HomeMy WebLinkAbout02-11-2020 Septic Compliance InspectionSP TESTING INC.
Steven B. Schirmers —951 Katydid Lane NE—St. Michael, MN 55376
Cert. No 627 — State License #394 — Phone 763-497-3566 — Fax 763-497-5011
www.sptesting.wastewater@comcast.net— schirmerswastewater.com
February 11, 2020
WD Larson
1205 French Creek Or.
Orono, MN
A Compliance inspection was completed for the existing on-site sewage treatment
system located on this property for the sale of the home. The system consists of 2-
1500 gallon septic tanks, 1-1500 gallon pump tank from 1989 & a 25' x 46'
pressurized seepage bed = 1250sq.ft. sized for a 6 bedroom home, built on 10-1-15.
The existing trenches were removed & backfilled with washed sand, then placed the
seepage bed.
There are 2 soil verifications, 1 by SP Testing, Inc. on 7-23-15 finding mottled soil
(redox features) at 72" & 1 by The City of Orono on 9-2-15 finding mottled soil at 74".
The bottom f the rock was found at 2.5' leaving a 3.5' separation from the bottom of
the system & redox features. This system meets the required 3' separation & is
classified as in compliance with Minnesota Chapter 7080 rules. Soil probing into the
system found the system to be dry, no sign of hydraulic overloading.
The tanks were pumped by Kothrade Sewer, Water & Excavating, Inc. & were found
to be compliant.
Nothing other than gray water (laundry, showers etc.) human waste & toilet tissue
should be disposed of into the septic tanks. Garbage disposals are not
recommended due to adding more solids & fine solids passing through into the
system. Iron filters are also not recommended & should be diverted out of the
system. Excessive amounts of soaps, antibacterial soaps, cleaning agents, shower
cleaners used every shower & chlorine agents may kill the bacteria you need living
in the system. Additives are not recommended. Recommend to pump & clean you
tanks through the manhole by a certified pumper every 2 years. Check with your
pumper to set up a schedule. IRON FILTERS MUST NOT BE PUT INTO THE SYSTEM.
This certificate of compliance is no guarantee that this system will continue to
function indefinitely.
Steven B. Schirmers
S -P TESTING INC. Steven B. Schirmers • MPCA Cert.No. 627
951 Katydid Lane NE • St. Michael, MN 55376 • (763) 497-3566
FAX (763) 497-5011
State License #394
wwwsptesting.wastewater@comcast.net _ schirmerswastewater.com
a o S ch1 c VIP, — -
SO NV
6,
mCONTROL AN CONTROL
AGENCY POLLUTION Compliance inspection report form
C
520 Lafayette Road North Existing Subsurface Sewage Treatment System (SSTS)
St. Paul, MN 55155-4194 Doc Type: Compliance and Enforcement
Instructions: Inspection results based on Minnesota Pollution Control Agency (MPCA) requirements and attached supporting
documentation — additional local requirements may also apply. Further information can be found here:
htt s://www. ca.state.mn.us/sites/defaultlfiles/w-wwists4-31a. df.
Inspector must submit completed form to Local Governmental Unit (LGU) and system owner within 15 days of final
determination of compliance or noncompliance.
Property information Local tracking number:
Parcel ID# or Sec[Twp/Range: Local regulatory authority: 0
Property address: 1 as 5 o t-
Owner/representative: Owner's phone:
Brief system description: 'a -t �,qD _+
System status
System status on date (mm/dd/yyyy): a —S. a 1
W Compliant — Certificate of compliance`
(Valid fora years from report date unless evidence of
an imminent threat to public health or safety requiring
removal and abatement undersection 145A.04,
subdivision 8 is discovered or a shorter time frame exists
in Local Ordinance.)
*Note: Compliance indicates conformance with Minn.
R. 7080.1500 as of system status date above and
does not guarantee future performance.
❑ Noncompliant— Notice of noncompliance
An imminent threat to public health and safety (ITPHS) must be
upgraded, replaced, or its use discontinued within ten months of
receipt of this notice or within a shorter period if required by
local ordinance or under section 145A. 04 subdivision 8.
Systems failing to protect ground water must be upgraded,
replaced, or use discontinued within the time required by local
ordinance.
Reason(s) for noncompliance (check all applicable)
❑ Impact on public health (Compliance component #1) — Imminent threat to public health and safety
❑ Tank integrity (Compliance component #2) — Failing to protect groundwater
❑ Other Compliance Conditions (Compliance component #3) — Imminent threat to public health and safety
❑ Other Compliance Conditions (Compliance component #3) — Failing to protect groundwater
❑ System not abandoned according to Minn. R. 70802500 (Compliance component #3) — Failing to protect groundwater
❑ Soil separation (Compliance component #5) — Failing to protect groundwater
❑ Operating permit/monitoring plan requirements (Compliance component #4) — Noncompliant - local ordinance applies
Comments or recommendations
Certification
I hereby certify that all the necessary information has been gathered to determine the compliance status of this system. No
determination of future system performance has been nor can be made due to unknown conditions during system construction, possible
abuse of the system, inadequate maintenance, or future water usage.
