HomeMy WebLinkAbout1978-05-22 Septic System Design & Soil Test ReportA
May 22, 1978
Mr. Don Roderick
1925 County Road 24
Long Lake, Minnesota 55356
545 Indian Mound
Wayzata, Minnesota 55391
(612)473-4224
-7kiy P19r wN ""-D
Re: Percolation Test for Tract A, Registered Land Survey No. 1275
Orono, Minnesota, Job No. 11-78-22
Dear Mr. Roderick:
Enclosed is information requested for an on -land sewage treatment
system for the above -referenced lot.
The drainfield information was based on percolation tests and soil
borings performed on May 10, 11, 18, and 19, 1978.
The average rate of percolation for the primary site, as tested,
was 32.7 minutes/inch. The average rate of percolation for the
secondary site, as tested, was 20.0 minutes/inch. The location of
the percolation test holes are indicated in Figure 1.
Soil borings were augered to a depth of eight feet (81). The soil
logs of the soil borings are shown in Table 1. The location of
the soil borings, as well as the soils map, are shown in Figure 1.
Because of an acceptable percolation rate of 32.7 minutes/inch and
because of an acceptable depth to the water table,'*a conventional
on-site sewage treatment system is recommended for the priniary
site. Due to the high water table, and the steepness of the slope,
an "innovative shallow trench system" is recommended for the
secondary site.
Stated percolation rates are averaged for the location shown, and
no guarantee is implied or expressed that these conditions exist
for the entire test area.
If you have any questions, please do not hesitate to contact me.
Sincerely,
EUGENE A. HICKOK & ASSOCIATES
Ames P. DeBenedet, P. E.
JPD/jel
Enclosures
SOIL BORING #1
Depth
0.0 - 1.0'
1.0 - 2.1'
2.1 - 8.0'
TABLE #1 - SOIL LOGS
Material
Dark brown loam
Yellowish brown silty loam
Olive brown silty clay
Water table encountered at -4.3'
SOIL BORING #2
Depth Material
0.0 - 0.9' Dark brown silty loam
0.9 - 2.0' Yellowish brown silty loam
2.0 - 8.0' Olive brown silty clay
Water table encountered at -6.0'
SOIL BORING #3
Depth Material
0.0 - 0.7' Dark brown loam
0.7 - 2.0' Yellowish brown silty loam
2.0 - 8.0' Olive brown silty clay loam
Water table was not encountered within 8.0' of the surface.
k
Y�fr1
°1h
u
O
`— 9s -rg —
i
cn
r I
c�
WON
0
c
Dai
SEPTI c_
E.A. HICKOK & ASSOCIATES JUNL I` I&
HYDROLOGISTS -ENGINEERS f`1V11
MINNEAPOLIS -MINNESOTA
I
�i
z
4
Z
-0
O
7 0
�oN (LbpF�1,IU<
E�EJP�'(la�� r�PP
O
X `—
E.A. HICKOK & ASSOCIATES JANE ME>
HYDROLOGISTS -ENGINEERS
MINNEAPOLIS -MINNESOTA
r_
a0
�
0�
c0
o
Y
O
X `—
E.A. HICKOK & ASSOCIATES JANE ME>
HYDROLOGISTS -ENGINEERS
MINNEAPOLIS -MINNESOTA
j t m �rnz
1 0 -urn
z Co m -n
r
rn xocz0
U)
o I
O
o r m C `::. , .�� c
X -- ---- ---i --- m-1
zr
.� o i
-4 -i
.� o ooc o
oc -uz-u
rnrD1
Zm VrTiq� x z
�m
--
___ oA �'9z cnc -nA0Z� ;'r-
-+----------- rn �AA pi C) mac_ r
z SC)
w0 m-1p-� m:5
T I 1 `\� m %i -0 Orn m 2-4� o z z v U)
---� rnOSBMi -vZ r-m;z moc rn
� N �--1--- - - - o c Z —A C oo i za "D � [-
.4--- cn
mr X>w or -xc i*a) m
_ �p-4 o—� -4p mzxz
-40 r z oxo mzm Fn zmx00 D
�' m s r�nc z� m z ovrnrn -�o i�DN r
a w m rn� rn m� �m o� v m
cnm =-� o -u< mm� LO
o m x�m m� Wim{
D m
H
CA
J
Z 7Y w� " g � � 9 �p Z_\j
7-0
t-- 3
-� 0
z
r�
�07 00
NZ
LA
IL
Id
o
DOn1 ZOpEILI C -IL E.A. MKOK & ASSOCIATES
-f ow -p GOm c_;r& l l ot) HYDROLOGISTS -ENGINEERS
MINNEAPOLIS -MINNESOTA
SPECIFICATIONS FOR PROPOSED ON-SITE SEWAGE DISPOSAL SYSTEM
CONVENTIONAL SYSTEM
LOCATION: Don Roderick, System Design for Tract A, Registered Land
Survey No. 1275 Orono, Minnesota, Job No. 11-78-22
DATE: May 31, 1978
I. SEWAGE TANK - TWO 1000 -gallon LIQUID CAPACITY tanks, IN SERIES,
manufactured and installed in compliance with the
following specifications. See Figure 1 for location.
