal tanks shall have a wall thickness of at least eight gauge
corrosion resistant alloys and shall be coated inside and out
with at least one coat of bitumastic seal, Koppers 300-M, or by
other equivalent means. Tanks shall be carefully installed so as
not to puncture or damage the seal coating.
E. Block or Sectional Tanks
(1) Rectangular Blocks
(a) Rectangular blocks shall be laid on an approved bottom.
Block shall be at least eight inches thick, constructed
of a 4,006 ore test concrete mix, and cured to a
28-day st before installation.
(b) Rectangular blocks shall be laid either with mortar
joints or filled cores.
(c) There shall be at least two coats of 1/4 inch thick
concrete plaster placed on the inside of the block tank.
There shall be at least two hours elapsed time between
• coats. The plaster coat shall start at the bottom course
and work up.
(2) Circular Block Tanks
(a) Circular blocks shall be carefully placed on an approved
bottom. Circular blocks shall be at least two inches
thick and constructed of a 4,000 psi core test concrete
mix, cured to a 28-day strength before installation.
(b) There shall be at least two coats of 1/4 inch thick
concrete plaster placed on the inside of the block tank.
There shall be at least two hours elapsed time between
coats. The plaster coat shall start at the bottom course
and work up.
(3) Sectional Tanks
(a) A sectional tank shall have an entire section cast as an
integral unit.
(b) A sectional tank shall have two or more sections and shall
have at least one joint below the level of the outlet in-
vert of the tank.
(c) Sectional tanks shall have an integrally cast bottom, or
. shall be laid on an approved bottom.
- 2 -
(d) The joint or joints shall be permanently se, .ed so as to
be watertight.
(4) Bottoms
(a) Any tank not having an integrally cast bottom shall not be
installed when the water table is closer than three inches
to the bottom of the excavation.
(b) If the bottom is poured -in -place concrete, it shall be
at least four inches thick and extend to at least four
inches outside the tank wall. A concrete mix of at
least one part cement, two parts washed sand and three
parts washed rock shall be mixed before placement in
the excavation.
(c) If a starter ring is used, it shall be constructed of a
4,000 ps- core test concrete mix, cured to a seven-day
strength before installation. It shall extend is least
one inch beyond the tank wall, inside and out. A bottom
shall be poured of concrete mix defined in Section (b)
above. It shall extend at least two inches above the
starter ring and shall be at least four inches thick.
(d) If a precast bottom is used, it shall be made of a 4,000
psi core test concrete mix, cured to a seven-day strength
before installation. It shall extend at least one inch
beyond the tank wall, or be cast integrally with the
bottom section.
(e) sectional tank not having an integrally precast bottom
shall have a four -inch thick bottom poured within the
tank walls.
(5) Covers
(a) Any tank cover not integrally cast with the tank shall be
so installed that the joint with the tank sidewall is
permanently sealed so as to be watertight.
(b) All covers shall be so designed and --onstructed as to
withstand a minimum of seven feet of saturated earth cover
above the tank top.
F. Inlet and Outlet•Device Materials
(1) Inlet and outlet devices shall be sanitary tees, or baffles
constructed of acid resistant concrete, acid resistant
fiberglass or plastic.
(2) Sanitary tees shall be glued to the inlet or outlet pipes.
Baffles shall be integrally cast with the tank, affixed with
a permanent waterproof adhesive or affixed with stainless
steel connectors, top and bottom.
- 3 -
i 2. DESIGN
All tanks, regardless of material or method of construction, shall
conform to the following design criteria:
A. The LIQUID DEPTH of any septic tank of compartment thereof
shall be not less than 30 inches. A liquid depth greater
than six and one-half feet shall not be considered in de-
termining tank capacity.
B. No tank or compartment thereof shall have an inside horizontal
dimension less than 24 inches.
C. Inlet and outlet connect -ions of the tank thereof shall be sub-
merged by means of ven ., sanitary tees or baffled.
D. The space in the tank between the liquid surface and the top
of the inlet and outlet baffles or sanitary tees shall be not
less than 20 percent of the total required liquid capacity,
except that in horizontal cylindrical tanks this space shall
be not less than 15 percent of the total required liquid
capacity.
E. The inlet baffle or sanitary tee shall extend at least six
inches but not more than 20 percent of the total liquid depth
• below the liquid surface and at least one inch above the crown
of the inlet sewer,
F. The outlet baffle or sanitary tee and the baffles or sanitary
tees between compartments shall extend below the liquid surface
a distance equal to 40 percent of the liquid depth except that
the penetration of the indicated baffles or sanitary tees for
horizontal cylndrical tanks shall be 35 percent of the total
liquid depth. They also shall extend above the liquid surface
as required in D. above. In no case shall they extend less
than six inches above the liquid surface.
