HomeMy WebLinkAbout02-16-2022 Septic Compliance ReportSP TESTING INC. Steven B. Schirmers -951 Katydid Lane NE -St. Michael, MN 55376 Cert. No 627 - State License #394 - Phone 763-497-3566 - Fax 763-497-5011 www.sptesting.wastewaterC@comcast.net - schirmerswastewater.com February 23, 2022 John & Julie Lesser 165 Cristofori Circle Orono, MN The soils were thawed using propane heaters. A Compliance inspection was completed for the existing on-site sewage treatment system located on this property for the sale of the home. The system consists of 1- 1300 gallon trash trap, 1-1300 gallon septic tank, 1-1300 gallon pump tank, a 750 gallon Multi -Flo Aerobic Wastewater Treatment System & a pressurized mound system, built in June of 1996 for a 5 bedroom home. The Multi -Flo unit was installed on 7-13-07. Soil boring #1A found mottled soil (redox features) at 1.3' & the original soil at elev. 88.1 & the bottom of the rock at elev. 89.8 leaving 1.7' of sand & a 3' separation from the bottom of the rock bed & redox features. Soil boring #2A found the sand & rock to be dry, no indication of hydraulic overloading. This system meets the required 3' separation from the bottom of the trenches & redox features & is classified as in compliance with Minnesota Chapter 7080 rules. The tanks were pumped & certified by Elmer J. Peterson Co. Risers will be extended to the surface in the spring by Elmer J. Peterson Co. after the frost is out. The cost of the repair should be completed at this time to assure this will tank place. The Gazebo placed over the Multi -Flo system will need to be removed. It is very difficult to service the Multi -Flo when it is needed. Nothing other than gray water (laundry, showers etc.) human waste & toilet tissue should be disposed of into the septic tanks. Garbage disposals are not recommended due to adding more solids & fine solids passing through into the system. Iron filters are also not recommended & should be diverted out of the system. Excessive amounts of soaps, antibacterial soaps, cleaning agents, shower cleaners used every shower & chlorine agents may kill the bacteria you need living in the system. Additives are not recommended. Dishwasher & Laundry pods should not be used. The Multi -Flo has been serviced by Schirmers Wastewater Treatment Systems since it was installed. Monitoring of the trenches have found the trenches dry. No indication of hydraulic overloading. The Multi -Flo Unit requires to be serviced 2 times a year at a cost of $250.00 a year (2022 price). The trenches have to be monitored 1 time a year at a cost of $50.00 a year (2022 price). These prices are subject to change. Nothing other than human waste, toilet tissue, laundry, showers, water softners etc. should be disposed of into the system. IRON FILTERS MUST NOT BE ALLOWED TO DISHCARGE INTO THE SYSTEM. Garbage disposals are not recommended. Excessive amounts of soaps, antibacterial soaps, cleaning agents, shower cleaners used every shower & chlorine agents may kill the bacteria needed to treat septic effluent. Additives are not recommended. Recommend laundering be limited to 3 to 4 loads per day. The Multi -Flo Unit will need to be pumped when the settable solids reach 40%. Schirmers Wastewater will meet the pumper & clean out the Multi -Flo at the same time. There will only be a $50.00 charge for Schirmers Wastewater to clean the filters in the Multi -Flo unit as long as pumping is only needed 1 time every 3 years. The pumping charges from the pumper are your responsibility. By using smaller amounts of laundry, dish, dishwasher soaps will help to decrease pumping the system. See the attached Multi -Flo Care Sheet. This certificate of compliance is no guarantee that this system will continue to function indefinitely. Steven B. Schirmers This inspection requires a siW(ature from an Advanced Designer. 