HomeMy WebLinkAboutNavWaterTower-1'77 ,' A V. .m/nlr+.. P_A. :N�TI7.i-Q S!x iC-T10Ns . A. SPECIFICATIONS: All material and workmanship to be in accordance with the specification issued for this contract by Hilly Engineering Company Long take, Minneid'tr_ 35356 11. SHOP: 1. Surface preparation: :All surfaces to be Grit blasted per SSPC #6 (commercial Blast) 2. Painting: No Paint within 2" of field welded edges or inside tubular columns. Inside: A Prime coat of Tnemec #272 Topox. Recommended coverage rate 240 sq. ftb per gallon for a dry mil thickness of 3 mils. Thin with VNEMEC 273 Thinner. Outside: A prime coat of Tnemec 880. Recommended coverage rate 300 sq. ft. per gallon for a dry mil thickness of 2.2 mils. Thin with Tnemae #883 Thinner Special Note: Do tint stack plates wet. C. FIELD: 1. Surface Preparation! Clean all unpainted and abraded areas by sand blasting per SSPC #6 (Commercial Blast) bs E0 2. Spot Painting: All unpainted and abraded areas to✓spot;'paint with same,coating as was used in shop. 3. Whip Blasting: In order for the field coats of inside paint,to r adhere to the shop primer of Topox, all inside M O $ areas should be scarified by whip blasting. A DILLS ENGINEERING Cp , LONG L4V&, MINA 200 M Gal, DEW T 6 T P'oe Orono, Hinni2ola P1 (Sh't l) Pi-rTs u mi-Des Motm m Stead. CawPANY r ENGINEERS -MANUFACTURNM—COM'Mt Mott > Data Contract 683