HomeMy WebLinkAboutNavWaterTower-54. Finish Painting:
Inside: Two coats of Tnemec #272 topox. Recommended coverage - 140
sq. ft. per gallon for a dry film thickness of 5.4.. Total
dry mil thickness - 12.0 ails. Tint first coat to insure
properccoverage.
Outside: Two coats of Tnemec Gloss, Recommended coverage rate - 320
sq ft. per gallon fqr a dry film thickness of 2.0 mils.
Tint first coat to insure proper coverage. Color to be
selected by engineer.
D. AREAS:
Inside: 4,700 sq. ft.
Outside: 11,250 sq. ft.
E. THICKNESS TEST:
Dry mil thicknesses to be tested with Mitcrotest Gage.