2--Z3`'2-Z_ Bernie Miller 165 Cristofori Circle date S -P TESTING, INC. „ Steven B. Schirmers • MPCA Cert -No. 627 951 Katydid Lane NE - St. Michael, MN 55376 - (763)'497-3566 FAX (763) 497-5011 State License #394 wwwsptesting.wastewater@comcast.net - schirmerswastewater.com � a �I y i 4ti.1 yq '% 37�°✓,►� lti v„Essrtiti £y43.1,_e�'.t�.S'. T+?G_°4•._—_.._ 1 q' SS4-i-A 96, b ds 3ry x 6. o �r 1 MINNESOTA POLLUTION CONTROL AGENCY Compliance inspection report farm _ 520 Lafayette Road worth Existing Subsurface Sewage Treatment System (SSTS) St. Paul, MN 55155-4194 Doc Type. Compliance and Enforcement Instructions: Inspector must submit completed form to Local Governmental Unit (LGU) and system owner within 15 days of final determination of compliance or noncompliance. Instructions for filling out this forth are located on the Minnesota Pollution Control Agency (MPCA) website at https://www.12ca.state.mn.us/sites/default/files/wo-wwists4-31a_.pdf. Property information Local tracking number: Parcel ID# or SecfTwp/Range: Reason for Inspection a Local regulatory authority info: G Property address: Own erfrepresentative: Owner's phone: 1. 4 c) -L4 19 <3 a, Brief system description: 1 100 t�1 -tyT r 130U M? � � j 1) .1,0 5.1 ..V%w -+r 11oul,1 rrum i? Il ra A j 4�i "005UJB-Cly IR Jo' Y iso 1 TV t,* System status System status on date (mmfdd/yyyy): W' Compliant —Certificate of compliance* (Valid for 3 years from report date unless evidence of an imminent threat to public health or safety requiring removal and abatement under section 145A.04, subdivision 8 is discovered or a shorter time frame exists in Local Ordinance.) *Note: Compliance indicates conformance with Minn. R. 7080.9500 as of system status date above and does not guarantee future performance. ❑ Noncompliant — Notice of noncompliance Systems fatting to protect ground water must be upgraded, replaced, or use discontinued within the time required by local ordinance. An imminent threat to public health and safety (ITPWS) most be upgraded, replaced, or its use discontinued within ten months of receipt of this notice or within a shorter period if required by loval ordinance or under section 145A.04 subdivision 8. Reason(s) for noncompliance (check all applicable) ❑ Impact on public health (Compliance component #1) — Imminent threat to public health and safety ❑ Tank integrity (Compliance component #2) — Failing to protect groundwater ❑ Other Compliance Conditions (Compliance component #3) — Imminent threat to public health and safety ❑ Other Compliance Conditions (Compliance component #3) — Falling to protect groundwater ❑ System not abandoned according to Minn. R. 7080.2500 (Compliance component #3) — Failing to protect groundwater Soil separation (Compliance component #5) — Falling to protect groundwater ❑ Operating permit/monitoring plan requirements (Compliance component #4) — Noncompliant - local ordinance applies Comments or recommendations Certification I hereby certify that all the necessary information has been gathered to determine the compliance status of this system. No determination of future system performance has been nor can be made due to unknown conditions during system construction, possible abuse of the system, inadequate maintenance, or future water usage. By typing my name below, t certify the above statements to be true and correct, to the best of my knowledge, and that this information can be used for the purpose of processing this form. Business name: Inspector signature: 3(7" w r t� A , ___•... �- f" 3 (this document has been electronically signed) CerHcation number: {� , License number: 129 Phone: '2, -t.t Necessary or locally required supporting documentation (must be attached) ❑ Soil observation logs ❑ System/As-Built ❑ Locally required forms ❑ Tank Integrity Assessment M Operating Permit ❑ Other information (list).