HomeMy WebLinkAbout06-28-2022 Septic - NON-CompliantSP TESTING INC. Steven B. Schirmers — 951 Katydid Lane NE —St. Michael, MN 55376 Cert. No 627 — State License #394 — Phone 763-497-3566 — Fax 763-497-5011 www.st)testing.wastewaterffi)comcast.net — schirmerswastewater.com Revised July 28, 2022 October 5, 2021 Pat Spencer 501 N. Ferndale Rd. Orono, MN A compliance inspection was completed for the existing on-site sewage treatment system for installing a new pump tank. The system consists of 2-1000 gallon septic tanks, 1-1000 gallon pump tank & a trench system with 7 trenches 50' long each, 3501in.ft. = 1050 sq.ft. of gravelless pipe, built in 1996. Soil boring #1 found mottled soil (redox features) at 5.31, elev. 95.0 & the bottom of the lowest gravelless pipe at elev. 98.9 leaving a 3.9' separation from the bottom of the gravelless pipe & redox features. Soil boring #2 found mottled soil at 61, elev. 93.7 & the bottom of the lowest gravelless pipe at elev. 98.6 leaving a 4.9' separation. This system meets the required 3' separation & is classified as in compliance with Minnesota Chapter 7080 rules. This site has an existing on-site sewage treatment system. The pump tank is plastic & the side wall is pushing in. Due to the limited access, the tank will need to be pumped & removed & install a new Infiltrator IM 1060 (1000 gallon) in the same foot print. Using the lowest floor at elev. 100.0, the ground at the 2"d tank is at elev. 99.3 & the top of the tank (2') is at elev. 97.3. The existing pump tank is at elev. 93.2 & the top of the tank (1.11) is at elev. 92.1. The top of the new tank must be at the (2') elev. 91.2.. Prior to installing the new pump tank, a tank Integrity report will need to be completed for the 1St & 2"d tanks. Upon those tanks passing the system can be fully classified as compliant. Steven B. Schirmers S_P TESTING, V, I C. „ Steven B, Schirmers • MPCA Cert -No. 627 951 Katydid Lane NE - St, Michael, MN 56376 - (763)'497-3566 FAX (763) 497-5011 State License #394 wwwsptesting.wastewater@comcast.net - schirmerswastewater.com eA cid- (u�il 0� °N+cz) V- o � 0- Li ' 65. J S I� 4iwG- IOU q, i S -P TESTING, INC. Steven B. Schirmers - MPCA Cert.No. 627 951 Katydid Lane NE - St. Michael, MN 65376 - (763) `497-3566 rAX (763) 407-5011 State License #394 wwwsptesting.wastewater@comcast.net - schirmerrwastewater.com I. MINNESOTAPOLLUTION CONTROL AGENCY Compliance inspection report form CY 520 Lafayette Road North Existing Subsurface Sewage Treatment System (SSTS) St. Raul, MN 55155-4194 Doc Type: Compliance and Enforcement Instructions: Inspector must submit completed form to Local Governmental Unit (LGU) and system owner within 15 days of final determination of compliance or noncompliance. Instructions for filling out this form are located on the Minnesota Pollution Control Agency (MPCA) website at htt s:JJwww, pca. state. mn,us/sites/default/fles/w-wwists4-31a. df. Property information Local tracking number: Parcel ID# or Sec/Twp/Range: Reason for Inspection.� Local regulatory authority info: f- jog 0 V4 -- Property address: r Own e0representative: Brief system description: a-looc9 g_[ SW -66 ^iii Y-� 1 r Pr ID '? - T C,0 S 5 u' t�ca t-111 System status System status on date (mm/dd/yyyy): 7-a-) EJ Compliant - Certificate of compliance* (Valid for,3 years from report date unless evidence of an imminent threat to public health or safety requiring removal and abatement under section 145A.04, subdivision 8 is discovered or a shorter time frame exists in Local Ordinance.) *Note.: Compliance indicates conformance with Minn. R. 7080.1500 as of system status date above and does not guarantee future performance. Owner's phone: (ol A . y 0 � ,;i o)9 M Noncompliant- Notice of noncompliance Systems failing to protect ground water trust be upgraded, replaced, or use discontinued within the time required by local ordinance. An imminent threat to public health and safety (ITPHS) must be upgraded, replaced, or its use discontinued within ten months of receipt of this notice or within a shorter period if required by local ordinance or under section 145A.04 subdivision B. Reason(s) for noncompliance (check all applicable) ❑ Impact on public health (Compliance component #1) - Imminent threat to public health and safety X Tank integrity (Compliance component #2) - Failing to protect groundwater 1 ,7 ❑ Other Compliance Conditions (Compliance component #3) - Imminent threat to public health and safety ❑ Other Compliance Conditions (Compliance component #3) - Failing to protect groundwater ❑ System not abandoned