HomeMy WebLinkAboutM18-000081 - install gas fireplace & gas lineFrom: oronoinspector@ci.orono.mn.us
Sent: 07/10/2018 - 11:35 AM
To: roseville_builder_ops@hearthnhome.com
CC:
Subject: Inspection Report Individual
Inspection Report
1140 WYNDMERE RD
Permit Number:
M18-000081
Site Address:
1140 WYNDMERE RD, WAYZATA, MN 55391
Property Owner:
DAVID A GAGNE
Description:
INSTALL GAS FIREPLACE AND GAS LINE
Inspection Date: 07/10/2018
Inspection Type: Fireplace Rough In
Inspection Results: Correct Work. Call for Reinspection
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. Fireplace on main level. Venting and clearances are OK. Copper gas line. 1. Provide solid fire stop at top of Chase, poly not code compliant. 2. Provide draft
stop at maximum 10 feet in fireplace chase. Metal fire stop must be provided.. 3. Provide air test for gas line. 4. Provide gas line air test. correct and call for
reinspection. Jim H.
Sincerely,
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 07/30/2018 - 09:11 AM
To: roseville_builder_ops@hearthnhome.com
CC:
Subject: Inspection Report Individual
Inspection Report
1140 WYNDMERE RD
Permit Number:
M18-000081
Site Address:
1140 WYNDMERE RD, WAYZATA, MN 55391
Property Owner:
DAVID A GAGNE
Description:
INSTALL GAS FIREPLACE AND GAS LINE
Inspection Date: 07/30/2018
Inspection Type: Mechanical - Rough In
Inspection Results: Work Satisfactory: Proceed
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. Venting and clearances were OK from inspection on July 10, 2018. Copper gas line air test was holding at 40 psi on inspection of July 16, 2018. Fire stops and
corrections provided per prior rough in inspection. OK to cover. Jim H.
Sincerely,
,--5 -
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here