HomeMy WebLinkAbout11-09-1996 - S-P Testing, Inc. re: onsite sewage S-P TESTINGS INC. Steven B. Schirmers • MPCA Cert.No. 627 951 Katydid Lane NE • St. Michael, MN 55376 • (612) 497-3566 FAX (612) 497-5011 State License #394 ?`-'� November 9, 1996 1 7 3- 3 �1 John Pruden 315 Woodhill Rd. Lot 2 Orono, Henn. Co., MN This On-Site Sewage Treatment System is Designed for a Type 1, five bedroom home, in accordance with the Minnesota Pollution Control Agency Chapter 7080 and local ordinances. The soils on this site are SCS soils mapped - KkC - Kilkenny loam. The seasonally saturated soils were located at 2-1/2' & 2'8" in th's #1, 2 & 3 (future site) which will require a pressurized mound system & 5-1/2' & 6-1/2' in th's #4, 5 & 6, the proposed site. The bottom of the treatment area must be located at least 3' above the seasonally saturated soils. A Standard Trench System may be installed. The soils at a depth of 12" in th's# 1, 2 & 3 have a percolation rate averaging 5.9 mpi. The soils at a depth of 24" in th's#4, 5 & 6 have a percolation rate averaging 17.6 mpi. All neighboring wells are located greater than 100' away from the proposed treatment area. Keep all heavy equipment off of the proposed treatment area before and after construction. The treatment area should be marked off before construction. This Design is not valid & the system will need to be relocated if failure to protect the areas proposed for On-Site Sewage Treatment occurs. 1 With proper installation and maintenance, this system should have no problem in treating septic effluent effectively. Nothing other than gray water (laundry, showers, etc.) should be disposed of into the septic tanks. Garbage disposals are not recommended, due to adding more solids & fine solids passing through to the system. Excessive amounts of soaps, cleaning agents & chlorine agents may kill the bacteria needed to treat septic effluent. Additives are not recommended. Recommend to pump & clean your tanks through the manhole by a certified pumper every 2 years. Check with your pumper to set up a schedule. e Steven B. Schirmers 2 - / ` `1� \ A\-� N )1"/LI, 6%,1,�r,i -vim o�-v- Or -n4- --- 'P14-74o •1‘sz- >-1'S Nl fir+T A'e rvYA 15s-SrOg t xcaz- c;vNs-Cts-e.-no)1. / \ 4 I \1 to K.° t r\ I ioau.o 1 �•F�� J 41 INc_\‘ . Is 1 I ,, ,__.0- L � , i I .L.1)-S a, s> J I \ O / .,,,,00-)•4I vi 1 \; f I ` 4o\ 14Z Yl,'N --60-V o ZizD at-I -fla / ioo+/ '(oozy b 0‘--"'C l �'�O P Z-T t 111 \� �/\ T\1 0 14 T x 1op1.1_ 7.1 Y'c. \ -\\\ ��opb•g+ 5d� "P4-t,•4oS k ma— 9�G .O fqSSilwti�ia \ \ '°oe\ \ • + 1 _ / 1024' �,R \ o sa-t-�- ,11014;1.4— zso .vr eD Per colotion Tests Scale- 1 = SO c 1• � -, toCl.°— —\ cp 1^ Q I.,__• x 1Q1tl' 1,1oo9.b C+SoiI Borings 'G�C�'�5104-(/ `� �A O'er RRA rno>,�+p, x 1Oo4• -.,. ;_ o, z._ o� ®Berx1: Mork 1°os° '0-'; '`ip04 Note This system is to be constructed to meet 1otl4.\ vN 3 �0 �2. ' -,::VII � the Minnesota Pollution Con!rot Agency ' � s Chapter 7080 & Local Ord inanc- / Q ,• Check all underground utilities _ Al.: ____ ( -.H., -... 