according to Minn. R. 7080.2500 (Compliance component #3) - Failing to protect groundwater ❑ Soil separation (Compliance component #5) - Failing to protect groundwater ❑ Operating permit/monitoring plan requirements (Compliance component #4) - Noncompliant - local ordinance applies Comments or recommendations Certification I hereby certify that all the necessary information has been gathered to determine the compliance status of this system. No determination of future system performance has been nor can be made due to unknown conditions during system construction, possible abuse of the system, inadequate maintenance, or future water usage. By typing my name below, 1 certify the above statements to be true and correct, to the best of my knowledge, and that this information can be used for the purpose of processing this form. Business name: t Inspector signature: (This document has been electronically signed) Certification number;-�0-a, 9 - License number: 14 Necessary or locally required supporting documentation (must be attached) ❑ Soil observation logs ❑ Other information (Jist)- https://www,pca.stato.mn.us wq-wwists4-31b • 412812021 Phone:�u qr1- t3 �1,vtc ❑ System/As-Built ❑ Locally required forms ❑ Tank Integrity Assessment ❑ Operating Permit • 651-296-6300 800-657-3864 • Use your preferred relay service Available in alternative formats Page 1 of 4 Property Address: S 0 >!�-V Business Name: L Date: e) 1. Impact on public health — Compliance component #1 of 5 Compliance criteria: System discharges sewage to the I [:]Yes* 0 No ground surface System discharges sewage to drain ❑ Yes* 0 No the nr ci irfnrc —f— System causes sewage backup into ❑Ye2No dwelling or establishment. Any "yes" answer above indicates the system is an imminent threat to public health and safety, Describe verification methods and results: Attached supporting documentation: ❑ Other: ® Not applicable Z. Tank integrity — Compliance component #Z of 5 Compliance criteria: System consists of a seepage pit, cesspool, drywell, leaching pit, orother pit"? Sewage tank(s) leak below their designed operating depth? ❑ Yes` ❑ No 1' Yes" ❑ No If yes, which sewage tanks) leaks: Any "yes" answer above indicates the system is failing to protect groundwater. 1411 4- a V,.,c? i t,.. - "4-,4 N1 `, Describe verification methods and results: Attached supporting documentation: ❑ Empty tank(s) viewed by inspector Name of maintenance business: License number of maintenance business: Date of maintenance: ❑ Existing tank integrity assessment (Attach) Date of maintenance _ (mmlddryyyy): (must be within three years) (See form instructions to ensure assessment complies with Minn- R. 7082.0700 subp. 4 B (7)) ❑ Tank is Noncornpiiant (pumping not necessary - explain below) ❑ other: https://www.pca.state.rnn.u5 651-296-6300 800-657-3864 • Use your preferred relay service Available in alternative formats wq-wwists4-31b • 412812021 Page 2 of 4 Property Address: tel,, Business Name- o_) �, J it I ( Date: 3. Other compliance conditions — Compliance component #3 of 5 3a. Maintenance hole covers appear to be structurally unsound (damaged, cracked, etc.), or unsecured? ❑ Yes* B No ❑ Unknown 3b. Other issues (electrical hazards, etc.) to immediately and adversely impact public health or safety? [❑ Yes* ❑ No ❑ Unknown *Yes to 3a or 3b - System is an imminent threat to public health and safety. 3c. System is non -protective of ground water for other conditions as determined by inspector? 3d. System not abandoned in accordance with Minn. R. 7080.2500? *Yes to 3c or 3d - System is failing to protect groundwater. Describe verification methods and results: Attached supporting documentation: ❑ Not applicable ❑ [:]Yes* ❑ No �t En Yes* [?No G' 4, Operating permit and nitrogen BMP* — Compliance component 44 of 5 El Not applicable Is the system operated under an Operating Permit? ❑ Yes Cl No If "yes", A below is required Is the system required to employ a Nitrogen BMP specified in the system design? ❑ Yes ❑ No If "yes", B below is required BMP = Best Management Practice(s) specified in the system design If the answer to both questions is "no", this section does not need to be completed. Compliance criteria: a. Have the operating permit requirements been met? 0 Yes ❑ No b. Is the required nitrogen BMP in place and properly functioning? ❑ Yes ❑ No Any "no" answer indicates noncompliance. Describe verification methods and results: .Attached supporting documentation: ❑ Operating permit (Attach) https;//www,pca.state.mn.u.s 651-296-6300 • 800-657-3864 + Use your preferred relay service Available in alternative formats wq-wwi5ts4-3Ib • 4/28/2021 Page 3 of 4 Property Address: I -Sy ..