Loading...
HomeMy WebLinkAbout10-23-1985 Septic System Design MemoSYSTEM DESIGN FOR SHAVER CORPORATION LOT 4, BLOCK I, ABINGDON GLEN ORONO, MINNESOTA 10-23-85 1. Percolation Rate, Type of System. 16.0 minutes per inch for the primary site(hoIes 1-4). Standard system with trenches no deeper than 2 feet in the natural soil. 2. Proposed Flow Rate. 600 G.P.D. 3. Soil Treatment Area Required. 600 G.P.D. X 1.67 percolation rate factor = 1000 Sq. Ft. 4. Size and Number of Trenches. 3 trenches 3 feet wide and 111 feet long = 1000 Sq. Ft. These trenches would be spaced a minimum of 7.5 feet apart center and be 1-2 feet deep in the na­ tural soil. 5. Drainfield Rack Needed. 55.6 cubic yds. of rock is needed to have 12 inches under and 2 inches over a 4 inch distribution pipe. 6. Septic Tanks. Two septic tanks each of 1000 gallons are recommended. It appears that grav­ ity flow can be used to reach the drainfield area if the house is kept high enough. If not, then a third pumping t.vok and pump would be needed. 7. Additional Information. Grading should be done to divert runoff water away from the drainfield area. No grading or construction traffic is allowed in either drainfield area and all construction and materials should adhere to the provisions of the City of Orono. If there are any other questions, please contact me. Sincerely, PERCOR, ijc. Mark S. Gronberg, P.E. ^ PCA certified