9 PROPERTY OF: SottN PRuDE.6 - 100' __It S. vsooDt-4\LL 'RD• LoT 1 31e oet),)0 1 \-1/4E_r1�1. Co.) VY\c4 S-P TESTING IN�= CL . �-e�� 5u� � ,• Designed By:� 62 , , I Do!e:J1/_ /2 PH.612 -497-3566 existing grade back fill lamin. I.)EoT -t1._-- - FA8Y--)c� 0 4"pipe dia. II T- � �I 15i'rock filter material SET- BACKS rake sidewalls & bottom to HOUSE System must be remove smearing {-4-18'-36'.I Tank (L. from property lines 'F-Ls\-L Is0-s.' T `)S ' from wells WA..y.--cr.-1< 1 from bldgs. TRENCH X- SECTION Iva (min. of two trenches) Treatment area �2 from property lines MA>JRRoL5 -mil x. nom'from wells (max. length 100 ) la."op a P 13xice Ftn 'from bldgs. - )0 'from trees SOIL BORING ELEVATIONS fromII `k_es&streams At least 4 I/2'of undisturbed earth min. I ' /°oe,o between trenches s 1i 4 dia. Pipe ' TH. I EL.-looc„1 --(1-a-"`-(o- 1007•{, / �---- - TH."l EL. -roog.i, Tank Tank trade °A slope TH. 3EL.-/oo9'1 Drop to Tank �uo'v L„-ate - ,__, .. 1� -,41.. -,LN )009.0 ') TH. 4 EL-tooS.to ' 30 - � Min. I to 8 TH. 5 EL.-)o0-2.‹ Max.I"to 4' DROP BOXES )'N' - s' °'F Y'`pt-y.- - io2,o.o 4't0 6"dia.pipe o Luc,'vs-c• Vi—oe,r__ /o)o. o SYSTEM DESIGN TYPE ry, S BEDROOM - Percolation rate PML min./inch (design 31 -HS min./inch) Treatment area required t/1`e of rock filter material --+-IG%-z c io sq.ft. of trench bottom area needed = 3 L" trench width -7-1.1a lin.ft.of trench needed , number of drop boxes (to be determined by the installer) Number of tanks required a , 1st tank].2.,_<0 gat, , 2nd tank/ocr>gal. minimums Cleon rock 13 cu.yds. ( 3/4" to 2 1/2”dia.,includes 2"above pipe ) PROPERTY OF To\--\S-\ �'i? 3 i. S W DO'V vw._t_... LTJ L V A 4 i-o)--(0 1✓1 r-A , A-1-'f4-k i-\ Gt7 . When constructingtrenches , this area should be shaped S-'_TEST/NG /t.v'C. Note: hNote: Distance from treatment area to neighboring wells— Designed By g- z— to divert run-off from entering treatment area. � '�� �� IDo _ Date:.1)_/. /96 , PH. 612-497-3566 INDIVIDUAL SEWAGE TREATMENT SYSTEM WORKSHEET D-25 FLOW Estimated Sewage Flow in Gallons per Day(mad) ' A'. Estimated 'ASO gpd Number measured - x 1.5= - gpd or 'type t Type U Type DI Type IV SEPTIC TANK VOLUME Bedrooms B. I I x:50 1 -/000 gallons 3 Oso 225 303 180 �A 4 600 375256 ,,,c. SOILS(Site evaluation data) 5 9 0 525 50 32 nu C. Depth to restricting layer= SLC.YF) L'-4S' feet 7 105026006737008 `'� D. Maximum depth of system C-3 ft= a , S feet E. Percolation rate J '1 . (i MPI F. SSF a.0 sq ft/gpd Number MincTaMinim Sc :i Capacity 1.-Mt of Liquid Garbage ry Disposal TRENCH BOTTOM AREA Bedrooms (galpmeion) (g H. For trenches with 6 inches of rock below the pipe: A x F= x = s ft of bottom area 2 orless4 00 1,1255 q 3 or 4 1,000 1,500 I. For trenches with 12 inches of rock below the pipe: 5 or 6 1,500 2.250 A x F x 0.8= x. x 0.8=; ,sq ft of bottom area 7 or 8 2,000 3.000 J. For trenches with 18 inches of rock below the pipe: over 9 See fig.C-6 (x 1.5) A x F x 0.66= ')Std x a.0 x 0.66= 990 sq ft of bottom area So4 Otaracterinas,,nequire Areas for seer.se>;<,m„we K. For trenches with 24 inches