-�-s _ Business Name: IS* • �1� t , - Date: 5. Soil separation — Compliance component #5 of 5 Date of installation Jt -) i,_ ❑ Unknown (mmldd/yyyy) Shoreland/Welihead protectiontFood beverage lodging? Compliance criteria (select one): ❑ Yes rX No 52. For systems built prior to April 1, 1996, and ❑ Yes ❑ No* not located in Shoreland or Wellhead Protection Area ornot serving a food, beverage or lodging establishment: Drainfield has at least a two -foot vertical separation distance from periodically saturated soil or bedrock. Sb. Non-performance systems built April 1, 1996, or later or for non- performance systems located in Shoreland or Wellhead Protection Areas or serving a food, beverage, or lodging establishment: Drainfield has a three-foot vertical separation distance from periodically saturated soil or bedrock.* 5c. "Experimental`; "Other'; or "Performance" systems built under pre -2008 Rules; Type IV or V systems built under 2008 I Rules 7080. 2350 or 7080.2400 (Intermediate Inspector License required <_ 2,500 gallons per day; Advanced Inspector License required > 2,500 gallons per day) Drainfield meets the designed vertical separation distance from periodically saturated soil or bedrock. 10 Yes ❑ No - El Yes ❑ No* 'Any "no" answer above indicates the system is failing to protect groundwater. Describe verification methods and results: Attached supporting documentation: FA Soil observation logs completed for the report ❑ Two previous verifications of required vertical separation ❑ Not applicable (No soil treatment area) Indicate depths or elevations \.-d VjC�� (' -4- 5a"`1 A. Bottom of distribution media &Jzf a B. Periodically saturated soil/bedrock sEv C. System separation S8 j D. Required_ compliance separation* *May be reduced up to 15 percent if allowed by Local Ordinance, Upgrade requirements: (Minn. Stat. § 115,55) An imminent threat to public health and safety (ITPHS) must be upgraded, replaced, or its use discontinued within ten months of receipt of this notice or within a shorter period if required by local ordinance. If the system is failing to protect ground water, the system must be upgraded, replaced, orits use discontinued within the time required by local ordinance. If an existing system is not failing as defined in law, and has at least two feet of design sort separation, then the system need not be upgraded, repaired, replaced, or its use discontinued, notwithstanding any local ordinance that is more strict. This provision does not apply to systems in shoreland areas, Wellhead Protection Areas, or those used in connection with food, beverage, and lodging establishments as defined in law. https://www,pca.state.mn.us 651-296-63oo - 800-657-3864 Use your preferred relay service Available in alternative formats wq-wwi5ts4-316 ° 4128/2021 Page 4 014 LA 0 V LA r 0 uo O n rt a O r N fir+ 0 CP p rn Ln N w 00 N a? OI, 1 N CD T�rt7 N rD rD N n' 7 rwr C 1 �zT rtr rt < `S pni CJ C5 fl O ;a N O0 � N �II N (D �• rt {� (p ( 0• .. rt �. Q O s n n n r: Ln i S w sv i r o _ m l[ �C 0 x n m. �., 0 0 0 " r m a a 3 rDp 3 rD fl n n n 1 o ¢a a o (D a tm O d N 0 cn cn � r� N r* a ziCD rt Ln n 70 ; X a u, n_ o i ON w N ia N 0 n N m DIn !r O f f2 N Ln p O s;Q ria 3 n Or un S11 i fl rt ❑] fl M. c C 0 0 0- fl 0 Q x 0 0 rD a o CD LA N p a) @ rt. C O (n _a w n D v fl Ort ti 0- 0 :3 (D Y CT LA rD ' to �n < r �. �o C) C) w 3 n uo uo tr rD !p cp 3 C =I v rD uo u4 v w w C C w a E o ❑ coo rD CL o r n 0 0 z a a 0 N N rp rf) rDn, rt rn M r w iv sv o u4 (D El7 r+ r+ 1+ruw T, F rD C r < rD rp @ nrQj SI)r p w C CDCT O D v SD D n C N (q M rD �O J -r � a• W < q O N Q' o a w' u' o 6�_ r m tb rD n rD CD CD w LA 0 V LA r 0 uo O n rt a rd tA 0 4. 0 D" P'f 0� IT o ro v cn w N M n Q ra D N � •p, 00 O .To Ln 0- rDua r -r rD N � w N W < 0 D0 � .--. lu r*, -0 �• © CD 0 0 r* UQ =5 3 rt N 4t Nd cii y, 0 �. rt O 0 _ �Ln O v �. rD w w p� ` (D Q rD 0 o CD --- O o_ a 0 CL 0 CD ua o a N iv 0 zi UJ 3t r -F D] O O CD d tfa vi 70 ;u ;Q X 0`C rD - LT Ln CTI CTI CTI w D O _ _ _ On d w W CT o� w N N 0 rD 0 o v o o LA rD Lr. p ❑ N r aj r -r Al 0 O Q N N — to V 7! ;f ¢1 N rD O C1 El rO �_ Q X Q o O M Q7 rD CZ n O CD V� 531 rn o C_ O fD — O v n � cv a � o � ❑ a n 4 c to cn CD G r I1 ronj r n J un S J uo R p* � �, �' o ❑ n n _0 � al rD m CL Cn 0 0 r � Gl rt pr iv a ~ UQ rD N ip r T rD C r G ❑ =3r r n -r C nj O w O [p O v �- rD n Tn Q n Q 1 LNn _ < w n y s m 4 O �/ C 1 " ~' �' J [' ( p = ' N o' I� rD r � � r� o +' a 3 cu o �o m ro Z) LLI 0 I I v rd tA 0 4. 0 D" P'f 0