1. MATERIALS
A. General
All tanks, regardless of material or method of construction shall
be:
(1) Water tight
(2) So designed and constructed as to withstand all lateral earth
pressures under saturated soil conditions with the tank empty.
(3) So designed and constructed as to withstand a minimum of seven
feet of saturated earth cover above the tank top.
In addition, the following specifications apply to specific mater-
ials as indicated.
B. Precast Concrete Tanks
(1) Precast concrete tanks shall be constructed of at least a
4,000 psi (pounds per square inch) core test, air entrained
concrete mix.
(2) Precast concrete tanks shall be cured to at least a seven-day
strength before installation.
C. Fiberglass and Plastic Tanks
Fiberglass and plastic tanks shall be designed and constructed to
meet the requirements in Section I - a. above.
D. Metal Tanks
Metal tanks shall have a wall thickness of at least eight gauge
corrosion resistant alloys and shall be coated inside and out
with at least one coat of bitumastic seal, Koppers 300-M, or by
other equivalent means. Tanks shall be carefully installed so as
not to puncture or damage the seal coating.
E. Block or Sectional Tanks
(1) Rectangular Blocks
(a) Rectangular blocks shall be laid on an approved bottom.
Block shall be at least eight inches thick, constructed
of a 4,000 psi core test concrete mix, and cured to a
28 -day strength before installation.
(b) Rectangular blocks shall be laid either with mortar
joints or filled cores.
(c) There shall be at least two coats of 1/4 inch thick
concrete plaster placed on the inside of the block tank.
There shall be at least two hours elapsed time between
coats. The plaster coat shall start at the bottom course
and work up.
(2) Circular Block Tanks
(a) Circular blocks shall be carefully placed on an approved
bottom. Circular blocks shall be at least two inches
thick and constructed of a 4,000 psi core test concrete
mix, cured to a 28 -day strength before installation.
(b) There shall be at least two coats of 1/4 inch thick
concrete plaster placed on the inside of the block tank.
There shall be at least two hours elapsed time between
coats. The plaster coat shall start at the bottom course
and work up.
(3) Sectional Tanks
(a) A sectional tank shall have an entire section cast as an
integral unit.
(b) A sectional tank shall have two or more sections and shall
have at least one joint below the level of the outlet in-
vert of the tank.
(c) Sectional tanks shall have an integrally cast bottom, or
shall be laid on an approved bottom.
(d) The joint or joints shall be permanently sealed so as to
be watertight.
(4) Bottoms
(a) Any tank not having an integrally cast bottom shall not be
installed when the water table is closer than three inches
to the bottom of the excavation.
- 2 -
(b) If the bottom is poured -in-place concrete, it shall be
at least four inches thick and extend to at least four
inches outside the tank wall. A concrete mix of at
least one part cement, two parts washed sand and three
parts washed rock shall be mixed before placement in
the excavation.
(c) If a starter ring is used, it shall be constructed of a
4,000 psi core test concrete mix, cured to a seven-day
strength before installation. It shall extend at least
one inch beyond the tank wall, inside and out. A bottom
shall be poured of concrete mix defined in Section (b)
above. It shall extend at least two inches above the
starter ring and shall be at least four inches thick.
(d) If a precast bottom is used, it shall be made of a 4,000
psi core test concrete mix, cured to a seven-day strength
before installation. It shall extend at least one inch
beyond the tank wall, or be cast integrally with the
bottom section.
(e) A sectional tank not having an integrally precast bottom
shall have a four -inch thick bottom poured within the
tank walls.
(5) Covers
(a) Any tank cover not integrally cast with the tank shall be
so installed that the joint with the tank sidewall is
permanently sealed so as to be watertight.
(b) All covers shall be so designed and constructed as to
withstand a minimum of seven feet of saturated earth cover
above the tank top.
F. Inlet and Outlet Device Materials
(1) Inlet and outlet devices shall be sanitary tees, or baffles
constructed of acid resistant concrete, acid resistant
fiberglass or plastic.
