HomeMy WebLinkAbout12-05-2018 Septic DesignJoseph Olson D.B.A.
Rusty Olson's--Soil and Percolation Testing
Joseph J. Olson--MPCA License #810
11481 Riverview Rd. NE, Hanover, MN 55341
(763) 498-8779 Fax (763) 498-8290
December 5, 2018
Norton Homes
4775 Augusta Street
Orono, Hennepin County
This on-site Sewage Treatment System is designed for a Type 1, Five -bedroom home in accordance with
the Minnesota Pollution Control Agency Chapter 7080 and local ordinances.
The periodically saturated soils were located at 12-18 inches (mottled soil). Due to the periodically
saturated soils, a pressurized mound system with 6 inches of rock will need to be installed to treat the septic
effluent. The bottom of the treatment area must be located at least 3' above the saturated soils. This system
is designed with 6 inches of rock.
The soils at a depth of 12" have a percolation rate averaging 11.5 MPI.
A 2250 -gallon septic tank or its equivalent is designed for this site. All tanks need to be insulated if there is
less than two feet of cover over the top of the tanks. Clean outs must be installed on the end of the laterals
for maintenance.
Use 7132 -inch perforations on the laterals
A 1250 -gallon pumping chamber or larger will need to be installed to lift the effluent to the treatment area.
The power supply and switches must be located outside the manhole and pumping chamber in a
weatherproof enclosure. A warning device must be installed with light and sound devices; this is in case of
a pump failure. A flow measurement device must be installed. Including but not limited to a water meter,
event counter, running time clocks or electronically controlled dosing.
Keep all heavy a ui ment off of the Proposed treatment areas before during and after construction.
The area around both sites must be fenced off by the contractor before any construction begins.
With proper installation and maintenance, this system should have no problem in treating septic effluent
effectively. Nothing other than gray water, (laundry, showers, etc.) Human water and toilet tissue should be
disposed of into the septic tanks. Iron filters cannot go into the septic sstem. Garbage disposals are not
recommended. Additives must not be used they may cause harmful damage to your septic system. It is
recommended that you pump the septic tanks every two years.
Sincerely,
Cr / Joseph J. Olson
2011 purple code Mound Design
www.SepticResource.cam (vers 15.2)
Property Owner: Norton Homes
Site Address: 4775 Augusta Street
Comments:
Date: 12/5/2018
PID: 0611723330010
instructions: = = enter data 0 m adjust if desired u = computer calculated - DO NOT CHANGE!
1) bedroom Type I ' l Residential System
2) 750 GPD design flow
3) Yes Garbage disposal or pumped to septic 50% larger tank with multiple comp/tanks
4) 2250 Gal Septic tank (code minimum) 2250 Gal Septic tank (design size / LUG req'd)
Tank options: none
s) 1.2 GPD/ft2 mound sand loading rate contour loading rate of 12 req's a min 62.5 ft. long rockbed
6) 10.0 ft rockbed width 63.0 ft rockbed length
7) 3.Q ft lateral spacing 3.0 ft perforation spacing (maximum of 3 for both)
end feed manifold connection
8) laterals 61.0 feet long 21.0 perfs / lateral 63 perfs total
(1 /2 a perf means the first perf starts at the middle feed manifold)
9) 7/32 inch perfs at feet residual head gives 0.56 gpm flow rate per perforation
for this perf size Et spacing, & pipe size on line 12, max perfs/lateral = F30-1, line #8 must be less > OK
10) 4.0 doses per day (4 minimum)
11) 188 gallons per dose (treatment volume)
2.00 5x
12) 2.00 inch diameter laterals must be used to meet "4x pipe volume" requirement
2.00 3x
13) 30 feet of 2.0 inch supply line leads to =gallons of drainback volume
(Tip: "top feed" manifold to control the drainback)
14) 193 gallons TOTAL pump out volume (treatment + drainback)
1s) 10 feet vertical lift from pump to mound laterals, leads to a:
16) 36 IGPM @ 17 feet of head, Pump requirement (note: >50gpm may require an extra 3-6' of head)
17) 750 gal Dose tank (code minimum) 1250 gal Dose tank (design size / LUG req'd) at 25.49 gpi
leads to a
18) 7.6 inch swing on Demand float, or timed dosing of5.4 min ON (confirm pump rate with drawdown
(this delivers Average flow, =70% of Peak design ftow)Mhrs OFF test and adjust as necessary)
19)If
inches from bottom of tank to "Pump OFF" float
20) inches from bottom of tank to "Pump ON" float, orP3fl
inches to "Timer ON" float if time dosed
21) inches from bottom of tank to "Hi Level" float, or inches to "Hi Level" float if time dosed
22) 664 gallons reserve capacity (after High Level Alarm is activated)
3) 0.45 gpd/ftz Absorption area Soil Loading Rate, which gives a mound ratio of 2.7 (minimum)
(this must match the soil boring tog) desired mound ratio 1 2.7
4) Qpercent site slope (0-20% range) �9 (% downslope site slope, if different than upslope)
5) 1$ inches, or 7.5 ft. to Redox or other limiting condition (need at least 12" to be a Type 1)
Treatment zone contains =D inches of 0% soil credit, and =inches of 50% soil credit. Giving a:
6) 18 inch, or 1.5 ft. Sand Lift Mound CRITICAL FOR FUTURE CERTIFICATIONS!!!