of rock below the pipe: Percolation y„ Tr"-" dulemo AxFx0.6= x x0.6= sq ft of bottom area sonTeXtt �,- BED BOTTOM AREA Faster than 0.1' Coarse Sand - - L. For seepage beds with 6 or 12 inches of rock below the pipe; 0.1 to s Sand 0.83 0.60 Pag 01 to s Fine Sand" 1.67 0.60 1.5 x A x F= 1.5 x x = sq ft of bottom area 6 to 15 Sandy Loam 1.27 0.79 16 to 30 Loam 1.6 0.60 31 to 45 Silt Loam 050 ROCK VOLUME IN CU FT46 to 64) a 0.24 Slower than 60"' ay - (024) M. Rock depth below distribution pipe plus 0.5 foot times bottom area: ge treetinerd M=Rock depth+6 inches x Area(H I,J L K) K' tar percniable soda. P •'salMarina sac a mored tam w x d eery fire.arid( ft)x "`1D =P AID cu ft -soil with too high a pamaag d day tar uutatLden d.n inBau,d nanda,d ire.,. ROCK VOLUME IN CU YDS N. Volume in cu ft divided by 27 M+27=cu yds +27= ')3 cu yds ROCK WEIGHT O. Cubic yards times 1.4=tons 6 inches= 0% Reduction* N x 1.4=tons r)3 x 1.4=/o P. tons • 12 inches=20% Reduction 18 inches 34%'Reduction DISTRIBUTION 24 inches=40% Reduction (Check one based on slope) *Sizing for gravelless trench Bed(less than 6%slope) Trenches Drop boxes(any slope) Distribution box(level to slightly sloping) "'1:t:;,-**�t�f**:?:I:f:t: T TRENCH LENGTH „•ti.ti.�•ti.�•,ti•ti.�.ti.ti•ti.ti 1.1.1.1.1.1.1.1.1.1.1▪.1.1• 2in'II(cch Cover P. Select trench width= 3•v ft 1.1.1.1.1.1.1.1.1.1.1.1.1• . 1.1,1,1,1 1,1.1,1, Q. Divide bottom area by trench width: (H,I,J,or K) +P = *PPP:, %.1::::::::::: lineal feet *PPP:. :141▪.1.1• 4 inch Pipe 90 Z =2o lineal feet f:1.1.1.1 1.1.1- 1.1• 1.1.1.1.1• LAWN AREA ",ti•ti•ti•ti• :.,•�•~., - . 1.1.1.1.1• t•f•1.1.1.1• ,ti.ti.ti.t.ti.ti.ti.ti.l.ti.ti.1.ti..t II R. Select trench spacing,center to center= ' feet Lti:{f;rtif{{{f;{{'•{r{f f{{ti{; )q: • 1.1.1.1.1.1.1.1.1.1.1.1.1• ,�,ti.ti.ti.ti,ti.ti.�.ti.ti.ti.�.ti.ti S. Multiply trench spacing by lineal feet R x Q=sq ft of lawn area ;;x5:4:44:13%{`{fti'ti'•ti'{fti 6-24 inch ••1.1.1.1.1.1.1.1.1.1.1.1.1• x 54 =,P(J•I(.) sqft �1ti1~1:1�1�1:P.741~rti1�1�1�Rock Below the Pipe� tir?rtirtiftiftiftir r`f~ftir?ftir: tif�fti,,ti, titi.ti•%•%•%•%•%•%•tifti.▪%• •%•% LAYOUT(Use other side) �ti,ti• ti. . .,,,,,,,,,•, 1.Select an appropriate scale;one square= feet. 2.Show pertinent property boundaries,right-of-way,easements. . 3.Show location of house,garage,driveway,and all other J improvements, existing or proposed .Show location and layout of sewage treatment system. 5.Show location of water supply well. 6.Dimension all set backs and separation distances. Figure D-26 S-P TESTING, INC. Steven B. Schirmers • MPCA Cert.No. 627 951 Katydid Lane NE • St. Michael, MN 55376 • (612) 497-3566 FAX • (612) 497-5011 State License #394 LOGS OF SOIL BORINGS John Pruden 315 Woodhill Rd., Lot 2 Orono, Henn. Co., MN Borings completed on 10-17-96, with a hand bucket auger. BORING NUMBER 1- Elev.1006.4 - MOTTLED SOIL AT 2-1/2' - No standing water present in boring. 