HomeMy WebLinkAboutWater Sample Results ReportTri�i i lirn Lloyd Ii Lr�°
9300 Poplar Bridge Road •Bloomington, MN 55437 • (952) 563-4904
sample Re�u1�: I2epO� t
.Report Date: December 15, 2011
Client: City of Orono
Address: PO Box 66
Orono, MN 55323
Sample Collector: BARRY
Collection Date: 12/ 13/ 11
Collection Time: 10:00 ,�
Client ID: 1105 S. Brown Road
Received By: JFD
Received Date/Time: 12/ 13/ 11 11:03
Sample Condition Upon Receipt:
■ Acceptable
❑ Other
Sam le ID
AA58260
Analysis Name
Analysis
Analysis
Analyst
Combination
Analysis Unit
Reference
Start Date
Result
P/A total coliform
Readycult
12/ 13/ 11
JFD
Absent
coliform/ 100mL
Arsenic
EPA 200.7
12/ 14/ 11
DJW
7.954
ug/L
Copper
EPA 200.7
12/15/11
DJW
1.611
ug/L
Lead
EPA 200.7
12/ 14/ 11
DJW
1.52
ug/L
Nitrate as N
EPA 353.2
12 13 11
JFD
<0.02
m L
The analyte(s) reported, for the samples) listed above, meet standards set by the
Minnesota Department of Health and U. S. Environmental Protection Agency for safe
drinking water.
MCL (maximum contaminant level) set by the EPA for Lead 15ug/L
MCL (maximum contaminant level) set by the EPA for Arsenic l0ug/L
MCL (maximum contaminant level) set by the EPA for Nitrate lOmg/L
MCL (maximum contaminant level) set by the EPA for Copper 1300ug/L
Approved by: -�-1 ��� �
Joe Dusek
Microbiologist
Approved by:
Laboratory Identification Number: 027-053-355
Deb Weltzin
Chemist
The results in this report apply only to the above listed samples. All routine quality
assurance procedures were followed, unless otherwise noted. This analytical report must
be reported in its entirety. All methods are certified by the Minnesota Department of
Health, unless otherwise noted. EPA 200.7 for the analysis of Lead in drinking water is
not certifiable by the MDH.
Page 1 of 1