- https://www.pea-state.mn.us 651-296-6300 800-657-3864 Use your preferred relay service Avai{able in alternative formats wq-wwists4-31b • 4/28/2021 Page 1 of 4 Property Address: 1 o y-,'0lii�L7tiz1 Business Name: �� '; ] >� �n KX L Date: l 1. Impact on public health — Compliance component 41 of 5 Comniiance criteria - System discharges sewage to the ❑ Yes* k) No ground surface System discharges sewage to drain ❑ Yes' H No tile or surface waters. System causes sewage backup into ❑ Yes' FMI No dwelling or establishment. Any "yes" answer above indicates the system is an imminent threat to public health and safety. Describe verification methods and results: Attached supporting documentation: ❑ Other: ❑ Not applicable 2. Tank integrity —Compliance component ##2 of 5 Comnliance rritPria- System consists of a seepage pit, ❑ Yes' ❑ Ne cesspool, drywell, leaching pit, or other pit? Sewage tank(s) leak below their ❑ Yes" ❑ No designed operating depth? If yes, which sewage tanks) leaks: Any "yes" answer above indicates the system is failing to protect groundwater. Describe verification methods and results: S -��; q w € / Attached supporting documentation: ❑ Empty tank(s) viewed by inspector Name of maintenance business: License number of maintenance business: Date of maintenance: ❑ Existing tank integrity assessment (Attach) Date of maintenance _ (mmlddlyyyy): mm(must be within three years) (See form instructions to ensure assessment complies with Minn. R. 7082,0700 subp. 4 B (1)) ❑ Tank is Noncompliant (pumping not necessary -explain below) ❑ Other: https://www.pca.state,mr.us 651-246-6300 800-657-3864 Use your preferred relay service Available in alternative formats wq-wwists4-31b • 4/28/2021 Page 2 of 4 Property Address: 1 f-�O-j�ljjr , Business fume: ���l x.P L, ) fr Date: 3. Other compliance conditions — Compliance component #3 of 5 3a. Maintenance hole covers appear to be structurally unsound (damaged, cracked, etc.), or unsecured? F]Yes* JjNo ❑ Unknown 3b. Other issues (electrical hazards, etc.) to immediately and adversely impact public health or safety? ❑ Yes"0 No ❑ Unknown "Yes to 3a or 3b - System is an imminent threat to public health and safety. 3c. System is non -protective of ground water for other conditions as determined by inspector? 3d. System not abandoned in accordance with Minn. R. 7080.2500? *Yes to 3c or 3d - System is failing to protect groundwater. Describe verification methods and results: Attached supporting documentation: ❑ Not applicable ❑ Yes" Q No 0 Yes' ✓❑ No 4. Operating permit and nitrogen BMP* Compliance component #4 of 5 0 Not applicable Is the system operated under an Operating Permit? 0 Yes ❑ No If "yes", A below is required Is the system required to employ a Nitrogen BMP specified in the system design? ❑ Yes f] No If "yes", B below is required BMR = Best Management Practice(s) specified in the system design If the answer to both questions is "no", this section does not need to be completed. Compliance criteria: a. Have the operating permit requirements been met? ❑ Yes ❑ No b. Is the required nitrogen BMP in place and properly functioning? ❑ Yes ❑ No Any "no" answer indicates noncompliance. Describe verification methods and results: Attached supporting documentation: ❑ Operating permit (Attach) https://www.pca.state.rnn.us 651-296-6300 800-657-3864 Use your preferred relay service Available in alternative formats wq-wwis84-31h • 4/28/2021 Poge 3 of 4 Property Address: -X Business Name: , Q � 5. Soil separation — Compliance component #5 of 5 Date of installation a �, _ e�q ❑ Unknown (mmIddryyyy) Shoreland[WelIhead protection/Food ❑ Yes B No beverage lodging? Compliance criteria [select on 5a. For systems built prior to April 1, 1996, and ❑ Yes ❑ No* not located in Shoreland or Wellhead Protection Area or not serving a food, beverage or lodging establishment: Drainfield has at least a two -foot vertical separation distance from periodically saturated soil or bedrock. 