7) 27.0 ft.Total ABSORPTION width (with sand beyond rockbed as follows:)
8) O.Q ft. upslope and sideslope
17.0 ft. Downslope
Individual slope ratios give BERM widths (topsoil beyond rockbed) of:
9) 4:1 upslope ratio 10 ft. upslope berm
o) 3:1 sideslope 13 ft. sideslope berms
i) 4;1 downslope 28 ft. downslope berm
Overall Dimensions: 10.0 1 ft. wide by 63.0 ft. long Rock bed
48 ft. wide by 89 ft. Long Mound footprint
4" inspection pipe
18" cover on top
Upslope herrn 101 L Downslope berm 28
12' cover on sides
(6" loamy cap & 6" topsoil)
1.5 Clean sand Lift
1.5 Depth to limiting
p 1-1
Absortion Width ~ 27.0 -- - - - - ---
Note
For 0 to 1 slopes, Absorption Width is measured from the Bedequally in both directions.
For slopes >1%, Absorption Width is measured downhill from the upslope edge of the Bed.
Rock Bed:
1D.D ft. by aflft. by ®inches under pipe, plus 20% gives 21 yds or *1.4= 29 ton
Mound Sand: (note: volume is based on 3:1/4:1 slope from top of rockbed, Exchange sand for Loamy cap if desired)
27.6 Up + 1D8.4 downslope + 12.8 ends + 45.5 under rock =233 yd' or *1.4= 326 ton
plus 20%
Loamy Cap:
44 ft. by 85 ft. 6" deep, plus 20% gives F--84—]yd" or *1.4= 118 ton
Topsoil:
48 ft. by 89 ft. 6" deep, plus 20% gives 95 yds or "1.4= 133 ton
I hereby certif that I have completed this work in accordance with all applicable ordinances, rules and taws.
Rusty Olson"s Soil ft Perc 810 12/5/2018
Designer Signature Company License# Date
Installer Summary
2250 gallon Septic tank (minimum) Tank options: none
Z)u7a Larger lanK WItn rnuu.ipLe comp/ LarrKs
1250 gallon Dose tank (minimum) at 25.49 gpi
36 GPM @ 17 ft. of head, Pump required
7.6 inch swing on Demand float which translates to roughly 4.8 inches of float tether length
if time dosing is required --> 5.4 minutes ON time Ft =hours OFF time
20 inches from bottom of tank to "pump ON" float, or 12 1 inches to "timer ON" float
23 linches from bottom of tank to "Hi Level Alarm" or 1 33 linches to "Hi level alarm" if time dosed
30 ft. of 2.0 inch supply line with end feed manifold connection
(Tip: "top feed" manifold to control drainback)
18 inch, or 1.5 ft. Sand Lift Mound
10.0 ft. wide by 63.0 ft. long Rock bed
3 laterals 2.00 inch diameter 61.0 ft. long 3.0 ft. lateral spacing
7/32 inch perfs 3.0 ft. perforation spacing
No Effluent filter Et alarm
3 Ictean out & valve box assemblies
27.0 ft.Total sand ABSORPTION width (minimum)
0.0 ft. upslope and sideslope (sand beyond rockbed, minimum)
17.0 ft. Downslope (sand beyond rockbed, minimum)
Specific slope ratios give BERM widths (topsoil beyond rockbed) of:
4:1 upslope ratio 10 ft. upslope berm
3:1 sideslope 13 ft. sideslope berms
4:1 downslope 28 ft. downslope berm
4" inspection pipe
18" cover on top
U pslope be rm 10 _ t I _
1.5 11 Clean sand lift
Downslope berm 1 28
12" cover on sides
(6" loamy cap & 6" topsoil)
1.5 Depth to Limiting
r�nc�itr'an �
Absorption Width
Note;
For 0 to 1 slopes, Absorption W dth is measured from the Bedequally in both directions.