8y typing my name below, I certify the above statements to be true and correct to the best of my knowledge, and that this Information
can be used for the purpose of processing this form.
Business name: S-- �{iS�i'ti"\" I }. t✓ , Certification number: b010
Inspector signature: tZ:--Z c ...®_ y( t'3. Cwt, , License number: 3 -')
(This document has been electronically signed) Phone: 7 !v -I! - L °f
Necessary or locally required supporting documentation (must be attached)
IN Soil observation logs ❑ Locally required forms ( Tank Integrity Assessment ❑ Operating Permit
® Other information (list):
https:/Jwww.pca.state.mn,us 651-296-63Qo 800-657-3864 • Use your preferred relay service • Available in alternative formats
wq wwists4-31b • 1111121 page 1 of
1 '�e 5 �c4� r -000y-- vv,
1. Impact on public health — Compliance component #1 of 5
Hance criteria:
System discharges sewage to the ❑ Yes* p No
ground surface
System discharges sewage to drain ❑ Yes" iP No
the or surface waters.
System causes sewage backup into ❑ Yes' 90 No
dwelling or establishment.
Any "yes" answer above indicates the system is an
imminent threat to public health and safe!y.
Describe verification methods and results:
Attached supporting documentation:
A Other: j&0zz7,> 5qe-Ai�--m,7
❑ Not applicable
�i i a
2. Tank integrity — Compliance component #2 of 5
Compliance criteria:
System consists of a seepage pit, ❑ Yes* ❑ No
cesspool, drywell, leaching pit,
or other it?
Sewage tank(s) leak below their ❑ Yes* ❑ No
designed operating depth?
If which sewage tank(s) leaks:
Any "yes" answer above indicates the system
is failing to protect groundwater.
Describe verification methods and results:
Attached supporting documentation:
❑ Pumped at time of inspection
Name of maintenance business:
License number of maintenance business:
Date of maintenance:
❑ Existing tank integrity assessment (Attach)
Date of maintenance
(mmlddlyyyy): (must be within three years)
(See form instructions to ensure assessment complies with
Minn. R. 7082.0700 subp, 4 8 (1))
❑ Tank is Noncompiiant (pumping not necessary — explain below)
❑ Other:
https://www.pca.state.mn.us 651-296-6300 800-657-3864 Use your preferred relay service Available in alternative formats
wq-wwists4-31b • 1111121 Page 2 cf 4
1. Impact on public health — Compliance component #1 of 5
Compliance criteria: Attached supporting documentation:
System discharges sewage to the ❑ Yes' ❑ No ❑ Other:
ground surface
❑ Not applicable
System discharges sewage to strain ❑ Yes' ❑ No
tile or surface waters.
System causes sewage backup into ❑ Yes' []No
dwelling or establishment.
Any "yes" answer above indicates the system is an
imminent threat to public health and safety.
Describe verification methods and results:
2. Tank integrity — Compliance component #2 of 5
lance criteria_
System consists of a seepage pit, ❑ Yes* DD. No
cesspool, drywell, leaching pit,
or other oit?
Sewage tank(s) leak below their ❑ Yes'�if�l0
designed operating depth? /`�
If yes, which sewage tank(s) leaks: j
Any "yes" answer above indicates the system
is failing to protect groundwater.
Attached supporting documentation:
'i --pumped at time of inspection
r•� _
Name of maintenance business:��L �n'C
License number of maintenance business: t 19?
Date of maintenance:
❑ Existing tank integrity assessment (Attach)
Hate of maintenance`"
(mmiddlyyyy): (must be within three years)
(See form instructions to ensure assessment complies with
Minn. R, 7082.0700 subp. 4 B (1))
❑ Tank is Noncompliant (pumping not necessary --explain below)
❑ Other:
Describe verification methods and results: { ? , —7, ;
https://www.pca.state.mn.us 651-296-6300 800-657-3864 Use your preferred relay service Available in alternative formats
wq-wwists4-31b • 1/11/21 Page 2 of 4
I Other compliance conditions — Compliance component #3 of 5
3a. Maintenance hole covers appear to be structurally unsound (damaged, cracked, etc.), or unsecured?
❑ Yes* RR'No ❑ Unknown
3b. Other issues (electrical hazards, etc.) to immediately and adversely impact public health or safety? ❑ Yes* ® No ❑ Unknown
*Yes to 3a or 3b - System is an imminent threat to public health and safety.
3c. System is non -protective of ground water for other conditions as determined by inspector?
