Laserfiche WebLink
AQUAPO <br /> Sprin lers <br /> RECEr. <br /> Job #14498073 <br /> JUN 09 2023 <br /> Backflow Test Report CITY OF ORONf <br /> Location & Customer Information <br /> Complete Job Address Location Contact Name (Owner) <br /> 430 Brown Road South, Wayzata, MN 55391 Cory Shannon <br /> USA <br /> Location Contact Phone Number <br /> (612) 730-4069 <br /> Were you able to complete the Backflow <br /> Test Today? <br /> Yes <br /> Device Information <br /> Test Date Device Type <br /> 2023-05-05 RPZ <br /> Device Manufacturer Device Model <br /> Wilkens 975XL <br /> Device Serial Number Device Size <br /> 274-0558 1.0" <br /> Device Location <br /> Back <br /> Test Results <br /> Test: Pass OR Fail Shut-Off Valve #1 <br /> Passed Closes Tightly <br /> Shut-Off Valve #2 Check Valve #1: Tightness <br /> Closes Tightly Closes Tight <br /> Check Valve #1: Spring Pressure Air-Inlet Valve OR Relief Valve Opened at <br /> Differential PSI <br /> PSI 3.50 <br /> 4.00 <br /> Check Valve #2: Tightness ( RPZ ONLY ) Check Valve #2: Spring Pressure <br /> Closes Tight Differential ( RPZ ONLY ) <br /> PSI <br /> 2.00 <br /> Did you tag device? <br /> Yes <br /> Tester Information <br />