A future expansion site wa� evaluated for this property. The design will need to be
completed prior to insta�lation.
The soils on this site are SCS soils mapped - Lr6 - Lester loam. The seasonally
saturated soils were located at 24" to 36" (mottled soil). Due to the seasonally saturated
soils, a Pressurized Mound System will need to be installed to treat septic effluent. The
bottom of the treatment area must be located at least 3' above the saturated soils.
The soils at a depth of 12" have a percolation rate averaging 3.0 mpi.
A pumping chamber will need to be installed to lift the effluent to the treatment area.
The power supply and switches must be located outside the manhole and pumping
chamber in a weather proof enclosure. A waming device must be installed with a light
and sound device, this is in case of a pump failure.
The manifold and supply line pipe must have back drainage to the pumping chamber.
The distribution pipes shall have their ends capped. Be sure the rock and sand fill
material are clean. The sod tayer below the entire mounded area must be tumed over,
just break up the sod, be sure not to over work.
All neighboring wells are located greater than 100' away from the proposed treatment
area. '
1
• " C
�
Keep all heavy equipment off of the proposed treatment areas before and after
construction. The treatment area should be marked off before construction. This
Design is not valid 8�the system wili need to be relocated if failure to protect the areas '
proposed for On-Site Sewage Treatment occurs.
With proper installation and maintenance, this system should have no problem in
treating septic effluent effectively.
Nothing other than human waste, toilet tissue, laundry, showers, water softener etc.
should be disposed of into the septic tanks. Iron filters must be diverted out of the
system. Garbage disposals are not recommended, due to adding more solids &fine
solids passing through to the system. Excessive amounts of soaps, cleaning agents &
chlorine agents may kill the bacteria needed to treat septic effiuent. Additives are not
recommended. Recommend to pump & clean your tanks through the manhole by a
certified pumper every 2 years. Check with your pumper to set up a schedule.
�
Steven B. Schirmers
2 '
i
j------�----- ---- ------ - ----- —----- — _
` 433,5� -—
�I
1
'� �t-�� 1�`,� t���� '�,��P�,�--� a�
O'� 'EX1S'�li-tl� $ 'Q�4��.�v -(��s�fwl�aT
Ik^��/prS e
IO
� `
r` rv �
m �
� e4n���o m
X T�N� �1•- '�, i' � Y+d^yG�'� �
�t�' ' .J. �.'�� � \ �� D��v��ito�-t
\ �� \2
. ` '.'/%� Z
t�.?
� �G O a
i � � 2
��S\�S I
Iti , Tg+�,.•. TaP oF ,r�EZ RL
_ � I -
F,,��,.� T�l�-�St�o�D gftSEnn��1T Do��_-
'G��S4{1 YZ/o�
�t�1k -r�o�r�o . EIF.�!P��'[OcJ � 10�.0
����Cl��s � "� -� 1 �
�s � �
� .o
-r� �.�.. — �, . a � e o - �q�.z . „ ,
"fla �`01 - C! a•7 �a- y q3i .�`� .�q�•o �P�rcc�olion Test� ,.-= S�
�� 3 _ � a,� Scale:
� 3�-�---''ati�-�
� �oil 6�ings
U'�-c��»-�o�n-(�i-+t, 15St�Li�l---99.�6 t' ���,..sris-C�vn� \ '� tL�—,_. � ��\ �Z �B@lK,�: MOtk
° +-� �' �ti-- �s '` '
,� " ,,�"� " -��.� � `�' ,e _ v �4-- -`' �i�� Note= Th�s system is to be canstructed fo meeS
�' =`z '- S`^ ��' � the NGrnesoto Pollu!ion Con!rd A^en
�(oQ o� `'• lst �� - a`�.5. � y- QQ�t -1-,0 - �- -__ = ,: = y t7
9�.a s�o„ -;,�.�_ --9 Chapter 7080 & •Local Ordinanc
r. •� n �va '� -`tSS.`6 �..YtvQ�F _-- a�\ i,Q,o i� r , 9t.S ,+rc9D' /
4�r'14»V ��/i J, ,1�� ��'l� �i .
G�'A�h6£�t � 0yy`�
u- o�,,� s�� Check all underground �tilities
toti�+.o a-c,ws
I, ;�-_~ PF�CPERTY OF: Ct-1f��s��NE g2aC_�
I �i"
I _ 2205 �g\�1C�b0(�1 uJfy� _
i —
/
� _D{'��c� ; H E�1cJ Co. � ru+�
�,0 3 o�T�oT �` -- '
Y
1
, �.__-�" Sm P TEST/NG/ C.
� Deygned By: ?�03. ��
, Oa:e�.2/��/2�', PH.6t2-497-3566 I
� „ ,� �7-P TESTING� ��C. Steven B. Schirmers & Debra M. Schirmers
951 Katydid Lane NE • St. Michael, MN 55376 • (612) 497-3566
FAX • (612) 497-5011
State License#394
�.OGS OF SOI� BORINGS
Christine Bruce
2205 Abingdon Way
Orono, Henn. Co., MN
Borings completed on 9-21-98, with a hand bucket auger.