3d. System not abandoned in accordance with Minn. R. 7080.2500?
`Yes to 3c or 3d - System is failing( to protect groundwater.
Describe verification methods and results:
Attached supporting documentation: ❑ Not applicable ❑
❑ Yes* No
❑ Yes* ® No
4. Operating permit and nitrogen BMP* — Compliance component #4 of 5 a Not applicable
Is the system operated under an Operating Permit? ❑ Yes ❑ No If "yes", A below is required
Is the system required to employ a Nitrogen BMP specified in the system design? ❑ Yes ❑ No If "yes", S below is required
BMP = Best Management Practice(s) specified in the system design
If the answer to both questions is "no", this section does not need to be completed.
Compliance criteria:
a. Have the operating permit requirements been met? ❑ Yes ❑ No
b. Is the required nitrogen BMP in place and properly functioning? ❑ Yes ❑ No
Any "no" answer indicates noncompliance.
Describe verification methods and results:
Attached supporting documentation: ❑ operating permit (Attach) ❑
https://www.pca.state.mn.us 651-246-6300 800-657-3864 Use your preferred relay service Available in alternative formats
wq-wwists4-31 b • 1111121 Page 3 of 4
5. Soil separation — Compliance component #5 of 5
Date of installation io_� - t 5 ❑ Unknown
(mmlddlyyyy)
Shoreland/WelIhead protection/Food
beverage lodging?
Compliance criteria
5a. For systems built prior to April 1, 1996,
and not located in Shoreland or Wellhead
Protection Area or not serving a food,
beverage or lodging establishment:
Drainfield has at least a two -foot vertical
separation distance from periodically
saturated soil or bedrock.
5b.Non-performance systems built April 1,
1996, or later or for non-performance
systems located in Shoreland or Wellhead
Protection Areas or serving a food,
beverage, or lodging establishment:
Drainfield has a three-foot vertical
separation distance from periodically
saturated soil or bedrock.*
5c. "Experimental', 'Other', or Performance"
systems built under pre -2008 Rules,-
Type
ules;Type IV or V system built under 2008
Rules 7080. 2350 or 7080.2400
(Advanced Inspector license required)
Drainfield meets the designed vertical
separation distance from periodically
saturated soil or bedrock.
V Yes ❑ No Attached supporting documentation:
❑ Soil observation logs completed for the report (Attach)
® Two previous verifications of required vertical
El Yes F1 No* separation (Attach)
❑ Not applicable (No soil treatment area)
X Yes ❑ No" indicate depths or elevations
A. Bottom of distribution media a S
B. Periodically saturated soil/bedrock b
1
C. System separation S
D. Required compliance separation* 3'0
*May be reduced up to 15 percent if allowed by Local
Ordinance.
❑ Yes ❑ No*
*Any "no" answer above indicates the system is
failing to protect groundwater.
Describe verification methods and results:
Upgrade requirements: (Minn. Stat. § 115.55) An imminent threat to public health and safety (1TPHS) must be upgraded, replaced,
or its use discontinued within ten months of receipt of this notice or within a shorter period if required by local ordinance. If the
system is failing to protect ground water, the system must be upgraded, replaced, or its use discontinued within the time required by
local ordinance. If an existing system is not failing as defined in law, and has at least two feet of design soil separation, then the
system need not be upgraded, repaired, replaced, or its use discontinued, notwithstanding any local ordinance that is more strict.
This provision does not apply to systems in shoreland areas, Wellhead Protection Areas, or those used in connection with food,
beverage, and lodging establishments as defined in law.