For slopes >1%, Absorption .t�4�fdtfr is measured downhill from the upslope edge of the Bea!
Rock Bed: 21.0 yd3 or *1.4= 29 ton
Mound Sand: 233 yd or *1.4= 326 ton
Loamy Cap: 84 yd or *1.4= 118 ton
Topsoil: 95 yd or *1.4= 133 ton
6 inches under pipe
calculation based on 3:1/4:1 slope from top of rockbet
6" deep
6" deep
INSPECTOR CHECKLIST - mound
4//5 Augusta Street
WELL setbacks: 20' to pressure tested sewer line (5 psi for 15 min)
50' to everything 100' to dispersal area with shallow well
PROPERTY LINES setback: 10' to everything
Road setback: platted: 10' prop line. Metes & bounds: out of road easement, or outer ditch.
LAKE/ BLUFF setback: 20' for bluff. Lakes: GD _, RD NE . Protected wetland _
Building setbacks: 10' for everything, 20' for dispersal area.
WATER LINE under pressure se 10' to bed,tank Ft sewer line. (else sewer line > 12" below)
Sewer line Et baffle connection (no 90's, 3' between 45's, slope min 1" in 8', max 2" in 8')
(no depth req's, clean out every 100', Sch 40 pipe)
Septic tank and risers (water tight, insulated, proper depth, existing verified by pumping)
Mfg 2250 gallons none
Riser over outlet, riser over inlet or center, and 6"+ inspection pipe over any remaining baffles.
No effluent filter Ft alarm
Dose tank risers and piping (water tight, insulated, proper depth, drainback)
mfg 1250 gallons
L1 dose pump 36 gpm 17 head VERIFY PUMP CURVE 5.4 min ON 9 hr OFF
float setting drop 7.6 inches at 25.5 gpi "DESIGNED" 4.8 inches approx float tether length
193.0 gal dose divided by gpi "INSTALLED" = inches float drop (field corrected
LABEL pump requirements and drawdown on riser or panel
Cam lock reachable from grade - 30" max. J -hook weep hole. Supply line access (no hard 90's)
2.0 inch supply pipe: Sch40, sloped 1 /8"+, supported by 4" sch40 sleeve or compacted, and buried 6"+.
splice box / control panel / electrical connections
flow measurement: CT, ETM, time dosed, home water meter
mound absorption area rough up
mound rock dimensions 10.0 K 63.0
Sand lift depth 18 inches. (Jar test : 2" sand leaves < 118" silt after 30 min)
❑ Absorption Sand beyond rock 0.0 upslope 17.0 downslope
❑ Bermed topsoil beyond rockbed 10 upslope 13 sideslope 28 downslope
cover depth of 12-18"+ VERIFY
3 laterals (1-2' from edge of rock)
2.00 inch pipe size (Sch40 pipe Et fittings)
3.0 ft lateral spacing
7132 inch perforations
3.0 ft perforation spacing
Air inlet at end of laterals, and at top feed manifold if necessary. VERIFY
clean outs (no hard 90's)
4" inspection pipe to bottom of rock, anchored VERIFY
Abandon existing system - if necessary �Re-use existing tank certification
monitoring plan and type
well abandonment form - if necessary
G�
H
Ia.