BORING NUMBER 1- Elev.91.2 - MOTTLED SOIL AT 36" - no standing water present
in the boring.
0 - 14" Topsoil dark brown loam 10YR 3/2
14" - 30" Brown sandy loam 10YR 5/3
30" - 36" Brown loam 10YR 5/6
36" - 42" Rusty brown loam 10YR 5/6 -motttes 6/8
42" - 48" Rusty brown silty loam 10YR 6/3 - motties 7/1,6/8
BORING NUMBER 2- Elev.92.7 - MOTTLED SOIL AT 24" - no standing water present
in the boring.
0 - 10" Topsoil dark brown loam 10YR 3/2
10" - 24" Brown loam 10YR 5/3
24" - 32" Rusty brown loam 10YR 5/6 - mottles 7/1,6/8
32" - 42" Rusty olive brown silty loam 10YR 6/3 -mottles 7/1,6/8
42" - 48" Rusty olive brown loam 10YR 6/3 - mottles 7/1,6/8
BORING NUMBER 3- Elev.92.5 - MOTTLED SOIL AT 28" - no standing water present
in the boring.
0 - 10" Topsoil dark brown loam 10YR 3/2
10" - 28" Brown loam 10YR 5/4
28" - 48" Rusty olive brown loam 10YR 6/3 - mottles 7/1,6/8
CERTIFICATION N0.627
S'�.�T�ICENSE N0.394
PERCOLATION TEST DATA SHEET
Percolation test readings made by S-P Testing��on Q 22-98 starting at :18�m•
Test hole location Bruce�,OS Abin on Wax,,Orono.
Test hole number� Date test hole was prepared 9-21_98• I
Depth of hole bottom 1�inches. Diameter of hole C inches.
SOIL•DATA FROM TE�T HOL�
DEPTH,INCHES SOIL TEXTURE
0 - 12" Topsoil dark brown loam
Method of scratching sidewall is�. Depth of gravel in bottom of hole is� inches. Date and hour of initial
water filling 9-21-98, 10:30am. Depth of initial wa.ter filling is 12 inches above the hole battom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic sinhon.
Maximum water depth above hole�ttom during test is�inches.
Measurement, Drop in water level, Percolation rate,
Time Time interval min inches inches minutes r inch Remarks
2:08 refill 6
2:18 2:33 6 5-1/2 2.7 15 min I
2:38 2:53 6 5-1/2 2.7 15 min
2:54 3:09 6 5-112 2.7 15 min
Percolation rate=�,,�ninutes per inch.
CE�TIFICATION N0.627
S'�'...A��,ICENSE N0.394
PERCOLATION TEST DATA SHEET �
Percolation test readings made by S-P Testin�.Inc. on 9-2�98 starting at 2:19�.
Test hole location Bruce,2205 Abingdon Way,Orono.
Test hole number� Date test hole was prepared 9-21_98•
Depth of hole bottom 12.inches. Diameter of hole�inches.
SOII,DATA FROM T�ST HOLF
DEPTH,INCHES SOIL TEXTURE
0 - 10" Topsoil dark brown loam
10" - 12" Brown loam
Method of scratching sidewall is 1�if� Depth of gravel in bottom of hole is 2 inches• Date and hour of initial
water filling 9-21-98, 10:30am. Depth of initial water filling is 12 inches above the hole bottom.
Method used to maintain at least 12 inches of wa.ter depth in hole for at least 4 hours is autumatic si�hon.
Maximum water depth above hole bottom during test is�inches.
Measurement, Drop in water level, Percolation rate,
Time Time intenral min inches inches minutes r inch Remarks
2:08 refill 6
2:19 2:34 6 43/16 3.6 15 min
2:37 2:52 6 41/16 3.7 15 min
2:55 3:10 5 4 3.8 15 min
Percolation rate=�xninutes per inch.
CERTIFICATION NO.b27
S'T¢�cT��,,ICENSE N0.394
PERCOLATION TEST DATA SHEET
Percolation test readings made by S-P Testing,Inc.on 9_22-9g starting at 2:20�m•
Test hole location Bruce,2205 Abingdon WaX�Orono.
Test hole number�. Date test hole was prepared 9_21_9g•
Depth of hole bottom�2.inches. Diameter of hole C inches.
SOI[.,DATA FROM TEST HOLE
DEPTH,INCHES SOIL TEXTURE
0 - 10" Topsoii dark browm loam
10" - 12" Brown loam
Method of scratching sidewall is� Depth of gravel in bottom of hole is 2 incbes• Date and hour of initial
water filling 9-21-98, 10:30am. Depth of initial water filling is 12 inches above the hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic sinhon.
Maximum wa.ter depth above hole bottom during test is(inches.
Measurement, Drop in water level, Percolation rate,
Time Time interval min inches inches minutes r inch Remar{cs
2:08 refill 6
2:20 2:35 6 5-1/2 2.7 15 min
2:36 2:51 6 5-1/2 2.7 15 min �
2:56 3:11 6 5-1/2 2.7 15 min
Percolarion rate=�,7.�minutes per inch.