(2) Sanitary tees shall be glued to the inlet or outlet pipes.
Baffles shall be integrally cast with the tank, affixed with
a permanent waterproof adhesive or affixed with stanless
steel connectors, top and bottom.
2. DESIGN
All tanks, regardless of material or method of construction, shall
conform to the following design criteria:
- 3 -
A. The LIQUID DEPTH of any septic tank of compartment thereof
shall be not less than 30 inches. A liquid depth greater
than six and one-half feet shall not be considered in de-
termining tank capacity.
B. No tank or compartment thereof shall have an inside horizontal
dimension less than 24 inches.
C. Inlet and outlet connections of the tank thereof shall be sub-
merged by means of vented, sanitary tees or baffled.
D. The space in the tank between the liquid surface and the top
of the inlet and outlet baffles or sanitary tees shall be not
less than 20 percent of the total required liquid capacity,
except that in horizontal cylindrical tanks this space shall
be not less than 15 percent of the total required liquid
capacity.
E. The inlet baffle or sanitary tee shall extend at least six
inches but not more than 20 percent of the total liquid depth
below the liquid surface and at least one inch above the crown
of the inlet sewer.
F. The outlet baffle or sanitary tee and the baffles or sanitary
tees between compartments shall extend below the liquid surface
a distance equal to 40 percent of the liquid depth except that
the penetration of the indicated baffles or sanitary tees for
horizontal cylindrical tanks shall be 35 percent of the total
liquid depth. They also shall extend above the liquid surface
as required in D. above. In no case shall they extend less
than six inches above the liquid surface.
G. There shall be at least one inch between the underside of the
top of the tank and the highest point of the inlet and outlet
devices.
H. The inlet invert shall be not less than three inches above the
outlet invert.
I. The inlet and outlet shall be located opposite each other along
the axis of maximum dimension. The horizontal distance between
the nearest points of the inlet and outlet devices shall be at
least four f=et.
J. Sanitary tees shall be at least four inches in
baffles shall be no less than six inches or no
inches measured from the end of the inlet pipe
point on the baffle. Outlet baffles shall be
ured from beginning of the outlet pipe to the
the )affle.
- 4 -
diameter. Inlet
more than 12
to the nearest
six inches meas -
nearest point on
Feature Minimum Setback Distances Cfeet)
Buildings
Property Lines
The ordinary High Water Mark of:
Natural Environment Lakes
and Rivers
Recreational Development
Lakes and Rivers
General Development Lakes
and Streams
Wild River
Scenic River
Designated Tributaries of
Wild, Scenic, and Recreational
Rivers
10'
20'
150*
75*
50*
150*
100*
75*
*Required for new developments and where practicable, for existing
developments.
4. SURFACE FLOODING
Sewage tanks shall not be placed in flood plains delineated by local
ordinances adopted in compliance with the Statewide Standards for
Management of Flood Plain Areas of Minnesota (Minn. Reg. NR85-93),
or in areas for which regional flood information is available from
the Department of Natural Resources, except that in areas where ten
year flood information is available from and/or approved by the
Department of Natural Resources.
- 5 -
II. DISTRIBUTION OF EFFLUENT
1. BY GRAVITY FLOW OVER THE SOIL TREATMENT AREA
A. Level Ground
(1) The box shall be watertight with a removable cover and
shall be constructed of durable materials not subject to
excessive corrosion or decay. The minimum inside dimen-
sion shall be at least ten inches.
(2) The inverts of all outlets shall be at the same elevation
as measured from a liquid surface in the bottom of the box.
(3) The inlet invert shall be at least one inch above the out-
let inverts.
(4) The outlet inverts shall be at least four inches above the
distribution box floor.
(5) Each drainfield trench line shall be connected separately
to the distribution box and shall not be subdivided.
When sewage tank effluent is delivered to the distribution box
by pump, either a baffle wall shall be installed in the distri-
bution box or the pump discharge shall be directed against a
wall or side of the box on which there is no outlet. The baffle
shall be secured to the box and shall extend at least one inch
above the crown of the inlet flow line.
B. Sloping Ground
Where the elevation difference of the ground surface exceeds
28 inches in any direction within soil treatment area a drop box
shall be installed at the head end of each lateral line. Connec-
tions between drop boxes shall be by watertight pipes.
(See Figure 2)
(1) The drop box shall be watertight and constructed of durable
materials not subject to excessive corrosion or decay. The
minimum inside dimension shall be at least ten inches, un-
less the box is to be used as a valve box. Then each outlet
shall have at least eiqht inches of sidewall space and the
side of any outlet shall be at least six inches from any
corner.