5b.Non-performance systems built ❑ Yes [❑ No* April 1, 1996, or later or for non- performance systems located in Shoreland or Wellhead Protection Areas or serving a food, beverage, or lodging establishment., Drainfield has a three-foot vertical separation distance from periodically saturated soil or bedrock.* 5c. "Experimental'; "Other'; or "Performance" systems built under pre -2008 Rules; Type IV or V systems built under 2008 Rules 7080. 2350 or 7080.2400 (intermediate Inspector License required 2,500 gallons per day; Advanced Inspector License required > 2,500 gallons per day) Drainfield meets the designed vertical separation distance from periodically saturated soil or bedrock. Date: Attached supporting documentation: PE Soil observation logs completed for the report ❑ Two previous verifications of required vertical separation ❑ Not applicable (No soil treatment area) El Indicate depths or elevations A. Bottom of distribution media 54v Z B. Periodically saturated soil/bedrock 55a" } 4 . 3 C. System separation —3 —10 to separation* I 2,C3 *May be reduced up to 15 percent if allowed by Local Ordinance. El Yes El No* -zl-,_� G.ariS'tiYasc.. ��� 5 LJ k,, i..14L *Any "no" answer above indicates the system is failing to protect groundwater. Describe verification methods and results: Upgrade requirements: (Minn. Stat. § 115.55) An imminent threat to public health and safety (IT"PHS) must be upgraded, replaced, or its use discontinued within ten months of receipt of this notice or within a shorter period if required by local ordinance. If the system is failing to protect ground water, the system must be upgraded, replaced, or its use discontinued within the time required by local ordinance. If an existing system is not failing as defined in law, and has at least two feet of design soil separation, then the system need not be upgraded, repaired, replaced, orits use discontinued, notwithstanding any local ordinance that is more strict. This provision does not apply to systems in shoreland areas, Wellhead Protection Areas, or those used in connection with food, beverage, and lodging establishments as defined in law. https://www.pca.state.mn.us 651-296-6300 800-657-3564 Use your preferred relays e rvice Available in alternative fOrmat5 wq-wwists4-31b • 4/18/2021 page 4 of 4 SP TESTING INC. Steven B. Schirmers —951 Katydid Lane NE—St. Michael, MN 55376 Cert, No 627 — State License #394 — Phone 763-497-3566 — Fax 763-497-5011 www.sptesting.wastewater@)comcast.net— schirmerswastewater.com SOIL BORING PROFILE John & Julie Lesser 165 Cristofori Circle Orono, MN The soils were thawed using propane heaters. Soil borings completed with a bucket auger on 2-16-22 SOIL BORING #1A - ELEV. 90.6 - MOTTLED SOIL PRESENT AT 1.3' INTO THE ORIGINAL SOIL - NO STANDING WATER. 0 - 12" Fill soil clay loam 12" - 30" Fill soil medium sand' 30" - 34" Original soil dark brown loam 10YR 312 34" - 46" Brawn clay loam 10YR 413 46" - 52" Brown clay loam 10YR 513 - distinct mottles 14YR 618, 1OYR 711 SOIL BORING #2A - sand & rock dry. w SCS M31ERS WASTEWATER TREATMENT SYSTEVZS,INC Steven B Schirmera — 951. Katydid Lane NE N St. Michael, AIN 55376 scttirmierswastewater.com s testin .wastewater eomeast.net Cert.NO.627 — (763) 497-3565 —FAX (763) 447-5011 State License #395 General Information OWNER; ��.) ' �. 5f5 _ PROPERTY LOCATION: ADDRESS: J L `r'i �7 ti L1 L+ r 0)�Q S c-) 0,h !41 COUNTY: 1AU-1 PHONE: c1 c7. 