0 - 10" Topsoil dark brown loam 10YR 3/2 10" - 30" Brown clay loam 10YR 5/4 30" - 46" Rusty brown clay loam 10YR 5/4 - mottles 6/1,6/6 46" - 60" Rusty brown loamy medium sand 10YR 5/4 - mottles 6/1,6/6 BORING NUMBER 2- EIev.1008.6 - MOTTLED SOIL AT 2'8" - No standing water present in boring. 0 - 10" Topsoil dark brown loam 10YR 3/2 10" - 32" Brown clay loam 10YR 5/4 32" - 50" Rusty brown clay loam 10YR 5/4 - mottles 6/1,6/6 50" - 60" Rusty olive brown silty loam 10YR 6/3 - mottles 6/1,6/6 BORING NUMBER 3- Elev.1007.1 - MOTTLED SOIL AT 2'8" - No standing water present in boring. 0 - 10" Topsoil dark brown loam 10YR 3/2 10" - 32" Brown clay loam 10YR 5/4 32" - 40" Rusty brown clay loam 10YR 5/4 - mottles 6/6 40" - 48" Rusty olive brown clay loam 10YR 6/3 - strong mottles 6/1,6/6 48" - 60" Rusty olive brown loam 10YR 6/3 - mottles 7/1,6/6 Pruden 315 Woodhill Rd. Lot 2 soil borings cont'd. BORING NUMBER 4- EIev.1005.6 - MOTTLED SOIL AT 61/2' - No Standing water present in the boring. 0 - 10" Topsoil dark brown loam 10YR 3/2 10" - 30" Brown clay loam 10YR 5/4 30" - 54" Yellowish brown loam 10YR 6/6 54" - 60" Brown sandy loam 10YR 6/4 60" - 78" Yellowish brown loam 10YR 6/6 78" - 84" Rusty brown loam 10YR 5/6 - mottles 6/1,6/6 BORING NUMBER 5- Elev.1007.5 - MOTTLED SOIL AT 5-1/2' - No standing water present in the boring. 0 - 8" Topsoil dark brown loam 10YR 3/2 8" - 38" Brown clay loam 10YR 5/4 38" - 66" Yellowish brown loam 10YR 6/6 66" - 84" Rusty olive brown loam 10YR 6/3 - mottles 6/1,6/8 BORING NUMBER 6- Elev.1007.6 - NO MOTTLED SOIL PRESENT IN THE BORING. 0 - 14" Topsoil dark brown loam 10YR 3/2 14" - 38" Brown clay loam 10YR 5/4 38" - 84" Yellowish brown loam 10YR 6/6 2 CERTIFICATION NO.627 STATE LICENSE NO.394 PERCOLATION TEST DATA SHEET Percolation test readings made by S-P Testing.Inc. on 10-18-96 starting at 10:30am. Test hole location Pruden,315 Woodhill Rd.,Lot 2,Orono. Test hole number L Date test hole was prepared 10-17-96. Depth of hole bottom 11 inches. Diameter of hole¢inches. SOIL DATA FROM TEST HOLE DEPTH,INCHES SOIL TEXTURE 0 - 10" Topsoil dark brown loam 10" - 12" Brown clay loam Method of scratching sidewall is knife. Depth of gravel in bottom of hole is 2 inches. Date and hour of initial water filling 10-17-96, 11:00am. Depth of initial water filling is 12 inches above the hole bottom. Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic siphon. Maximum water depth above hole bottom during test is¢inches. Measurement, Drop in water level, Percolation rate, Time Time interval,min inches inches minutes per inch Remarks 10:15 prefill 6 10:30 11:00 6 5 6 30 min 11:11 11:41 6 4-7/8 6.2 30 min 11:42 12:12 6 4-3/4 6.3 30 min Percolation rate=6.2 minutes per inch. CERTIFICATION NO.627 STATE LICENSE NO.394 PERCOLATION TEST DATA SHEET Percolation test readings made by S-P Testing.Inc. on 10-18-96 starting at 10:31am. Test hole location Pruden,315 Woodhil Rd.,Lot 2,Orono. Test hole number 2.. Date test hole was prepared 10-17-96. Depth of hole bottom 12,inches. Diameter of hole fi inches. SOIL DATA FROM TEST HOLE DEPTH,INCHES SOIL TEXTURE 0 - 10" Topsoil dark brown loam 10" - 12" Brown clay loam Method of scratching sidewall is knife. Depth of gravel in bottom of hole is 2 inches. Date and hour of initial water filling 10-17-96, 11:00am. Depth of initial water filling is 12 inches above the hole bottom. Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic siphon. Maximum water depth above hole bottom during test is¢inches. Measurement, Drop in water level, Percolation rate, Time Time interval,min inches inches minutes per inch Remarks 10:15 prefill 6 10:31 11:01 6 5-1/2 5.5 30 min 11:10 11:40 6 5-1/2 5.5 30 min 11:43 12:13 6 5-1/2 5.5 30 min Percolation rate=5.5 minutes per inch. CERTIFICATION NO.627 STATE LICENSE NO.394 PERCOLATION TEST DATA SHEET Percolation test readings made by S-P Testing,Inc. on 10-18-96 starting at 10:32am. Test hole location Pruden,315 Woodhill Rd.,Lot 2,Orono. Test hole number a. Date test hole was prepared 10-17-96. Depth of hole bottom 1.2.inches. Diameter of hole li inches. SOIL DATA FROM TEST HOLE DEPTH,INCHES SOIL TEXTURE 0 - 10" Topsoil dark brown loam 10" - 12" Brown clay loam Method of scratching sidewall is knife. Depth of gravel in bottom of hole is 2 inches. Date and hour of initial water filling 10-17-96. 11:00am. Depth of initial water filling is 12 inches above the hole bottom. Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic siphon. Maximum water depth above hole bottom during test is¢inches. Measurement, Drop in water level, Percolation rate, Time Time interval,min inches inches minutes per inch Remarks 10:15 prefill 6 10:32 11:02 6 5-1/4 5.7 30 min 11:09 11:39 6 5 6 30 min 11:44 12:14 6 4-3/4 6.3 30 min Percolation rate=6.0 minutes per inch. CERTIFICATION NO.627 STATE LICENSE NO.394 PERCOLATION TEST DATA SHEET Percolation test readings made by S-P Testing.Inc. on 10-18-96 starting at 10:33am. Test hole location Pruden,315 Woodhill Rd.,Lot 2, Orono. Test hole number 4. Date test hole was prepared 10-17-96, Depth of hole bottom 24 inches. Diameter of hole li inches. SOIL DATA FROM TEST HOLE DEPTH,INCHES SOIL TEXTURE 0 - 10" Topsoil dark brown loam 10" - 24" Brown clay loam Method of scratching sidewall is]wife. Depth of gravel in bottom of hole is 2 inches. Date and hour of initial water filling 10-17-96. 11:00am, Depth of initial water filling is 12 inches above the hole bottom. Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic siphon. Maximum water depth above hole bottom during test is li inches. Measurement, Drop in water level, Percolation rate, Time Time interval,min inches inches minutes per inch Remarks 10:15 prefill 6 10:33 11:03 6 2-1/16 14.5 30 min 11:08 11:38 6 2 15 30 min 11:45 12:15 6 2 15 30 min Percolation rate=14.8 minutes per inch. CERTIFICATION NO.627 STATE LICENSE NO.394 PERCOLATION TEST DATA SHEET Percolation test readings made by S-P Testing.Inc. on 10-18-96 starting at 10:34am. Test hole location Pruden,315 Woodhill,Lot 2,Orono. Test hole number a. Date test hole was prepared 10-17-96. Depth of hole bottom 24 inches. Diameter of hole inches. SOIL DATA FROM TEST HOLE DEPTH,INCHES SOIL TEXTURE 0 - 8" Topsoil dark brown loam 8" - 24" Brown clay loam Method of scratching sidewall is knife. Depth of gravel in bottom of hole is 2 inches. Date and hour of initial water filling 10-17-96, 11:00am.. Depth of initial water filling is 12 inches above the hole bottom. Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic siphon. Maximum water depth above hole bottom during test is¢inches. Measurement, Drop in water level, Percolation rate, Time Time interval,min inches inches minutes per inch Remarks 10:15 prefill 6 10:34 11:04 6 2-3/4 10.9 30 min 11:07 11:37 6 2-5/8 11.4 30 min 11:46 12:16 6 2-9/16 11.7 30 min Percolation rate= 11.3 minutes per inch. CERTIFICATION NO.627 STATE LICENSE NO.394 PERCOLATION TEST DATA SHEET Percolation test readings made by S-P Testing.Inc. on 10-18-96 starting at 10:35am. Test hole location Pruden,315 Woodhill Rd.,Lot 2,Orono. Test hole number¢, Date test hole was prepared 10-17-96. Depth of hole bottom 24 inches. Diameter of hole 6.inches. SOIL DATA FROM TEST HOLE DEPTH,INCHES SOIL TEXTURE 0 - 14" Topsoil dark brown loam 14" - 24" Brown clay loam Method of scratching sidewall is knife. Depth of gravel in bottom of hole is 2 inches. Date and hour of initial water filling 10-17-96,11:00am. Depth of initial water filling is 12 inches above the hole bottom. Method used to maintain at least 12 inches of water depth in hole for at least 4 hours is automatic siphon. Maximum water depth above hole bottom during test is inches. Measurement, Drop in water level, Percolation rate, Time Time interval,min inches inches minutes per inch Remarks 10:15 prefill 6 10:35 11:05 6 1-1/8 26.7 30 min 11:06 11:36 6 1-1/8 26.7 30 min 11:47 12:17 6 1-1/8 26.7 30 min Percolation rate=26.7 minutes per inch. V_ C Z u O _pJ O 7a� L W Z •JL OC O ' 3",• I.� a Zx m . ill O xx jt¢ W y O Lii N W 3 6A\ Coo W B wu xU Owg 24o-- u� r Ny O m W W I- W WII.W 1-0 yN H C O ~ 3ON u 0 ,Er C cW N 0 3 0 Q ..`Ztt'e• -i I..0 ,43d0 ?x Y.O ,. '^f I /\lOOV •�� vg Z2� ;;G - Vx O miaowFa >J NWw @I� ,,.E .i W3 QJH< / \ hWJJ JN 2= W bJ L 7 Q ■ A gyJj LLWOZ 016 It i• R I \ U i0([N O > u u • yy-'� F- p. '� :� \ Sao $ v c6 i J O ? aZ N Z~WNF� LaIL tA0 NJN ��t ` au JV W t1 (n L.. ..: !- 1 • • 410 V >`•' u W „taw U C¢m N= �W2 S+:' .r:,' C O a2 0 Z_ TU Q •' x> > o O " :•�•) ,� F¢ O UW m O WWWaJ J tat-.`k. ! , 1 S -C CO > m= 2J Z dJIW H C V2 1'-' t.+h:. C`�� t _.. ,•.` I I~ 2 2 Or 0. <a5 W I¢'-N CJ~m0 CrU a ¢0 W :'; .1 \ 1 = 7- zyyg a 20 H I-co 'nv0 ZI-ua0 g 0- j �.,•. .';,x-. .�' 3_ a W O W In a1= WCOm . r� �\ 1 N Z `" CLLO W ISI- 00 oZ W Z7 W7 {� \`. I f3 3o 0 tLOf• W O+ Zz 2 I-O_ yN N Cr Z • Js {y -1.,:!..... :- r `N• 1 OR ¢< W WW O O 22 c°42 ai� S �WZ- O j.Y5L'; � * ♦� 'p N d J xYC 1 W O O WJ3 IH ZV ZVO �:. ♦ ! o1 I In m ~aF- F Y LW0 ..v'16.0" 2 ',JO L1 ` I ♦J , OW a 3J0 2 . 00 WWW WJ Off. a¢ x2N5 �-:tiy:: ;� _� \t\\ y� 1i a pr Zd =• m¢ aJ¢ odI24 2r- 3a_►- cr - Ca t y�yt L � -� \ \ 3 >�0.a • W 3 t •.•,. . ,..:, ..„-,:z,, \ 1 liii Jt1 p J W {L 1x-41.,., 0 ,„28r.,- Litt4/0)44 _O ....,. i..1......1.2:......;.liti• ..1/4 . 