(2) The invert of the inlet pipe shall be at least one inch
higher than the invert of the outlet pipe to the next
trench.
(3) The invert of the outlet pipe to the next trench shall be at
least two inches higher than the invert of the outlet pipe
of the trench in which the box is located.
(4) When sewage tank effluent is delivered to the drop box by a
pr�ap, the pump discharge shall be directed against a wall
or side of the box on which there is no outlet.
(5) The drop box shall have a removable cover either flush or
above finished grade or covered by no more than six inches
of soil.
III. DRAIN FIELD - Final treatment and disposal of all sewage tank
effluent shall be by means of soil treatment.
1. SIZING
Indicated average percolation rate is 32.7 minutes per inch for
the primary site and 20.0 minutes per inch for the alternate site.
The proposed flow rate into the system is based on the require-
ments for a four-bedroom house.
A. Total drainfield absorption area is 1200 square feet.
B. Drainfield trench bottom width is 3'.
C. TOTAL lineal feet of drain tile is 400.
D. This requires 5 laterals of 80 feet in length.
(See Figure 1 for typical placement.)
E. Minimum spacing of laterals is 7.5 feet from center
to center.
2. LOCATION
A. On slopes in excess of 12 percent the soil profile shall be
carefully evaluated in the loca*ion of the proposed soil
treatment area and downslope to identify the presence of
layers that mai► cause sidehill seepage. In no case shall a
trench be located within 15 feet of such a layer surfacing
on the downslope.
B. Bed construction shall be limited to areas having natural
slopes of less than six percent.
C. Any soil treatment area other than seepaqe pits shall be set
bacx the following distances from the features given below:
Feature
Set back distance
in feet
Water supply well less than 50 feet deep
and not encountering at least 10 feet of
impervious material 100
- 7 -
Feature
Set back distance
in feet
Any other water supply well or buried
water suction pipe 75
Buried pipe distributing water under pressure 10
Building 20
Property lines 20
The ordinary High Water Mark of:
Natural Environment Lakes and Streams 150*
Recreational Development Lakes and Rivers 75*
General Development Lakes and Streams 50*
Wild River 150*
Scenic River 100*
Designated Tributaries of Wild, Scenic, and
Recreational Rivers 75
*Required for new developments and where practicable, for existing
developments.
3. DESIGN AND CONSTRUCTION
A. The bottom of trenches and beds shall be at least three feet
above the water table or bedrock.
B. The bottom of the trench or bed excavation shall be level.
The bottom and sides of the trench or bed excavation to the
level of the filter material shall be scarified to remove
smears left by the construction equipment and footprints. All
loose material shall be removed from the excavation The
bottom of the excavation shall not be driven on or walked on
after scarification.
C. When the soil percolation rate at the bottom of the trench or
bed is slower than 15 minutes per inch, no vehicle or excava-
tion equipment shall be allowed on the trench or bed area.
Excavation shall be by back hoe or other means that allow the
equipment wheels or tracks to remain on the surface soil.
M_
D. There shall be a layer of 12 inches of filter material in
the bottom of the trenches and beds placed as shown in
Figure 3.
E. Distribution pipe used in trenches or beds for gravity flow
distribution shall be at least four inches in diameter and
constructed of sound and durable material not subject to
corrosion or decay or to loss of strength under continuously
wet conditions. The ends of each lateral shall be capped.
(1) Agricultural drain tile shall be in 12 -inch It Tths and laid
with 1/4 -inch open joints on grade boards. All open joints
shall be protected on top by strips of asphalt -treated
building paper at least ten inches long and three to six
inches wide or by other acceptable means.
(2) Perforated plastic pipe shall be laid with one row of per-
forations on the bottom. Perforations shall be at least
1/2 -inch in diameter and spaced no farther than 12 inches
apart.
(3) Other devices may be used to distribute sewage tank effluent
over the soil treatment area upon approval of the local ad-
ministrator of the sanitary ordinance.
(4) The distribution pipes shall be laid level or on a uniform
slope away from the sewage tank of no more than four inches
per 100 feet.
F. The filter material shall be covered with untreated building
paper or a two-inch layer of hay or straw or similar, ap-
proved permeable materials.
G. The trenches or beds shall be backfilled with the excavated
material and slightly crowned above finished grade to allow
for settling. The backfill shall not be compacted to a density
greater than that of the original soil.
H. The minimum depth of cover over the distribution pipes shall be
at least eight inches.
I. The maximum depth of cover over the distribution pipes shall be
no more than 36 inches and preferably 24 inches.
J. A grass cover shall be established over the soil treatment area.
K. See Figure 3 for further detail.