https://www.pca.state.mn.us 651-296-6300 800-657-3864 Use your preferred relay service Available in alternative formats
wq-wwists4-31b • 1/11/21 Page 4 of 4
WORK SATISFACTORY. PROCEED
CORRECT WORK & PROCEED
CORRECT WORK, CALL FOR REINSPECTION
BEFORE COVERING
I CORRECT UNSAFE CONDITION WITHIN — HOURS_
INSPECTORWILL RETURN
1 STOP ORDER POSTED. CALL iNSPECTOR
:,: tNSPECTION REQUIRED. CALL TO ARRANGE ACCESS_
PROJECTCOMPLETE
ISSUE CERTIFICATE OF OCCUPANCY
TEMPORARY
— PERMANENT
iPHOTOTAKEN
I CITATION ISSUED
Call for the next inspection 24 hours in advance. (952) 249-4600
While CopyflnzpeCtOr's File Canary CopyfSite Notice
DATE TIME
CITY OF ORONO
CALLED IN
INSPECTION NOTjCE SCHEDULED
PERMIT NO. ZVN — 010 2? COMPLETED
ADDRESS J
A (f
OWNER --- ------------.-.-
--- TEI-EPHONENO. --.—
CONTRACTOR r:<2' r2 ��151' �&-W�Pl C-4 -
7
DESCRIPTION
❑ FOOTING
(j DEMO -FINAL EJ SEPTIC FINAL
❑ POURED WALL
❑ PLUMBING RI EXCAV,GHADINGiFILLING,
❑ F OUN D AT ION WATERPROOF
❑ PLUMBING FINAL TREE REMCVAL
❑ RADON 'SLAB
❑ MECHANICAL RI C1 SITE INSPECTION
❑ FRAMING
❑ MECHANICAL FINIAL Ej PROGRESS
!N'3VLA`rION
WOOD BURN L-R.-F IR EPLACF 0 COMPLAINT
El PiNAL
El WATER HOOK-UP C1 FOLLOW-UP
[I A$ BUIL SURVEY
El SEWER HOOK-UP Ll HARD COVER REMOVAL
Ej DEK10 - SITE
El SEPTIC INSTALL C1 FOUND ATIOWITE MOVAL
OWN ERICO NTRACTOR TO MEET
YOU:— YES— NO
COMMENTS:
WORK SATISFACTORY. PROCEED
CORRECT WORK & PROCEED
CORRECT WORK, CALL FOR REINSPECTION
BEFORE COVERING
I CORRECT UNSAFE CONDITION WITHIN — HOURS_
INSPECTORWILL RETURN
1 STOP ORDER POSTED. CALL iNSPECTOR
:,: tNSPECTION REQUIRED. CALL TO ARRANGE ACCESS_
PROJECTCOMPLETE
ISSUE CERTIFICATE OF OCCUPANCY
TEMPORARY
— PERMANENT
iPHOTOTAKEN
I CITATION ISSUED
Call for the next inspection 24 hours in advance. (952) 249-4600
While CopyflnzpeCtOr's File Canary CopyfSite Notice
SP TESTING INC.
Steven B. Schirmers — 951 Katydid Lane NE— St. Michael, MN 55376
Cert. No 627 — State License #394 — Phone 763-497-3566 — Fax 763-497-5011
www.sRtesting.wastewater@comcast.net— schirmerswastewater.com
SOIL BORING PROFILE
Clark Winslow
1205 French Creek Dr.
Orono, MN
Soil borings completed with a bucket auger on 7-23-15
SOIL BORING #1 -- ELEV.97.8 - NO MOTTLED SOIL PRESENT TO A
DEPTH OF 78".
0 -
1437
Fill soil brown sandy loam
1433 -
2271
Fill soil pea rock
2233 -
26"
Fill soil sandy clay loam
2633 -
3433
Original soil brown sandy loam 10YR 412
3431 -
60"
Brown loamy medium sand 10YR 513
6073 -
6633
Brown loamy coarse sand 10YR 513
6671 -
7833
Brown loamy medium sand 10YR 614
SOIL BORING #2 - ELEV.99.0 - MOTTLED SOIL PRESENT AT 63 - NO
STANDING WATER PRESENT IN THE BORING.
0 -
1271
Fill soil loam
1271 -
30"
Fill soil sandy loam
3033 -
3637
Original soil brown sandy loam 10YR 412
3637 -
5073
Yellowish brown loamy medium sand 10YR 513
5033 -
5873
Yellowish brown loam 10YR 516
58" -
6431
Yellowish brown sandy loam 10YR 516
643' -
7213
Light brown medium to fine sand 10YR 614
7273 -
783'
Yellowish brown fine sandy silty loam 10YR 614 -
distinct mottles 10YR 618, 10YR 711
SOIL BORING #6 -- ELEV.94.3 - MOTTLED SOIL PRESENT AT 48" -
STANDING WATER PRESENT IN THE BORING at 52".
0 -
22"
o & medium sand
Fill soil loa<bn
22" -
38"
Original sdium sand 1 OYR 513
38" -
48"
Brown co0YR 513
48" -
52"
Brown loasand 10YR 413 -
30" -
34"
distinct m 61852"
-
56"
Brown loasand 10YR 614 -
42" -
60"
distinct m618
56" -
72"
Brown sandy loam 10YR 614 -
66" -
78"
distinct mottles 10YR 618, 10YR 711
SOIL BORING #7 - ELEV. - NO MOTTLED SOIL PRESENT IN THE
BORING.
0 -
12"
Topsoil dark brown sandy loam 10YR 313
12" -
18"
Brown sandy loam 10YR 413
18" -
22"
Brown clay loam 10YR 516
22" -
30"
Brown loam 10YR 516
30" -
34"
Brown clay loam 10YR 614
34" -
42"
Brown loamy fine sand 10YR 614
42" -
60"
Brown medium sand 10YR +614
60" -
66"
Brown coarse sand 1OYR 613
66" -
78"
Light brown fine sand 10YR 613