7...t.:.; \1\\ 4.,i\\%s i :::a."12 e6:1- i 11:f 1 Z r:z P-12.-1 40.1 0 n 6 . IF oil u..- LIJ J.',.. J�st, • �-':;: -.. --� \\ I_ 4. I_O • N • � '4 h \ � _'y151, �i•, ,• ~ tip �t _J • \_ \ \ OO ., ::. WIp 1 f .. ce m rim- e 4.• ...:1, ";Al,. .Ct.; -7:. .-/- 0,e• // E° Hall co 00 9 // 1‘‘ . , • i i: / /i/ O �Yi ' 'h,:../ /� ci I I / NOTES OUTLET TO J. ALL PIPES SHOULD BE AT LEAST 4-INCH i TRENCH DIAMETER. INLET FROMN ill 2. ELEVATION OF INLET AND SUPPLY LINE TO SEPTIC TANK BOX NEXT DROP BOX MAY BE ADJUSTED UP OR DROP B OR PREVIOUSDOWN FOR DESIRED EFFLUENT LEVEL IN ,� � -SUPPLY LINE' TO NEXT TRENCH. DROP DOX 3 SUGGESTED TRENCH LIQUID LEVELS: (A) 2 INCHES —AIL, , iiri--...- ,. ABOVE TOP 1 , . ABRICOUTLET COVERSPIPE ROCKP( BMATBTE OP OF OUTLET PIPE IF HAY OR STRAW AND _ BUILDING PAPER COVERS ROCK. •r 4. INVERT OF INLET MUST BE AT LEAST ONE INCH HIGHER THAN. INVERT OF SUPPLY PIPE TO NEXT DROP BOX. le OUTLET TO I TRENCH 5. TRENCHES MAYOUTLET ONE SIDE OR BOTFI SIDES OF DROP BOX. :elIMININIMIIIIM / ., •/ -. I SUPPLY I -INLET '����� ;T_ LINE 1� �'-SUPPLY LINE ! ILLNIA JI I. ( .I _ I ; 1 MI TO TRENCH ---_ -T- OUTLE ___ _ OU TTRLET TO ENCH \ DROP BOX • • • . --- n.` . VERTICAL SIDEWALL SEPTIC TANK ' ---L /—FINISHED GRADE —AT LEAST sq., 6"TO 12" SOIL AT LEAST 4" DIA. t COVER 4" DIA. ,` P�11r1 rAT LEAST I" ' AT LEAST I" -I 1 A DIMENSIONS FOR_TANKS WITH VERTICAL SIDES A WIDTH, W _24• MINIMUM — --J I I—(3 1 LENGTH, L_ 2 TO 3 TIMES THE WIDTH DIAMETER 60• MINIMUM _ _ 4 L B DEPTH, D 30• MINIMUM; 78` MAXIMUM C — A0.2 D _ 4 r — _ --AT LEAST g 6" MINIMUM• 0.2 0 MAXIMUM _ C 0.4 D — - ------• • - --AT LEAST 4 FEET-- -- ---1 NOTES: • I. SNNIT NIY ZEES AT(FAST A INCHES IN OLAMWII E1Ff1 J. L 101 E COVERS SI NIL FE LOCATED WIIIIW 121NG(ES. 2. 11 IEFIE_SHAI l DE ONE OR 1,01E tifNJl AXES,20-IF AST IE TIE MANX KxE IS MALI NN SIX NCI E S OF 111E SU(V ACE DIMEILSIONAAJO LOCATED WI I ITN 6 FEET C6 ALL TAN!( II IE COVET{mist OE SECUIED IOMEVENT ACCESS. .. • WAILS 6. SEM-LAIAN DIS f ANCE BETWEEN ENO OF INLET f'ME ANU 3. AN IASVECIION PIPE OF AT LEASE 4 NCIIES DIAAEEIER NEATIEST POr11 ON DMFLE TALI OE NO LESS 11 INN 6 NCI IES On A TAM IDLE Si MT RE tOCA1 ED 0,./En COIN TIE INLET CO NO 1.4011E T1 LAN 12 ICI IES, N10 OUTLE T DEVKYS.TNECENI Ell LNC OF 11 E TIS1'EC1014 6. 10X11101620(I ALCYl6JfX11CA1.1ANKS DIMENSION A IS 0.150 PIPES ST NIL OE IRS SAM1 AS TIlE CONI in INE OF INE AND OII.ENSION C ISO.350. e DN FLE OPENINGS OD SANT I NTY TEES.A 114100 NSI'EC I ON • T'I'E IJJST RE LOCA IEU(II:IWC FN TIlE ME ANO(XIII ET DN ILES. ---- PENCIL r1MARKS ^ II��/' 1 ':7Tt•• a'•ai■•. 20" 0i `., • 1 ,S.; ,. MANHOLE 1 INLET • [r���) W 11..111 OUTLET r-''OUTI.ET LEVEL ��} I p .-, Y r. _.__ SCUM CLEAR SPACE- ' J�11 —,ir y CLEANEOUT TANK WHEN �. -- _ ��—"A• _ 3 4 IS 3" OR LESS OR - —3 —'— 1} B 'B'IS 12*OR LESS • • I :• •�• �:_BLACK COLOR ki.'.....•:...,•:.:.:''' SLUDGE .'•• i•k .,•1 DISTINGUISHES SLUDGE ,�::;:• ! • • LAYER FROM LIQUID IA imiS)1:�r}•i .,•,i`L_ti.. :if% .e AARP 4 iii ;rte • •,•:.44,1' io -7 Y� yr MEASURE SCUM AND SLUDGE ACCUMULATIONS IN THE SEPTIC TANK