G. There shall be at least one inch between the underside of the
top of the tank and the highest point of the inlet and outlet
devices.
H. The inlet invert shall be not less than three inches above the
outlet invert.
I. The inlet and outlet shall be located opposite each other along
the axis of maximum'dimension. The horizontal distance between
the nearest points'of the inlet and outlet deices shall be at
least four feet.
0
• J. Sanitary tees shall be at least four inches in diameter. Inlet
baffles shall be no less than six inches or no more than 12
inches measured from the end of the inlet pipe to the nearest
point on the baffle. Outlet baffles shall be six inches meas-
ured from beginning of the outlet pipe to the nearest point on
the baffle.
K. Access to the septic tank shall be as follows:
(1) There shall be one or more manholes, at least 20 inches least
dimension, and located within six feet of all walls of the
tank. The manhole shall extend through the cover to a point
within 12 inches but no closer than six inches below finished
grade. The manhole cover shall be covered with at least six
inches of earth.
(2) There shall be an inspection pipe of at least four inches
diameter or a manhole over both the inlet and outlet devices.
The inspection pipe shall extend through the cover and be
capped flush or above finished grade. A downward projection
of the center line of the inspection pipe shall be directly
in line with the center line of the inlet, or outlet device.
L. Multiple tanks
• (1; Where more than one tank is used to obtain the required liquid
volume, the tanks shall be connected in series.
•
(2) Each tank shall comply with all other provisions of Section I. A.
(3) No more than four tanks in series can be used to obtain the
required liquid volume.
MAINTENANCE SUGGESTIONS -
Inspect the tank annually and have the tank cleaned when the scum is
3 inches or less above the outlet baffle and/or when the sludge level is
8 inches or less below the outlet baffle.
3. LOCATION
A. The sewage tank shall be placed so that access is convenient
for the removal of liquids and accumulated solids.
B. The sewage tank shall be placed on firm and settled soil
capable of bearing the weight of the tank and its contents.
- 5 -
• C. Sewage tanks shall be set back the following distances from
the features given below:
•
•
Feature
Water Supply Well and Buried
Water Suction Pipe
Buried Pipe Distributing
Water Under Pressure
Buildings
Property Lines
The ordinary High Water Mark of:
Natural Environment Lakes
and Rivers
Recreational Development
Lakes and Rivers
General Development Lakes
and Streams
Wild River
Scenic River
Designated Tributaries of
Wild, Scenic, and Recreational
Rivers
Wetlands
Minimum Setback Distances (feet)
75'
10'
20'
20'
150*
75*
50*
150*
100*
75*
75'
*Required for new developments and where practicable, for existing
developments.
4. SURFACE FLOODING
Sewage tanks shall not be placed in flood plains delineated by lo0al
ordinances adopted in compliance with the Statewide Standards for
Management of Flood Plain Areas of Minnesota Minn. Reg. NR 5-93T,
or in areas for which regional floodinformation is available from
the Department of Natural Resources, except that in areas where ten-
year flood information is available from and/or approved by the
Department of Natural Resources.
- 6 -
•
III. DISTRIBUTION OF EFFLUENT
1. BY GRAVITY FLOW OVER THE SOIL TREATMENT AREA
A. Level Ground
Where the elevation difference of the ground surface does not
exceed 28 inches in any direction within the soil treatmrit area,
the sewage tank eff- ant may be directed to the soil tr atment
area through a distribution box.
(1) ,The box shall be watertight with a removable cover and
shall be constructed of durable materials not subject to
excessive corrosion or decay. The minimum inside dimen-
sion shall be at least ten inches.
(2) The inverts of all outlets shall be at the same elevation
as measured from a liquid surface in the bottom of the box.
(3) The inlet invert shall be at least one inch above the outlet
inverts.
(4) The outlet inverts shall be at least four inches above the
distribution box floor.
• (5) Each drainfield trench line shall be connected separately to
the distribution box and shall not be subdivided.
When sewage tank effluent is delivered to the distribution
box by pump, either a baffle wall shall be installed in the
distribution box or the pump discharge shall be directed
against a wall or side of the box on which there is no out-
let. The baffle shall be secured to the box and shall ex-
tend at least one inch above the crown of the inlet flow line.
B. Sloping Ground
Where the elevation difference of the ground surface exceeds
28 inches in any direction within soil treatment area a drop box
shall be installed at the head end of each lateral line. Connec-
tions between drop boxes shall re b_, wa' right pipes. (See
Figure 2)
(1) The drop box shall be watertight and constructed of durable
material- not subject to excessive corrosion or decay. The
minimum inside dimension shall be at least ten inches, un-
less the box is to be used as a valve box. Then each outlet
shall have at least eight inches of sidewall space and the
side of any outlet shall be at least six inches from any
corner.