5� j !c q -)a, _ EMAIL: Unit Information Last pumped �,- l,- �Z TANK NO. raF, OF TANK ZO NO. OF MOTORS ERIAL NO. _'7 • 1112 `UV REQUIRED Check List Date of Inspection: c �, Date of Inspection: Item Done Per. Specs Needs Attention Item Dome Per. Specs Needs Attention Take Mixed Liquor Sample V Brown _ Gray Black Take Mixed Liquor Sample Brown Gray Blacl4 Check Alarm System Check Alarm System Turn Off Power — Turn Off Power Rinse Surge Bowly Inspect Effluent Quality Clear Rinse Surge Bowl Gray Inspect Effluent Quality Clear Gray_ Vacuum Weir And Finers Vacuum Weir And Filters ^' Wash filters Spray off Flushed off Wash Filters Spray off Flushed off Inspect/Replace Top Gasket InspectlRep]acerop Gasket Inspectlldeplaee Bottom Iuspect/Replace Bottom Inspect Alarm Sensors — Inspect Alarm Sensors Inspect Aerator Inspect Aerator Turn On Power .f Turn On Power CORRECTION RECOMAI:ENDED CO3RRECTION RECOMMENDED SETTABLE SOLIDS % UV SETTABLE SOLIDS % UV LAB TEST TES ` PIE' CAL COLIFORMS IT, CAL COLIFORMS MONITORED DRAINFIELD ©ry2 Ponding Depth B20 ./ 6F-- ! J L�*. r` SIGNATURE OF SERVICE OR REPAIR MAN MONITORED DRARi IELD Dry.___.. Ponding _____ Depth H2O SIGNATI]ME OF SERVICE OR REPAIR MAN AUTHORIZED DISTRIBUOR FOR MULTI-FLO AERATION EQUIPMENT SALES AND SERVICE SC RS WASTEWATER TREATMENT SYSTEMS,IN+C Steven E Schirmers — 951 ]Katydid Labe NE — St. MichaeL MN 55376 sch-Irrnersw: etewater.corn s testin .wastewater eomcast.net Cer°t.N0.627 — (163) 497-3566 — FAX (763) 497-5011 State License #395 fz'eueral Information OWNER; `� �' L � � �-� �✓S � _ _ PROPERTY LOCATION: ADDRESS; _S �1n � (r1�4��i�° c�� ti G � �GLL G ` 34y a-� a - COUNTY: PHONE: g # - 5 1:11 C, o, EMAIL: Unit Information TANK NC, TSE OF TANK j _ Q N®. OF MOTORS 1 SERIAL No. r), -,y, i-!-> UV REQUE ED Check Last Date of Inspection.: Date of Inspection: 1 d (a -1 Item Done Per. Specs Needs A•Ctention Item Done Per. Sum Needs Attention ^" Ere Mixed Liquor Sample4.-� Brown Grafi Black Take Mixed Liquor ,Sample Brown Gral ]Blac1 .zk Alarm System Check Alarm System 'a'urn Off Power Rinse Sorge Bowl Turn Off Pourer Inspect Effluent Quality Clear �GM Rinse Surge Bowl Inspect Effluent Gray Vacuum Weir And Filters Quality Vacuum Weir And Filters Wash Filters , S Flashed Wash ra vff off � Filters Flushed off Inspect/Replace Top Gasket Innspect(Replacc Top Gasket Inspect/Replace Bottom Inspect/Replace Bottom Inspect Alarm Sensors Inspect Alarm Sensors �- Inspect Aerator Inspect Aerator 'earn On Dower Tuan On Power CORRECTION RECGAIMMNIDED CORRECTION RECOMMENDED SETTABLE SOLIDS % UV SETTABLE SOLIDS % UV LAB TEST LAB TEST FECAL COLIFORMS FECAL COLIFORMS MONITORED DRAINFIELD Dry, Ponding _ Depth H20 � 671-- -9?- O il. -i.iGNAIURE+ Of SERVICE OR IMPAIR WkN MONITOIRED DR AINFIRLD Dry_ bonding i Depth H2O SIGNATURE OF SERVICE OR REPAIR MAN AUTHCRMED DISTRIBUOR. FOR MULTI FLO AERATION EQUEPMENT SALES AND SERVICE MINNESOTA POLLUTION CONTROL AGENCY Sewage tank integrity assessment form sea Lafayette Road worth Subsurface Sewage St, Paul, MN 55155-4194 Treatment Systems (SSTS) Program Doc Type: Compliance and Enforcement Purpose: This form may be used to certify the compliance status of the sewage tank components of the SSTS. This form is not a complete SSTS inspection report, only a tank integrity assessment, and may only certify sewage tank compliance status when entirely completed and signed by a qualified professional. SSTS compliance inspection report forms can be found at: https:ICwww nca state mn us/water/inspections. Instructions: This form may be completed, and signed, by a Designated Certified Individual (DCI) of a licensed SSTS inspection, maintenance, installation, or service provider business who personally conducts the necessary procedures to assess the compliance status of each sewage tank in the system. Only a licensed maintenance business is authorized