E
3
CL
Wo
z
a�
v
f
I
a�
LA
Wo
��
LA M IL
CL 0
•&
OLD4
Ln W
f
I
��
LA M IL
CL 0
•&
OLD4
Ln W
Property Owner / project:
Property Address / PID:
Soil Observation Log
Owner Information
Norton Homes
4775 Augusta Street
www.SepticResource.com vers 12.4
Date 6/1/2014
Soil Survey Information ❑ refer to attached soil survey
Parent matl's: ❑� Till ❑ Outwash ❑ t.acustrine ❑ Alluvium ❑ Organic ❑ Bedrock
landscape position: ❑ Summit ❑ Shoulder 11 Side slope ❑ Toe slope
soil survey map units: L41 D2 slope 9 % direction- Linear
Soil Log #1
7 Boring
❑ Pit
Elevation 1000.0 Depth to SHWT
14
Inches
Depth (in)
Texture
fragment %
matrix color redox color
consistence
grade
shape
0-6
Topsoil
<35
10yr3/2
Friable
Moderate
Blocky
6-14
Loam
35
10yr4/4
Friable
Strong
Rlockv
14-24
Loam
<35
10yr5/4 IOy4/8,1-6/10y
Firm
Strong
Black:
<35
loose
loose
single grain
35-50
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
<35
loose
loose
single grain
35-50
friable
weak
granular blocky,
>50
firm
moderate
prismatic platy
rigid
strong
massive
Comments:
4775 Augusta Street Soil Log #2
0 Boring ❑ Pit Elevation 1000.4 Depth to SHWT 18 inches
Depth (in) Texture fragment % matrix color redox color consistence grade shape
0-6
Topsoil
<35
10yr3/2
Friable
Moderate
Blocky
6-12
Loam
<35
10yr4/3
Friable
Strong
Blocky
12-18
Loam
<35
10yr5/4
Friable
Strong
Block}
18-24
Clay Loam
<35
10yr5/4
10y4/8,1 -6/10y
Firm
Strong
Blocky
<35
loose
loose
single grain
35-50
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
4775 Augusta Street Soil Log #3
❑ Boring ❑ Pit Elevation 988.0 Depth to SHWT 18 inches
Depth (in) Texture fragment % matrix color redox color consistence grade shape
0-14
Topsoil
<35
10yr3/2
Friable
Moderate
Blocky
14-18
Loam
<- 3 5
10yr4/4
Friable
Strong
Blocky
18-24
Loam
<35
10yr5/4
10y4/8,1-6/l0y
Firm
Strong
Blocky
<35
loose
lease
single grain
3s - sa
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
<35
loose
loose
single grain
35-50
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
I hereby certify this work was completed in accordance with MN 7080 and any local reqs.
Rusty Olson's Soil & Perc. 810
esigner Signature Company License #
4775 Augusta Street Soil Log #4
❑ Boring ❑ pit Elevation 988.2 Depth to SHWT 18 Inches
Depth (in) Texture fragment % matrix color redox color consistence grade shape
0-6 Topsoil T<35 IOyt-3/2 Friable Moderate IBIouky
6-14 I Loam I <35 I 10yr4/4
Friable I Strong (Block%
14-24
Loam
<35
10yr5/4
I Oy4/8,1-6/1 Oy
Firm
Strong
Blocky
loose
single grain
<35
granular blocky
moderate
loose
loose
single grain
35-50
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
<35
loose
loose
single grain
35-50
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
4775 Augusta Street Soil Log #5
0 Boring [] pit Elevation 998.8 Depth to SHWT 16 inches
Depth (in) Texture fragment % matrix color redox color consistence grade shape
0-8
Topsoil
<35
10yr3/2
Friable
Moderate
Blocky
8-16 Loam
16-24 Loam
<35
<35
<35
35-50
>50
<35
35-50
>50
I Oyr4/4
1 OyrS/3
Friable I Strong (Blocky
10y4/8,1 -6/10y IFirm
loose
friable
firm
rigid
loose
friable
firm
rigid
I hereby certify this work was completed in accordance with .LIN 7080 and any local reqs.
Rusty Olson's Soil & Pere,
esigner Signature Company
Strong OBlocky
loose
single grain
weak
granular blocky
moderate
Prismatic platy
strong
massive
loose
single grain
weak
granular blocky
moderate
Prismatic platy
strong
massive
810
License #
Property Owner / project
Property Address / PID:
Soil Observation Log
www.SepticResource.com vers 12.