- 7 -
•
(2) The invert of the inlet pipe shall be at least one inch
higher than the invert of the outlet pipe to the next trench.
(3) The invert of the outlet pipe to the next trench shall be at
least two inches higher than the invert of the outlet pipe
of the trench in which the box is located.
(4) When sewage tank effluent is delivered to the drop box by a
pump, the pump discharge shall be directed against a wall or
side of the box on which there is no outlet.
(5) The drop box shall have a removable cover either flush or
above finished grade or covered by no more than six inches
of soil.
IV. DRAINFIELD - Final treatment and disposal of all sewage tank
effluent shall be by means of soil treatment.
1. SIZING
Indicated average percolation rat is 27.5 minutes per inch for
the primary site and 23.3 minutes per inch for the alternate site.
A. Total a ainfield area is 1002 ft2
• B. Drainfield trench bottom width is 31.
C. TOTAL lineal feet of drain tile is 3349.
D. This requires 5 laterals of 66' in length.
See Figure 1 for typical plac3ment.
E. Minimum spacing of laterals is 7.5 feet from center to center.
2. LOCATION
A. On slopes in excess of 12 percent the soil profile FiAall be
carefully evaluated in the location of the propoe-4d soil treat-
ment area and downslope to identify the presence of layers
that may cause sidehill seepage. In no case shall. a trench be
located within 15 feet of such a layer surfacing on the downslope.
B. Bt ;onstruction shall be .limited to areas having natural slopes
of less than six percent.
C. Any soil treatment area other than seepage pits shall be set
back the following distances from the features gl.ven below:
•
.•
Feature
Any other water supply well or buried
water suction pipe
Buried pipe distributing water under pressure
Building
Property line
The ordinary H ter Mark of:
Natural Envircir AkeQ and Streams
g Recreational Development Lakes and Rivers
General Development .akes and Streams
Wild River
Scenic River
Designated Tributari-a of Wild, Scenic, and
Recreational Rivers
Set back distance
in feet
20'
20'
201
150'*
75'*
50'*
150'*
100'*
75'
Wetlands 75'
*Required for new developments and where practicable, for existing
I-velopments.
3. DESIGN AND CONSTRUCTION
A. The bottom of trenches and beds shall be at least three feet
above the water table or bedrock.
B. The bottom of the trench or bed excavation shall --vel.
The bott,.i and sides of the trench or 'A excavat-on to the
level of the filter material shall be z--arified to remove
smears left by the construction equipment and footprints. All
loose material shall be removed from the excavation The
bottom of the excavation shall not be driven on or walked on
aft r scarification.
C. When the soil percolation rate at the bottom of the trench or
bed is slower than 15 minutes per inch, no vehicle or excava-
• tion equipment shall be allowed on the trench or bed area.
Excavation shall be by back hoe or other means t-' t allow the
equipment wheels o., tracks to remain on the sur :� soil.
- 9 -
1
�r
•
40
D. There shall be a layer of 12 inches of filter material in
the bottom of the trenches and beds placed as shown in
Figure 3.
E. Distribution pipe used in trenches or beds for gravity flow
distribution shall be at least four inches in diameter and
constructed of sound and durable material not subject to
corrosion or decay or to loss of strength under continuously
wet conditions. The ends of each lateral shall be capped.
(1) Agricultural drain tile shall be in 12-inch lengths and laid
with I./4-inch open joints on grade boards. Ali open joints
shall be protected on top by strips of asphalt -treated
building paper at least ten inch.:s long and three to six
inches wide or by other acceptable means.
(2) Perforated plastic pipe shall be laid with one row of - r-
forations on the bottom. Perforations shall be at least
1/2-inch in diameter and spaced no farther than 12 inches
aF:Art.
(3) Other devices may be used to distribute sewage tank effluent
over the soil ,'eatme.t area upon approval of the local ad-
ministrator of the sanitary ordinance.
(4) The distribution pipes shall be laid 19vel or on a uniform
slope away from the sewage tank of no more than four inches
pe. 100 feet.
F. The filter material shall be coverfld with untreated building
paper or a two-inch layer of hay or straw or similar, ap-
proved permeable materials.
G. The trenches or beds shall be backfilled with the excavated
material and slightly crowned above finished grade to allow
for settling. The backfill shall not be compacted to a density
greater than that of the original soil.
H. The minimum depth of cover over the distribution pipes shall be
at least eight inches.
I. The maximum depth of cover over the distribution pipes shall be
no more than 36 inches and preferably 24 inches.
J. A grass cover shall be catablished over th_- soil treatment area.
K. See Figure 3 for further detail.
- 10 -
Pt-4TP I N T7,. M-#10, 110 LA.HVMAAIlDCNII' 8 d%Kl1>
41 ; I N"v=I I
IM-lowm-
AP"s -