to pump the tank for assessment. A copy of this information should be submitted to the system owner and be maintained by the licensed SSTS business for a period of five (5) years from the assessment date. When this form is signed by a qualified certified professional, it becomes necessary supporting documentation to an Existing System Compliance Inspection Report: C_- omLIiance inspection form - Existing system (wq_wwists4 31 b). This form can be found on the MPGA website at htt s:Nwww. ca.state.mn.us/water/ins ections. The information and certified statement on this form is required when existing septic tank compliance status is determined by an individual other than the SSTS Inspector that submits an inspection report. This form represents a third party assessment of SSTS component compliance and is allowable under Minn. R. 7082.0700, subp, 4(B)(1)- This form is valid for a period of three years beyond the signature date on this form unless a new evaluation is requested by the owner or owners agent or is required according to local regulations_ Additional Administrative Rule references for this activity can be found at Minn. R. 7082.0700, subp. 4(B),(C), and (D) and; Minn. R. 7083.0730(C). Owner information Owner/Representative _John or Julie Lesser Property address: 165 Cristofori Circle, Orono, MN Local Regulatory Authority: _ _ Parcel ID: System Status System status on date (mm/dd/yyyy): 2/16/2022 ® Certificate of sewage tank compliance ❑ Notice of sewage tank non-compliance Compliance criteria: The SSTS has a seepage pit, cesspool, drywell, leaching pit, or other pit- "Failure to Protect Groundwater." The SSTS has a sewage tank that leaks below the designed operating depth - "Failure to Protect Groundwater." The SSTS presents a threat to public safety by reason of structurally unsound (damaged, cracked, or weak) maintenance hole cover(s) or lids or any other unsafe condition - "Imminent Threat to Public Health or Safety." ❑ Yes" ® No Q Yes" ® No I Ll Yes" ® No Any "Yes" answer above indicates sewage tank non-cornpllanco.. Company information Designated Certified Individual (DCI) information Company name: Elmer J, Peterson Co Print name; James L Brae_ elmann _ Business license number: 219 Certification number: _ I personally conducted the work described above as a Designated Certified Individual of a Minnesota -licensed SSTS inspection, maintenance, installation, or service provider Business. t personally conducted the necessary procedures to assess the compliance status of each sewage tank in this SSTS. By typing/signing my name below, f certify the above statements to be true and correct, to the best of my knowledge, and that this information can be used for the purpose of processing this form. Designated Certified Individual's signature: James L Brae elmann Date (mmlddtyyyy): 2116f2o22 (This document has been electronically signed.) www.pca.state.mn.us 651-296-6300 800-657-3564 Use your preferred relay service Available in alternative formats wq-wwists4-91 • 5110121 Page 1 of 1 Tank Report Date: February 16, 2022 Elsner I Peterson Co. 5921 Dague Ave. Delano, MN 55528 Phone 765-972--2420 Fax 763-972-7217 MPGA License# 219 John or Julie Lesser 165 Cristofori Circle Orono, MN 952-451-5992 Baffles: O / Tank Capacity: # of Tanks: 4 Type of Tanks: OFF 3-1300 Gallon Septic Tanks, 1-750 Gallon Multi -Flo Concrete Gallons Pumped: 3000 Manholes to Grade: YES / NO Comments: On February 16, 2022, Elmer J. Peterson Co. uncovered and pumped septic tanks. No cracks or water leaking in tanks at the time of pumping. Manhole risers to be installed in April or May 2022 once the frost is out of ground. NOTE: This is only a tank report. This is not a compliance inspection for point of sale nor does it replace a compliance inspection.