Owner Information
Norton Homes
4775 Augusta Street
Date 6/1/2014
Soil Survey Information ❑ refer to attached sail survey
Parent matt"s: 0 Till ❑ Outwash ❑ Lacustrine ❑ Alluvium ❑ organic ❑ Bedrock
landscape position: ❑ Summit ❑ Shoulder Q Slde slope ❑ Toe slope
soil survey map units: L41D2 slope 9 % direction- Linear
Soil Log #6
0 Boring ❑ Pit Elevation 986.1 Depth to SHWT 12 Inches
Depth (in) Texture fragment % matrix color redox color consistence grade shape
0-12
Topsoil
<35
10yr3/2
Friable
Moderate
Blocky
12-18
Loam
<3S
10yr4/4
10y4/8,1 -6/10y
Friable
Strong
Blocky
<35
loose
loose
single grain
35-50
friable
Weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
<35
loose
loose
single grain
35 - 50friable
'firm
weak
granular blocky
>50
moderate
prismatic platy
rigid
strong
massive
<35
loose
loose
single grain
35-50
friable
weak
granular blocky
>50
firm
moderate
prismatic platy
rigid
strong
massive
Comments:
Percolation Test Data Sheet
Lic.#810
Percolating test readings made by: Rusty Olson"s Perc. starting at 1:29 P.M. On 7102114
Location: Lot 8, Blk 1
Hole number: 1'
Date hole was prepared 7/01114
Depth of hole bottom —12"_ inches, Diameter of hole _6"_ inches.
Soil data from test hole:
Depth, inches Soil texture
0-12" Dark brown loam 10yr312
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date of initial water filling 7/01/14 depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
1:39 1:54 6" 1.0 15.0
2:01 2:16 6" 1.0 15.0
2:17 2:32 6" 1.0 15.0
AVERAGE PERC, RATE 15.0 MPI
Percolation Test Data Sheet
Lic.#810
Percolating test readings made by: Rusty Olson's Perc. starting at 1:29 P.M. On 7102114
Location: Lot 8, Blk 1
Hole number: 2
Date hole was prepared 7101114
Depth of hole bottom _12"� inches, Diameter of hole —6"—inches.
Soil data from test hole:
Depth, inches Soil texture
0-12" Dark brown loam 10yr312
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date of initial water filling 7/01/14 depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
Time
Time
Depth
Drop in H2O
Perc Rate
1:40
1:55
6"
1.0
15.0
2:00
2:15
6"
0.9
16.7
2:18
2:33
6"
0.9
16.7
AVERAGE PERC. RATE 16.1 MIDI
Percolation Fest Data Sheet
Lic.#810
Percolating test readings made by: Rusty Olson's Perc. starting at 1:29 P.M. On 7102114
Location: Lot 8. Blk 1
Hole number: 3
Date hole was prepared 7101/14
Depth of hole bottom _12"_ inches, Diameter of hole _6"— inches.
Soil data from test hole:
Depth, inches Soil texture
0-12" Dark brown loam 10yr3/2
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date of initial water filling 7101/14 depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
1:41 1:56 6" 2.7 5.5
1:59 2:14 6" 2.6 5.8
2:19 2:34 6" 2.5 6.0
AVERAGE PERC. RAPE 5.8 MPI
Percolation Test Data Sheet
Lic.#810
Percolating test readings made by: Rusty Olson's Perc. starting at 1:29 P.M. On 7102114
Location: Lot 8. Blk 1
Hale number: 4
Date hole was prepared 7/01114
Depth of hole bottom _12"_
Soil data from test hole:
Depth, inches
0-12"
inches, Diameter of hole _6"— inches.
Soil texture
Dark brown loam I0yr3/2
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches.-
Date
nches:Date of initial water filling 7101114 depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
Time
Time
Depth
Drop in H2O
Perc Rate
1:42
1:57
6"
1.7
8.8 _..
1:58
2:13
6"
1.6
9.4
2:20
2:35
6"
1.6
9.4
AVERAGE PERC, RATE 9.2 MPI