HomeMy WebLinkAboutM18-000072 - mechanicalFrom: oronoinspector@ci.orono.mn.us
Sent: 07/24/2018 - 03:50 PM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 07/24/2018
Inspection Type: Mechanical - Rough In
Inspection Results: Correct Work & Proceed
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. Underground gas line from house to generator and then to detached garage. Depth is OK. Underground gas tight gas line with tracer wire provided. Four
powered bath fans with insulated duct and terminated out roof on upper level. Two remote bath fans for master suite on main level. New supplies and returns for
master suite. New supplies and returns for kitchen, Butlers??s pantry and dining room. New supplies and returns in lower level tied to existing ductwork. All
ductwork to be Aerosealed. Provide air test results. OK to continue in these areas. Jim H.
Sincerely,
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 07/30/2018 - 03:02 PM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 07/30/2018
Inspection Type: Mechanical - Rough In
Inspection Results: Correct Work & Proceed
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. In floor heat rough in. Pex tubing with air test is holding. Boiler venting through unused Masonary chimney. Exhaust and combustion air OK. 1. Seal all
penetrations in all chases. Correct and OK to continue. Jim H.
Sincerely,
,--5 -
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 09/28/2018 - 09:30 AM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 09/28/2018
Inspection Type: Mechanical - Rough In
Inspection Results: Work Satisfactory: Proceed
Inspection Status: General Comment
1. 80 PSI test on 100 PSI gauge for in floor heat installed on uponor quick track system OK
Sincerely,
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 01/02/2019 - 11:24 AM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 01/02/2019
Inspection Type: Mechanical - Rough In
Inspection Results: Work Satisfactory: Proceed
Inspection Status: General Comment
1. Inspection of insulated duct work in garage work satisfactory ok to cover this section.
Sincerely,
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 05/07/2019 - 01:28 PM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 05/07/2019
Inspection Type: Mechanical - Rough In
Inspection Results: Work Satisfactory: Proceed
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. Detached garage. Garage heater vent- clearances OK. Attic insulation shield provided. Flash shield gas line with air test holding at 50 psi since 4/23/19. OK to
continue. Jim H.
Sincerely,
,--5 -
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 06/25/2019 - 01:32 PM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 06/25/2019
Inspection Type: Mechanical - Final
Inspection Results: Correct Work. Call for Reinspection
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. Boiler TPR valve OK . Closed system. 2 air handlers are balanced. Furnace in garage in rated closet. Other 2 furnaces OK. All ductwork has been areosealed
with test results posted in LL mech room. 1. Provide sleeve for gas line thru masonry wall. 2. Bond gas tight gas line. 3. Repair kinked condensate line on
furnace in garage. 4. Paint any exterior black iron gas fittings. Label all gas lines. Correct and call for reinspection. Jim H.
Sincerely,
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!
From: oronoinspector@ci.orono.mn.us
Sent: 02/24/2020 - 09:27 AM
To: GRSCHEDULING@GENZRYAN.COM
CC:
Subject: Inspection Report Individual
Inspection Report
1300 BRACKETTS POINT RD
Permit Number: M18-000072
Site Address: 1300 BRACKETTS POINT RD, WAYZATA, MN 55391
Property Owner: FERNDALE PROPERTIES LLC
Description: base 2- new forced air units and I boiler with infloor for heating
Inspection Date: 02/24/2020
Inspection Type: Mechanical - Final
Inspection Results: Permit Finaled
Inspection Status: General Comment
CITY OF ORONO
2750 KELLEY PARKWAY
ORONO, MN 55356
PH: (952) 249-4600
FAX: (952)249-4616
1. House remodel. Corrections provided for mech final. Work complete, permit finaled. Jim H.
2. Boiler TPR valve OK . Closed system. 2 air handlers are balanced. Furnace in garage in rated closet. Other 2 furnaces OK. All ductwork has been areosealed
with test results posted in LL mech room. 1. Provide sleeve for gas line thru masonry wall. 2. Bond gas tight gas line. 3. Repair kinked condensate line on
furnace in garage. 4. Paint any exterior black iron gas fittings. Label all gas lines. Correct and call for reinspection. Jim H.
Sincerely,
Roger Peitso
Building Official
952-249-4625
To schedule your inspections please call: (952) 249-4600
To schedule your inspection online Click Here
CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY!