H.V.A.C. Calculations
H.V.A.C. CALCULATIONS McGUIRE RESIDENCE 315 WOODHILL ROAD ORONO, MINNESOTA PREPARED BY: AFTON CONSULTING ENGINEERS 1421 NEAL AVENUE SOUTH AFTON, MINNESOTA 55001 PHONE: 612-436-1389 FAX: 612-436-2594 FOR: EXCEL AIR SYSTEMS, INC. 2075 PROSPERITY ROAD MAPLEWOOD, MN 55109 PHONE: 612-779-9725 FAX: 612-779-7040 11/16/97 DESIGN CONDITIONS FOR HVAC McGUIRE RESIDENCE ORONO, MN. DESIGN TEMPERATURES: INDOOR OUTDOOR WINTER 70° -25°F SUMMER 78°/50%R.H. 92°db/75°Wb BUILDING HEAT TRANSMISSION VALUES (U btu/hr/°F/S.F.) ROOF: Wood Frame Roof with R-44 insulation U = .023 WINDOWS: Double glazed, insulating U = 0.60 DOORS: Insulating Glass U = 0.60 WALLS: Wood frame, 2"x 6", R 19 insulation, stucco U = 0.053 GRADE FOUND: 12" Concrete Block, 2" insulation U = 0.15 HEAT LOSS CALCULATION MULTIPLIERS: ROOF: AREA X 95°x U value =AREA X 2.2 WINDOWS: AREA X 90°X U value =AREA X 57 DOORS: AREA X 95°x U value =AREA X 57 WALLS: AREA X 95°X U value =AREA X 5.0 FOUNDATION WALLS: AREA X 50°X U value=AREA X 7.5 HEAT GAIN CALCULATION MULTIPLIERS: ROOF: AREA X 40°(Equiv. Temp Diff.) x U value =AREA 0.92 SOUTH OR WEST WINDOWS: NON SHADED AREA X 100 NORTH WINDOWS: AREA X U value X 15°=AREA X 9.0 EAST WINDOWS: NON SHADED AREA X 60 SOUTH OR WEST WALLS: AREA X 35° (Equiv. Temp Diff.) X U value = AREA X 1.90 NORTH WALLS: AREA X 15°X U value=AREA X 0.80 EAST WALLS: AREA X 25°X U value =AREA X 1.33 VENTILATION CRITERIA: 20 CFM PER PERSON 2 CFM per S.F. exhaust in bathrooms 11/16/97 BUILDING SUMMARY McGUIRE RESIDENCE, ORONO, MN SUMMARY OF HVAC LOADS FOR TOTAL BUILDING ROOM HEAT LOSS AND GAIN NOT INCLUDING VENTILATION FIXAMININIMAginna !���(• BTU/HR SENSIBLE LATENT 'TOTAL FIRST 119,662 64,529 11,478 78,690 SECOND 85,186 46,796 4,112 50,908 BASEMENT 11,400 - - - POOL 45,444 TOTALS 1 261,692 111,325 1 15,590 ] 129,598 NOTE: Heat loss and gain figures do not include Wine Cellar HVAC BATHROOM AND LAUNDRY AREAS VENTILATION REQUIREMENTS EWA: riVERESKAI� �x: � ' _ ;' r.:....r .. CFM SENSIBLE 'LATENT ]TOTAL FIRST 120 1,920 3,000 4,920 12,369 SECOND 1,520 24,320 38.000 62,320 156,674 TOTALS 1,640 26,240 I 41,000 I 67,240 169,043 SWIMMING POOL VENTILATION REQUIREMENTS OOLIN -HEATIN . t CFM SENSIBLE LATENT TOTAL 1500 24,000 37,500 61,500 154,613 FIRST FLOOR AIR HANDLING UNIT: TOTAL COOLING CAPACITY REQUIRED INCLUDING VENTILATION: 83,610 =7 TONS TOTAL HEATING REQUIRED INCLUDING VENTILATION: 132,031 BTU/HR SECOND FLOOR AIR HANDLING UNIT: TOTAL COOLING CAPACITY REQUIRED INCLUDING VENTILATION: 113,228 = 9.4 TONS TOTAL HEATING REQUIRED INCLUDING VENTILATION: 241,860 BTU/HR 11/16/97 SECOND FLOOR SUMMARY 1 A McGUIRE RESIDENCE SUMMARY OF SECOND FLOOR HVAC I:'4, 5''1.-"- .'"'"'''''"d'r, r 1 ; "t'l I .:;q00 '440... ,1.. , ,"E ". t 4,., . „ e: , , 0,0 : ,,.! , i i„, p _„ ,.IT 1 I 0 4 , t• , ' ''''t''' rill 6. AING tA200041 -' i4Tt ' ' 1.'" - - -1 ' '' iiiiffENSIE0 '')"V` g -- 49!--)-- 1,---- ' 41-1 t ' --r-itiPc ' '1- - Isr i ' -'-- i-f-1, -- -i-- la ti 4,t-t-rikll , . , - -.I •' Jr:, 47 • 6., . •,,,:a •,.. ,,,,... o i , _ •, v t.,,L1 '4, dt• 14 . 'i ,'.. q,,t- • t L • -', 201/202 STAIRS/HALL 4,180 4,120 255 4,375 0 86 146 245 203 HALLWAY 4,514 831 183 1,014 0 92 34 176 204 CLOSET 2,318 421 85 506 0 47 17 82 205/206 CLOSETS 5,422 1,044 289 1,332 0 111 44 277 207 CLOSET 6,435 7,078 191 7,270 0 132 242 184 208 MASTER BEDROOM 6,281 1,281 452 1,733 0 129 58 433 209 MASTER BATHROOM I 4,747 1,734 219 1,953 494 97 65 247 210 OFFICE 3,043 1,190 158 1,347 0 62 45 151 211 BATHROOM 1,961 835 f--- 117 952 264 40 32 112 212 BEDROOM 8,393 2,882 287 3,169 0 172 106 275 213 BEDROOM 3,598 3,967 173 4,139 0 74 138 166 215 BATHROOM 1,608 672 93 765 210 33 26 89 216 SEWING ROOM 2,303 758 88 846 0 47 28 84 217 BATHROOM 3,787 1,299 156 1,455 352 NA NA 150 218 BEDROOM 5,555 1,062 287 1,349 0 114 45 275 219 CLOSET 1,383 316 151 467 0 28 16 145 220 STORAGE 9,125 7,523 398 7,921 0 187 264 383 221 TOYROOM 4,075 3,728 207 3,935 0 83 131 199 222 LAUNDRY 3,163 3,821 89 3,909 200 65 130 85 223 STAIRWAY/HALL 3,295 2,234 234 2,468 0 67 82 224 TOTALS 85,186 46,796 4,112 50,905 1,520 1,667 1,648 3,982 NOTES: 1. Heating/cooling does not include the ventilation load which is heated at the makeup air unit 2. Heating CFM is based on a temperature rise of 45 degrees 3. Cooling CFM is based on 400 CFM per Ton of air conditioning 4. CFM required for six air changes per hour assuming an 8 foot height of delivery at the diffusers. 11/16/97 FIRST FLOOR SUMMARY -- -- _ McGUIRE RESIDENCE SUMMARY OF FIRST FLOOR HVAC . YI111 t gg inti' N 1N Q ¥t -e, .911 a Y ® an.� ' zyG - 4 Pa 5 ;,; E t.,.,,. 44,:,:i!,, -y , 4y!R ,:.F. f< �,4;141i rTi'tui(*.' 2� bi'%ti tiF'�p., 4 , ,., i 1,6.. R€,d^7 R c ra`� i 1 I t t ' i,,3, ci,x.. .m.5.04-;;'4-S,: .,A , ,,, !, S NSIY : a .: . �i 'Al' '3 1I fl1 s )5 ., J . �k� `i. -%' ,- 101 ENTRY 10,057 5,354 1,525 6,879 0 NA NA NA 102 GALLERY 7,270 3,043 600 3,643 40 149 121 530 103 OFFICE 12,246 14,252 307 14,559 20 251 485 413 104 LIBRARY 6,315 2,771 683 3,453 20 129 115 367 105 LIVING ROOM 15,476 3,905 1,965 8,555 80 317 285 734 106 DINING 6,902 5,032 2,759 7,791 160 141 260 344 -- ---------- ----- --- - - - - 108/109 KITCHEN/DINING 10,943 12,142 1,375 13,516 - 40 224 451 744 111 FAMILY 11,680 8,151 1,731 9,882 80 239 329 510 112 STAIRS 3,965 4,144 199 4,343 0 81 145 191 113 GARAGE 25,530 0 0 0 0 523 0 979 114 BATHROOM 291 176 22 198 50 6 7 21 116 PANTRY 2,156 2,698 106 2,804 0 44 93 102 117/118 STAIRWAY 2,414 2,608 175 2,783 0 49 93 168 120 BATHROOM 4,417 253 31 284 70 NA NA 30 TOTALS 119,662 64,529 11,478 78,690 560 2,154 2,384 5,133 NOTES: 1. Heating/cooling does not include the ventilation load which is heated at the makeup air unit 2. Heating CFM is based on a temperature rise of 45 degrees i - - - 3. Cooling CFM is based on 400 CFM per Ton of air conditioning 4. CFM required for six air changes per hour assuming an 8 foot height of delivery at the diffusers. 11/16/97 SWIMMING POOL McGUIRE RESIDENCE 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I ROOM: (SWIMMING POOL 1 j I HEIGHT: I 11 1 FLOOR 1 11 1 AREA: 1690 IVOLUME:1 18,590 OCCUPANTS: 0 1 i 1 'HEAT LOSS I ELEMENT AREA I X MULTIPLIER 1= BTU/HR ROOF 1690 1S.F I 2.2 Btu/Hr/S.FI j 3,718 ' DOORS 0 1" 57 " j I - WINDOWS 0 1" 57 " - WALLS 1 j 1,027 +1" 38 1 39,026 FOUNDATION i 360 1 7.51 " 1 2,700 INFILTRATION* 0 (CFM j 102.6 Btu/Hr/CFM 1 - 1 VENTILATION** 1500 (CFM 102.6,Btu/Hr/CFM 1 153,9001 TOTAL 1199,3441 1 1 HEAT GAIN f SENS. LATENT TOTAL ROOF 1 j 0 S.F. 0.92IBtu/Hr/S.F. ! - - DOORS l S&W 0 1" 1001 " 1 - - DOORS IN&E 0 91 - WINDOWS S&W 1 0 1" 1001 - i - WINDOWS N 0 F 91 " I - - WINDOWS E 0 1 601 " I - - WALLS 1S&W 0 1.91 " - - WALLS 1N 0 1" 0.81 " - - WALLS E 0 1 0.81 - - i LIGHTS 1 i 0 3.415 *** L - - EQUIPMENT 0 1KW 34151Btu/kw ! I - ! 1 - OCCUPANTS i 0 **** 300/3001 1 - - - INFILTRATION 0 CFH 0.3/0.41Btu/hr/CFH - - - VENTILATION 1,500 ,CFM 16/251Btu/hr/CFM 24,000 37,5001 61,500 j 1TOTAL: i 1 24,000 L 37,500 I 61,500 NOTES: Infiltration based on 1/2 CFM per lineal feet of crack 1 ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise Page 1 • ORIGINAL BASEMENT McGUIRE RESIDENCE HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES j ROOM: 1ORIGINAL BUILDING 1 1 I 1HEIGHT: 8 ' FLOOR 1 BASEMENT i 'AREA: 3344 VOLUME:I 26,752 OCCUPANTS: 01 ii HEAT LOSS ELEMENT AREA X MULTIPLIER 1= ROOF 0 1S.F 2 .2IBtu/Hr/S.Fi - ' DOORS 1 0 1" 57[ " - WINDOWS 0 I" 571 " - WALLS I 1 0 I" 5 I I - FOUNDATION 916 7.5' 6,870 INFILTRATION* 0 ICFM 102.6 Btu/Hr/CFM - VENTILATION** 0 ICFM 102.6IBtu/Hr/CFM - TOTAL i 6,870 j r { HEAT GAIN !SENS. LATENT TOTAL ROOF I 0 S.F. 0.92IBtu/Hr/S.F. - - DOORS S&W 0 1" 100 " j - - DOORS 1N&E 0 ;" I 91 " ! - 1 - WINDOWS S&W 0 1" 1001 " 1 - j - WINDOWS N I 0 1" 91 " ! - - WINDOWS E 0 1 601 " j - - WALLS 1S&W 0 1.91 " 1 - I - WALLS ,N 0 0.81 " - - WALLS E 0 1 0.81 " - - LIGHTS 0 3.4151*** - - EQUIPMENT 0 ;KW 34151,Btu/kw ± - - OCCUPANTS 1 0 I**** 300/3001 - - - INFILTRATION I 0 (CFH 0.3/0.41Btu/hr/CFH 1 - - - VENTILATION 1 0 iCFM 16/251Btu/hr/CFM - - - TOTAL: I - - J - NOTES: Infiltration based on 1/2 CFM per lineal feet of crack I , *** Lighting heat gain based on 1 watt per square foot 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise Page 1 • NEW BASEMENT I i McGUIRE RESIDENCE 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: NEW ADDITION t 'HEIGHT: 8 FLOOR (BASEMENT I , AREA: 1138 VOLUME: 9,104 OCCUPANTS: 01 1 HEAT LOSS ELEMENT AREAI X MULTIPLIER = BTU/HR ROOF I 0S.F 2.2lBtu/Hr/S.F - DOORS j 0 I" 571 " - WINDOWS 0 " j 57 " - WALLS 1 1 0 " j 5^ " I 1 i - FOUNDATION 604 7.5 1 1 1 4,530 INFILTRATION* 0 ICFM 102.6 Btu/Hr/CFM 1 1 - 1 VENTILATION** 0 CFM [ 102.6 Btu/Hr/CFM 1 - TOTAL I 4,5301 I i HEAT GAIN SENS. LATENT TOTAL ROOF 1 0 S.F. 1 0.92 Btu/Hr/S.F. - - DOORS IS&W 0 " 100 " - - DOORS IN&E 0 " j 9 " 1 - - WINDOWS S&W 0 1" 100 " - - WINDOWS N 1 0 91 " ' - I - WINDOWS E 0 601 " - 1 - WALLS 1 S&W 0 I" j 1.91 I - - WALLS I N 0 1" 0.8 " WALLS 1E 0 1 0.8 " 1 - - LIGHTS 1 i 0 1" 3.4151*** iI - - EQUIPMENT 0 1KW 3415 Btu/kw ! - ' - OCCUPANTS 0 **** 300/3001 1 - - - INFILTRATION 0 CFH ! 0.3/0.4IBtu/hr/CFH - - - VENTILATION 0 ICFM 16/251Btu/hr/CFM - - 1 - i 1TOTAL: l - I - - NOTES: 1 1 Infiltration based on 1/2 CFM per lineal feet of crack ! 1 ***Lighting heat gain based on 1 watt per square foot 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area i Sensible and Latent load-based on light activity unless noted otherwise • Page 1 101 entry j I ,; McGUIRE RESIDENCE i 1 1 I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 101 entry jI HEIGHT: 1 8.5 II FLOOR 1 1 I AREA: 72 VOLUME:1 612 OCCUPANTS: 0 1 1 HEAT LOSS I ELEMENT AREA X MULTIPLIER = BTU/HR ROOF I 72 S.F i I2.2Btu/Hr/S.F i 158 DOORS j 40 57 " I 1 2,280 WINDOWS 1 0 -" 57 " I - WALLS 164 1" 5 " j 820 FOUNDATION 72 ; 7.5 " 1 I 540 INFILTRATION* 61 CFM i 102.6 Btu/Hr/CFM 6,259 VENTILATION** 0 'CFM 102.6 Btu/Hr/CFM 1 - , i l TOTAL IT 10,057 j j 1 HEAT GAIN SENS. LATENT TOTAL ROOF 1 72 S.F. 0.92 Btu/Hr/S.F. 66 66 DOORS S&W j 40 I" 100 " i i I 4,0001 4,000 DOORS jN&E 0 91 „ - _ - WINDOWS S&W I 0 j" 1001 " - - WINDOWS N j 0 I" 91 ' 1 - 1 i - WINDOWS E I 0j 601 " - - WALLS ',S&W 164 i" 1.9 " 312 312 WALLS IN 0i" 0.81 ' I 1 - - WALLS E 0 0.81 - i 1 - LIGHTS 1 0 j" 3.415'*** I - I - EQUIPMENT 0 !KW 3415 Btu/kw ! - - OCCUPANTS I 0 **** 300/3001 i I 1 INFILTRATION 61 ;CFH 16/25lBtu/hr/CFM j 976 1,525 ! 2,501 VENTILATION I 0 CFM 16/25!Btu/hr/CFM j 1 - I - - 1 (TOTAL: j I 5,3541 1,5251 6,879 NOTES: I 1 Infiltration based on six air changes per hour ! j ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area ! , Sensible and Latent load-based on light activity unless noted otherwise , • Page 1 102 GALLERY I j McGUIRE RESIDENCE HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 102 GALLERY I1 HEIGHT: T 8.5 FLOOR 1 , ! ! j AREA: 624 VOLUME:1 5,304 OCCUPANTS: '2 I ' HEAT LOSS ELEMENT AREA1 X MULTIPLIER 1= BTU/HR ROOF 0 S.F i 2.21 Btu/Hr/S.Fj - COORS 0 I" 571 " I I - WINDOWS I 0 57 " 1 - ! WALLS 1 518 I" j 5 " I 2,590 FOUNDATION I 624 7.5 1 4,680 INFILTRATION* 0 CFM 102.6 Btu/Hr/CFM 1 - ' I VENTILATION** 40 !CFM j 102.6 Btu/Hr/CFM 4,104 1 TOTAL 11,374 1 HEAT GAIN SENS. LATENT TOTAL ROOF I 0 S.F. 0.92 Btu/Hr/S.F. - - i DOORS S&W 0 1001 " 1 - - DOORS N&E 0 " 91 " ( I - - WINDOWS S&W 0 " 1001 - - WINDOWS N 1 0 " 91 " 1 - 1 1 - WINDOWS E 1 0 601 - I - WALLS I S&W 164 i" 1.91 " 312 1 312 WALLS IN 0 1" 0.81 " j - WALLS 'E 0 0.81 " j - I - LIGHTS j I 624 1" 3.4151*** 2,131 2,131 EQUIPMENT ! 0 1KW 1 34151Btu/kw j - 1 - OCCUPANTS 2 **** ! 300/3001 600 600 '; 1,200 INFILTRATION 0 ]CFH 16/251Btu/hr/CFM - - 1 - VENTILATION 40 CFM 16/251Btu/hr/CFM 640 1,000 1,640 TOTAL: 3,683 J 1,600 1 5,283 NOTES: ! ii Infiltration based on 1/4 air changes per hour 1 ***Lighting heat gain based on 1 watt per square foot 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise] Page 1 103 OFFICE I ; 1 McGUIRE RESIDENCE I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES 1 ROOM: 1103 OFFICE I !HEIGHT: j 8.5 FLOOR j 11 I 1 AREA: 1 486 (VOLUME:, 4,131 OCCUPANTS: '1 ',HEAT LOSS ELEMENT I AREAI X MULTIPLIER ;= j BTU/HR ROOF j 0 1S.F 2.21 Btu/Hr/S.FIl - ! DOORS I 0 l" { 571 I - WINDOWS I 150 ," 57 " 1 8,550 WALLS 386 " 5 " � 1,930 FOUNDATION 0 ! 7.5 " 1 - INFILTRATION* 17 (CFM 102.61Btu/Hr/CFM 1,766 VENTILATION** 20 CFM 102.61Btu/Hr/CFM , I 2,052 j !TOTAL 1 I 14,298 r l HEAT GAIN ISENS. LATENT TOTAL I ROOF I 0 S.F. 1 0.921Btu/Hr/S.F. - - DOORS IS&W 1 0 I" 1001 " 1 - - DOORS jN&E 0 " 91- " - - WINDOWS S&W 50 ," 1001 " 5,000 5,000 WINDOWS N 50 1" 91 " 450 450 WINDOWS E { 50 6011 3,000 1 3,000 WALLS I S&W 103 1.91 " 1 I 196 196 WALLS N 283 j 0.81 '' 1 226 226 WALLS jE j 0 0.81 - , - LIGHTS 486 1 3.4151*** 1 1,660 i �j 1,660 EQUIPMENT 1 KW 34151Btu/kw I 3,415 j 1 3,415 OCCUPANTS j 1 1**'* 300/3001 j 1 300 j 300 ! 600 INFILTRATION 1 17 !CFH 0.3/0.41Btu/hr/CFH 5 J 71 12 VENTILATION 1 20 ;CFM 16/251-Btu/hr/CFM I 320 j 500 1 820 I ,TOTAL: ! 14,572 I 807 I 15,379 NOTES: ! Infiltration based on 1/4 air exchange per hour+A9 *** Lighting heat gain based on 1 watt per square foot ] j **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load- based on light activity unless noted otherwise Page 1 104 LIBRARY McGUIRE RESIDENCE , j I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I ROOM: 104 LIBRARY HEIGHT: 8.5 FLOOR 1 ;AREA: I 432 ,VOLUME:I 3,672 OCCUPANTS: I 1 1 I (HEAT LOSS ELEMENT AREA I X MULTIPLIER = BTU/HR ROOF 1 0 S.F 2.21Btu/Hr/S.F - I DOORS I 0 " 57 " - WINDOWS 70 ," 57 " 1 3 ,990 f WALLS I I 151 1 5 " I 755 FOUNDATION 0 I 7.5, " I - INFILTRATION* 15 CFM 102.6 Btu/Hr/CFM 1,570 VENTILATION** 20 CFM 102.6 Btu/Hr/CFM 2,052 ;TOTAL 8,367 1 HEAT GAIN SENS. LATENT TOTAL ROOF 0 S.F.j0.92 Btu/Hr/S.F. - - DOORS S&W 0 " 100 " 1 I - - DOORS N&E 0 I" 9 I [ I - 1 I - WINDOWS S&W 0 100 " - - WINDOWS N 70 I" 9 " 1 630 630 WINDOWS E 0 601 - i - WALLS S&W 0 " 1.9 " - WALLS N 151 I" 0.8 " j 121 j 121 WALLS 1E 0 1 0.81 " T - 1 - LIGHTS I 432 " 3.4151*** 1,475 i 1,475 EQUIPMENT 0 KW I 34151Btu/kw - ( - OCCUPANTS 1 i* ••' ' 300/3001 300 300 I 600 INFILTRATION ! 15 1CFH 16/251Btu/hr/CFM 245 383 627 VENTILATION 20 1CFM 1 16/2518tu/hr/CFM 320 500 820 I i TOTAL: I 3,091 I 1,183I 4,273 NOTES: f Infiltration based on 1/4 air changes per hour I , ***Lighting heat gain based on 1 watt per square foot 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry —*Occupants normally in continuous use of area ! 1 Sensible and Latent load-based on light activity unless noted otherwise; I Page 1 105 LIVING } ' McGUIRE RESIDENCE HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1105 LIVING RM 1HEIGHT: 8.5 FLOOR 1 j AREA: 864 VOLUME: 7,344 OCCUPANTS: '4 j I I HEAT LOSS j ELEMENT AREA I X MULTIPLIER = 1 BTU/HR ROOF 0 1S.F 2.2 Btu/Hr/S.F - DOORS 0 1" 57 , - WINDOWS 198 57 " 11,286 WALLS 210 51 1,050 FOUNDATION 0 7.5 i I ` INFILTRATION* 31 CFM } 102.6 Btu/Hr/CFM 1 3,140 ITOTAL: 15,476 VENTILATION** 80 CFM 102.6 Btu/Hr/CFM 8,208-1 TOTAL 23,684 II I HEAT GAIN ISENS. LATENT TOTAL ROOF { 0 S.F. 0.92 Btu/Hr/S.F. -- DOORS S&W I 0 " I 1001 " - - DOORS N&E 0 " 91 " - - WINDOWS S&W 0 " 1 100 WINDOWS N j 198 j 9 1,782 1,782 WINDOWS E 0 ' 60 - - WALLS S&W 0 1" 1.91 " I - - WALLS N 210 1" 0.81 " I j 168 1 168 WALLS E 0 0.81 " - - LIGHTS 1 864 3.4151*** 1 2,951 i 2,951 EQUIPMENT ! 0 1IKW I 34151Btu/kw - ; - OCCUPANTS 4 **** j 300/3001 1 1,200 1,200 2,400 INFILTRATION 31 CFH 16/25 I Btu/hr/CFM j 490 765 ' 1,255 VENTILATION ; 80 CFM , 16/251Btu/hr/CFM 1,280 1 2,000 i 3,280 ' TOTAL: J 7,870 3,965 I 11,835 NOTES: 1 1 j Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise! , Page 1 106 DINING McGUIRE RESIDENCE � j 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 106 DINING 1HEIGHT: 1 8.5 FLOOR 11 I AREA: 405 !VOLUME: 3,443 OCCUPANTS: 18 j HEAT LOSS ELEMENT AREA X jMULTIPLIERj= BTU/HR ROOF j 0 S.F 2.2IBtu/Hr/S.F - DOORS 1 0 " ! 57 " ! - WINDOWS 70 f" 57 " 1 3,990 WALLS 1 288 1" 5 j 1 1,440 FOUNDATION 0 7.5 " 1 - INFILTRATION* ) 14 CFM 102.6 Btu/Hr/CFM 1,472 1 1 TOTAL: 6,902 VENTILATION** 160 !CFM 102.61Btu/Hr/CFM ! 16,4161 1 j TOTAL 23,318 1HEAT GAIN ISENS. LATENT (TOTAL ROOF I 0 S.F. 0.921Btu/Hr/S.F. - - DOORS IS&W 0 " j 1001 " j - - DOORS IN&E 0 1" 91 " - - WINDOWS S&W 0 " 1001 " - - WINDOWS N 70 " 91 " i 630 630 WINDOWS E 0 60 " j ( , - i - WALLS ;S&W j 145 " 1.91 1 276 276 WALLS 1N 143 1" 0.81 " 114 114 WALLS ,E 0 0.81 " - - LIGHTS 1 405 I" 3.4151*** 1,383 1,383 EQUIPMENT 0 1KW 34151Btu/kw j r - j - OCCUPANTS 8 t*"'* 300/300 i 2,400 2,400 4,800 INFILTRATION 14 !CFM ! 16/251Btu/hr/CFM 230 1 359 588 VENTILATION ! 160 !CFM 16/251Btu/hr/CFM 2,560 1 4,000 1 6,560 j ;TOTAL: ' 7,592 1 6,759 j 14,351 NOTES: : Infiltration based on 1/4 air changes per hour ' *** Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area 1i 1 ***** Sensible and Latent load- based on light activity unless noted otherwise, 1 Page 1 108 KITCHEN 1 1 McGUIRE RESIDENCE 1 I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1108,109 KITCHEN/DINING i HEIGHT: I 8.5 FLOOR 11 I AREA: 875 (VOLUME: 7,438 OCCUPANTS: 12 1 1 1 HEAT LOSS ELEMENT AREA X 1 MULTIPLIER -- i BTU/HR j ROOF 0 S.F j 2.2IBtu/Hr/S.F j - DOORS 35 571 " 1 1,995 WINDOWS 1 84 " I 57 " 1 4,788 WALLS 1 1 196 " 1 5� " 1 980 { FOUNDATION 0 7.5 - INFILTRATION* 31 CFM 102.6_Btu/Hr/CFM 1 1 3,180 TOTAL: 10,943 VENTILATION** 40 CFM j 102.61 Btu/Hr/CFM I 4,104 TOTAL 15,047 , 1 1 { HEAT GAIN SENS. LATENT TOTAL ROOF 1 0 S.F. j 0.921 Btu/Hr/S.F. ! - - DOORS !S&W 0 1001 - ! - DOORS N&E 35 1" 1 91 i 315 315 WINDOWS S&W 0 1" 1001 " 1 - - WINDOWS N 84 1" 91 " I 756 756 WINDOWS E 0 601 " - ! - WALLS 1 S&W 0 I" 1.91 " 1 - - WALLS ,N 196 0.8j " 1 157 157 WALLS E 0 0.8 i - - LIGHTS 1 j 875 1" 3.4151*** j 2,988 2,988 EQUIPMENT 2 1KW , 3415[Btu/kw ! 6,830 ! 1 6,830 OCCUPANTS 2 **** ! 300/3001 600 600 1,200 INFILTRATION 31 1 CFM 16/25(Btu/hr/CFM 496 j 775 1,271 1 1TOTAL: { 12,142 1,375 13,516 VENTILATION 40 1 CFM 16/25{Btu/hr/CFM 11 640 ! 1,000 i 1,640 1 TOTAL: 12,782 I 2,375 I 15,156 NOTES: Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot � I 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area 1 Sensible and Latent load-based on light activity unless noted otherwise! 1 Page 1 111 FAMILY 1 I 1 McGUIRE RESIDENCE 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1111 FAMILY 1 1 !HEIGHT: 8.5 FLOOR 1 11 1 (AREA: 600 ,VOLUME: 5,100 OCCUPANTS: 14 1 ,HEAT LOSS ELEMENT AREA] X MULTIPLIER j= BTU/HR ROOF 1 0 IS.F ' 2.21Btu/Hr/S.FI 1 - 1 DOORS 1 0 1" 57 " 1 - WINDOWS 150 I 57 , 8,5501 1 WALLS 1 1 190 5 " 1 1 950 1 I FOUNDATION 0 1 7.51 " I - INFILTRATION* 21 CFM 102.6jBtu/Hr/CFM I 2,180 1. 1 I 1 !TOTAL: 11,680 VENTILATION** 80 1CFM 102.6 I Btu/Hr/CFM I 8,2087 I 11 1 fi !TOTAL 19,888! ! r 1 I iHEAT GAIN SENS. LATENT !TOTAL ROOF 0 1S.F. 0.92 Btu/Hr/S.F. - - DOORS 1 S&W 0 1" 100 " ' I - 1 - DOORS 1N&E 0 !" 9 " - - WINDOWS S&W 0 1" 100 " 1 - - WINDOWS N 1 90 " 9 810 ! 810 WINDOWS E i 60 601 " 3,600 i 3,600 WALLS 1 S&W 0 " 1.91 " 1 ! - - WALLS 'N 190 ' 0.81 " 152 152 WALLS !E 0 0.81 " j - j - LIGHTS 600 3.4151*** j 2,049 1 2,049 EQUIPMENT 0 IKW 34151Btu/kw - - OCCUPANTS 4 1**** 300/3001 1,200 1,200 2,400 INFILTRATION 21 CFM 16/251Btu/hr/CFM 340 531 871 TOTAL: j 8,151 1,731 1 9,882 VENTILATION 80 !CFM 16/25!Btu/hr/CFM j 1,280 1 2,000 j 3,280 TOTAL: 9,431 1 3,731 1 13,162 NOTES: Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry "'Occupants normally in continuous use of area 1 Sensible and Latent load-based on light activity unless noted otherwise 1 1 Page 1 112 STAIRS 1 1 1 McGUIRE RESIDENCE I 1 1 ! HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES 1 ROOM: 1112 STAIRS 1 1 HEIGHT: 1 8.5 FLOOR 1 AREA: 1 225 1VOLUME:; 1,913 OCCUPANTS: 10 j HEAT LOSS i ELEMENT AREA; X MULTIPLIER = BTU/HR ROOF j 0 !S.F 2.2jBtu/Hr/S.F - DOORS 1 0 571 " 1 - WINDOWS 36 " 571 " 2,052 WALLS 1 219 " 5 " 1 1,095 FOUNDATION 0 7.5 - INFILTRATION* 8 CFM 102.6 Btu/Hr/CFM 818 1 1 TOTAL: 3,965 VENTILATION** 0 CFM I 102.6 Btu/Hr/CFM 1 1 j TOTAL I 3,965 j 1 1 I I 1 HEAT GAIN 'SENS. LATENT 1TOTAL ROOF 0 S.F. i 0.92 Btu/Hr/S.F. - 1 - DOORS 1S&W 1 0 " 1001 " ! I - i j - DOORS IN&E 0 91 " 1 1 - - WINDOWS S&W 36 " 1001 " I ! 3,600 ; 3,600 WINDOWS N 0 1" 9j " j - - WINDOWS E 0 1 60! " - - WALLS 1 S&W 219 I" 1.91 " I 416 416 WALLS IN 1 0 1" 0.81 " 1 - - WALLS 1E 7 1 0 1 0.81 1 - - LIGHTS i 1 0 1" 3.4151*** 1 - - EQUIPMENT 0 KW 34151Btu/kw 1 - - OCCUPANTS 0 1**** 1 300/3001 1 - - - INFILTRATION 8 i CFM 1 16/251Btu/hr/CFM 128 199 327 ( 1 TOTAL: 1 4,144 1991 4,343 VENTILATIONi 0 1CFM 16/25IBtu/hr/CFM - - - 1 TOTAL: ( 4,144 I 199 I 4,343 NOTES: 1 Infiltration based on 1/4 air changes per hour ', ***Lighting heat gain based on 1 watt per square foot 1 1 , **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ', ****Occupants normally in continuous use of area Sensible and Latent load- based on light activity unless noted otherwise: Page 1 113 GARAGE I1 i McGUIRE RESIDENCE 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 113 GARAGE I I HEIGHT: ! 8.5 FLOOR 1 ;AREA: ' 1152 VOLUME: 9,792 OCCUPANTS: 0 HEAT LOSS 1 ELEMENT AREA I X MULTIPLIER = 1 BTU/HR ROOF I 0 S.F 2.2 Btu/Hr/S.F - DOORS 1 227 " 57 " i 12,939 WINDOWS 60 57 " I 3,420 WALLS 469 1 5 " 2,345 FOUNDATION 352 7.5 " I 2,640 INFILTRATION* 1 41 CFM 102.6 Btu/Hr/CFM I 1 4,186 1 I TOTA L: 25,530 VENTILATION** 0 'CFM I 102.6 Btu/Hr/CFM - TOTAL 25,530 1 I ! I I !HEAT GAIN I SENS. LATENT TOTAL ROOF i 0 S .F. 0.92 Btu/Hr/S.F. - - DOORS iS&W j 0 100 " i - � - DOORS N&E 0 "' 9 " ' 1 - I I - WINDOWS S&W ! 0 j 100 " I 1 - I - WINDOWS N 0 " 97 " - I - WINDOWS E 0 I 601 " - ! - WALLS S&W 0 1" 1.9 " I - 1 - WALLS !N ' 0 " 0.81 I i - - WALLS E 0 0.81 " j - - LIGHTS 0 I" 3.4151*** ! - • - EQUIPMENT 1 0 !KW 34151Btu/kwI - 1 - I OCCUPANTS I 0 i**** I 300/3001 INFILTRATION -0 CFM 16/25IBtu/hr/CFM I - - I I ;TOTAL: , - - - VENTILATION 0 CFM 16/251Btu/hr/CFM 1 i - - - 1 1 ;TOTAL: ' - - � - NOTES: Infiltration based on 1/4 air changes per hour I ***Lighting heat gain based on 1 watt per square foot I I **Ventilation based on 2 CFM per S.F. Bathroom or Laundry • ****Occupants normally in continuous use of area Sensible and Latent load- based on light activity unless noted otherwise! • Page 1 114 BATHROOM j McGUIRE RESIDENCE 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I ROOM: 1114 BATHROOM 1 1 1 1 ;HEIGHT: 8.5 1 FLOOR 1 1 I AREA: 25 (VOLUME:! 213 OCCUPANTS: ;0 i 1 1 ' HEAT LOSS ELEMENT AREA X IMULTIPLIER i= BTU/HR ROOF 0 S.F 221Btu/Hr/S.F - DOORS 0 " 57 - WINDOWS I 0 57 " - WALLS 40 1" 51 " I 200 FOUNDATION 0 7.51 " 1 - INFILTRATION* ! 1 1CFM 102.6 Btu/Hr/CFM I 91 j 1 I I 1 TOTAL: 291 VENTILATION** 1 50 CFM ! 102.6 Btu/Hr/CFM 5,130 i I TOTAL 5,421 1 ; !I ;HEAT GAIN ;SENS. LATENT TOTAL ROOF 1 0 S.F. 0.921Btu/Hr/S.F. - - DOORS I S&W 0 " 100 " I 1 - - DOORS 1N&E 1 0 " 91 " 1 - - WINDOWS S&W 1 0 " 1001 " ! - I - WINDOWS N 0 I" 91 " 1 j - - WINDOWS E 1 0 1 601 " 1 i - - WALLS 1 S&W 40 1.91 j ! 76 i 76 WALLS IN 0 " j 0.81 " 1 { 1 - - WALLS IE 1 0 0.81 " r L - 1 - LIGHTS j 25 1" j 3.4151*** I i 85 1 1 85 EQUIPMENT 0 KW 3415iBtu/kw - 1 - OCCUPANTS 0 **** 300/3001 1 - - INFILTRATION 1 CFM 16/251Btu/hr/CFM 14 22 36 VENTILATION 50 FCFM 16/251Btu/hr/CFM 800 1,250 j 2,050 1 ! ;TOTAL: , 976 I 1,272 I 2,248 NOTES: i j Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry i ****Occupants normally in continuous use of area i j i Sensible and Latent load-based on light activity unless noted otherwise; Page 1 116 PANTRY 1 I McGUIRE RESIDENCE j 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1116 PANTRY I HEIGHT: 8.5 FLOOR 1 1! AREA: 120 VOLUME: 1,020 OCCUPANTS: 10 I 1 HEAT LOSS ELEMENT T AREA X MULTIPLIER = BTU/HR ROOF I 0 I S.F 257 IBtu/Hr/S.FI DOORS 0 1 - WINDOWS 20 1" i 57 " f 1,140 WALLS j 116 5 " 1 580 FOUNDATION I 0 7.5 - ' INFILTRATION* 1 4 ,CFM 102.6 Btu/Hr/CFM 436 1 ' I TOTAL: 2,156 VENTILATION** 0 1CFM 102.6 Btu/Hr/CFM 1 - j TOTAL 2,156 1 1 j HEAT GAIN 1SENS. LATENT TOTAL ROOF f 0 S.F. 1 0.92 Btu/Hr/S.F. 1 - - DOORS S&W 0 " 1001 ! 1 - - DOORS I N&E 0 " 91 " l - - WINDOWS S&W 20 " I 100! 1 1 2,000 2,000 WINDOWS N 0 " 91 " 1 - I - WINDOWS E 0 60! " 1 - I - WALLS !S&W ; 116 1.91 " 220 220 WALLS IN 0 0.81 i - - WALLS IE 0 1 0.81 " - I - LIGHTS 1 120 3.4151*** I 410 I 410 EQUIPMENT 0 KW 3415$Btu/kw - - OCCUPANTS 0 1**** 1 300/300! I - 1 - - I INFILTRATION 4 1CFM 16/25jBtu/hr/CFM 68 1061 174 I TOTAL: 2,698 106 2,804 VENTILATION 0 1CFM 16/251Btu/hr/CFM - 1 - - I 1 1 !TOTAL: j 2,698 1 106 j 2,804 NOTES: ; , 1 Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry I ` ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise! • Page 1 117-118 STAIR 1 1I McGUIRE RESIDENCE 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: ,117,118 STAIRWAY i HEIGHT: 8.5 FLOOR 1. I AREA: 198 VOLUME:- 1,683 OCCUPANTS: 0 I I HEAT LOSS ELEMENT I AREA X MULTIPLIER = BTU/HR ROOF 1 0 IS.F 1 2.2 Btu/Hr/S.F - DOORS I 0 '" 1 57 " - I WINDOWS 15 " 57 " 855 WALLS 1 168 I" i 5 " 840 FOUNDATION 0 7.5 I - INFILTRATION* 7 CFM 102.6 Btu/Hr/CFM 719 TOTAL: 2,414 VENTILATION** 0 CFM 102.6 Btu/Hr/CFM 1 - I TOTAL 2,414 1 _ I HEAT GAIN SENS. LATENT TOTAL ROOF 0 S.F. I 0.92 Btu/Hr/S.F. - - DOORS S&W 0 " 100 " T - - DOORS 1N&E 0 9 " l - - WINDOWS S&W ! 15 100 " i 1,500 1 1,500 WINDOWS N 0 " 9+ " - WINDOWS E ! 0 601 11 1 - I - WALLS I S&W 168 1.9 1 319 1 319 WALLS N 0 " 0.8, " ( I - ! - WALLS 1E 0 1 0.8 " - - LIGHTS 1 198 �" 3.4151*** 1 676 676 EQUIPMENT 0 IKW 3415 Btu/kw - i - OCCUPANTS 0 I**** 300/300 - I - ? - INFILTRATION 7 1C FM 16/251Btu/hr/CFM 112 1 175 1 288 1 TOTAL: I 2,608 1 175 ' 2,783 VENTILATION I 0 ICFM 16/25 Btu/hr/CFM - 1 - - I TOTAL: 2,608 , 175 I 2,783 NOTES: Infiltration based on 1/4 air changes per hour **Lighting heat gain based on 1 watt per square foot �� **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area I 1 Sensible and Latent load- based on light activity unless noted otherwise) I I Page 1 120 BATHROOM 1 I McGUIRE RESIDENCE 1 i 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1120 BATHROOM 1 1 'HEIGHT: I 8.5 FLOOR 1 11 1 F AREA: 1 35 'VOLUME: 298 OCCUPANTS: 10 I 1HEAT LOSS ELEMENT AREA X MULTIPLIER I— !— (BTU/HR ROOF 0 S.F 1 2.21Btu/Hr/S.FI 1 - DOORS 0 " i 57! " i 1 - WINDOWS 1 70 I" 1 571 " I f 3,990 WALLS I I 60 51 " 300 FOUNDATION 0 7.51 '' 1 , i - INFILTRATION* 1 1CFM 102.6 Btu/Hr/CFM j 127 I TOTAL: 4,417 VENTILATION** I 70 CFM 102.61Btu/Hr/CFM 7,182 I 1 (TOTAL 11,599 ! I1 HEAT GAIN SENS. LATENT TOTAL ROOF 1 1 0 1S.F. 1 0.92 Btu/Hr/S.F. - - DOORS 1S&W 0 " 1001 DOORS N&E 0 1" 9 " 1 - - WINDOWS S&W 0 100 I - WINDOWS N 0 " 9 " - - WINDOWS E 1 0 60f " i - - WALLS 1 S&W 1 60 " 1.9 " I j 114 1 114 WALLS ;N 1 0 !" 0.81 - 1 - WALLS E 0 0.81 " I - - LIGHTS 35 1" 3.4151*** t 120 120 EQUIPMENT 0 ;KW 34151Btu/kw - - OCCUPANTS 0 **** 300/3001 I 1 - 1 - INFILTRATION 1 CFM 16/251Btu/hr/CFM 20 31 51 VENTILATION 1 70 1 CFM 16/251 Btu/hr/CFM 1,120 1,750 2,870 TOTAL: 1 1,373 i 1,781 3,154 NOTES: 1 Infiltration based on 1/4 air changes per hour 1 *** Lighting heat gain based on 1 watt per square foot j **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 ****Occupants normally in continuous use of area 1 . j Sensible and Latent load- based on light activity unless noted otherwisei Page 1 202-202 STAIRS-HALL j I 1 McGUIRE RESIDENCE HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1201/202 STAIRS/HALL 1 j HEIGHT: 8.5 FLOOR 1 2� j AREA: 288 VOLUME: 2,448 OCCUPANTS: 0 1 j 1 IHEAT LOSS ELEMENT AREA X 'MULTIPLIER 1= 'BTU/HR ROOF 1 288 IS.F 2.21Btu/Hr/S.F' 634 DOORS j 0 " 57 " i - WINDOWS 35 1 57; " 1 1,9951 WALLS 1 101 " j 51 " 1 505 FOUNDATION 0 1 7.51 " 1 - INFILTRATION* 10 ICFM 1 102.6 Btu/Hr/CFM 1,047 1 (TOTAL: 4,180 VENTILATION** 0 CFM 102.6JBtu/Hr/CFM j - 1 I I I TOTAL 4,180 I I 1 ! ! HEAT GAIN ;SENS. LATENT TOTAL ROOF 288 S.F. 0.92!Btu/Hr/S.F. j 265 265 DOORS !S&W j 0 " j 1001 " - - DOORS 1N&E 1 0 " 91 " - 1 - WINDOWS S&W 1 35 i" ' 1001 " I 3,500 3,500 WINDOWS N 0 " 91 " 1 - ! 1 - WINDOWS E 0 601 " 1 + - ! - WALLS 1 S&W 101 1 1.91 " 192 1 1 192 WALLS N 0 i" 1 0.81 " 1 - i - WALLS ,E 0 1 O.Si " - - i LIGHTS 1 1 0 " 3.4151*** j - - EQUIPMENT 0 1KW 34151Btu/kw jI - - j OCCUPANTS i 0 **** 300/3001 1 - - - INFILTRATION 10 jCFM 16/25iBtu/hr/CFM 163 255 418 1 1 TOTAL: 4,120 j 255 4,375 VENTILATION 0 (CFM 16/25iBtu/hr/CFM - - - • 1TOTAL: 4,120 255 I 4,375 NOTES: Infiltration based on 1/4 air changes per hour *** Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 1 ****Occupants normally in continuous use of area *****Sensible and Latent load- based on light activity unless noted otherwisei Page 1 203 HALLWAY j 1 ! McGUIRE RESIDENCE j HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1203 HALLWAY I !HEIGHT: 8.5 1 FLOOR 2 j j AREA: 207 (VOLUME:! 1,760 OCCUPANTS: 0 HEAT LOSS ELEMENT AREA X MULTIPLIER 1= BTU/HR ROOF j 207 S.F ! 2.21Btu/Hr/S.FI 455 DOORS 1 0 57 " 1 - j WINDOWS 48 " 57 " 1 2,7361 WALLS ) j 114 j 5 " 1 570 FOUNDATION 0 7.5 " 1 - INFILTRATION* I 7 CFM j 102.6 Btu/Hr/CFM 1 752 j I TOTAL: 4,514 VENTILATION** 0 CFM 102.6 Btu/Hr/CFM - l 1 j TOTAL 4,514 • 1 1 1HEAT GAIN JSENS. LATENT 'TOTAL ROOF j I 207 1S.F. 0.92 Btu/Hr/S.F. 190 1 190 DOORS 'S&W 0 j" i 100 " 1 -- DOORS 1 N&E 0 I 91 0 f - WINDOWS S&W 0 1" 100 " j i - 1 - WINDOWS N 48 " 9 " 432 432 WINDOWS E 0 601 " - - WALLS j S&W 0 1.91 - WALLS IN 114 1" 0.8 " I 91 j 91 WALLSIE 1 0 1 0.8 - LIGHTS 1 0 1" 3.415j*** ? j - _ EQUIPMENT 0 !KW 34151Btu/kw - - OCCUPANTS 0 l**** 300/3001 - - - INFILTRATION j 7 1CFM 16/25iBtu/hr/CFM 117 183 301 1 j ;TOTAL: j 831 183 1,014 VENTILATION 0 ;CFM 1 16/251Btu/hr/CFM - 1 _ - TOTAL: I 831 I 183 I 1,014 NOTES: Infiltration based on 1/4 air changes per hour • ***Lighting heat gain based on 1 watt per square foot 1 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area 1 *****Sensible and Latent load-based on light activity unless noted otherwisei Page 1 204 CLOSET j I McGUIRE RESIDENCE 1 i 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES 1 ROOM: 204 CLOSET I 1 1HEIGHT: 8.5 FLOOR I 21 1 AREA: 96 VOLUME: 816 OCCUPANTS: 10 1 j 1 HEAT LOSS ELEMENT AREA! X MULTIPLIER = BTU/HR ROOF ' 1 96 1S.F 2.2 Btu/Hr/S.F 211 DOORS 0 571 ! - WINDOWS 24 57 I 1,368] WALLS j 78 j 5 " 1 390 11 FOUNDATION I 0 ! 7.51 " I - 1 1 INFILTRATION* 3 1CFM 102.6 Btu/Hr/CFM 349 I 1 ;TOTAL: 2,3181 VENTILATION** 0 ,CFM 102.6lBtu/Hr/CFM 1 - 1 TOTAL 2,318 1 I , 1 , 1 HEAT GAIN SENS. LATENT TOTAL ROOF I 96 S.F.; 0.921Btu/Hr/S.F. 88 88 DOORS 1S&W j 0 t" 1001 - - DOORS 1 N&E 1 0 91 " - - WINDOWS S&W 0 1" 1001 " 1 - I - WINDOWS N 24 I" 91 " 216 1 216 WINDOWS E 0601 " - 1 - WALLS IS&W 0 " 1.91 " - - WALLS IN ! 78 1" 0.81 ! 62 62 WALLS 1E 0 j • 0.81 " j j - ! - LIGHTS 1 0 3.4151*** 1 - j - EQUIPMENT 0 KW 3415jBtu/kw 1 j - 1 - OCCUPANTS 0 I**** 300/3001 - i - - INFILTRATION 3 ;CFM • 16/251Btu/hr/CFM , j 54 1 85 I 139 ITOTAL: 421 1 85 ; 506 VENTILATION 0 !CFM 16/251Btu/hr/CFM - - • - TOTAL: I- 421 r 85 I 506 NOTES: Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ' I ****Occupants normally in continuous use of area 1 Sensible and Latent load-based on light activity unless noted otherwise! , 1 Page 1 205-206 CLOSETS 1 McGUIRE RESIDENCE j HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES 1 ROOM: 1205/206 CLOSETS 1 1 !HEIGHT: 8.5 1 FLOOR 1 21 1 1 (AREA: I 326 iVOLUME:I 2,771 OCCUPANTS: 0 � I I f HEAT LOSS 1 j ELEMENT AREA X jMULTIPLIER 1= 'BTU/HR ROOF 1 326 IS.F 2.2 Btu/Hr/S.FI 717 DOORS 0 " 57 - WINDOWS 35 1" 57 " 1,995 , '' WALLS 305 j" 5 " 1 , 1,525 FOUNDATION 0 7.5 " j - INFILTRATION* 12 CFM 102.6 Btu/Hr/CFM 1,185 j ;TOTAL: 5,422 VENTILATION** j 0 CFM j 102.61Btu/Hr/CFMj - 1 1 TOTAL 5,422 , 1 HEAT GAIN JSENS. (LATENT TOTAL ROOF ! 326 S.F. 0.92 Btu/Hr/S.F. 1 300 300 DOORS jS&W 0 " 1001 - I - DOORS jN&E 0 !" j 9 " 1 - - WINDOWS S&W 0 1" ! 1001 " ! 1 - - WINDOWS N 35 j" j 91 315 315 WINDOWS E 0 1 60 " 1 - - WALLS 1S&W 0 j" i 1.9! - WALLS N 305 I" 0.81 " 1 244 j ! 244 WALLS E 0 i i 0.81 " - - LIGHTS ; 0 1" 3.4151*** j - - EQUIPMENT 0 1KW j 34151Btu/kw Ii - - OCCUPANTS 0 ""'" 1 300/30011 1 - - - INFILTRATION j 12 !CFM 16/25 Btu/hr/CFM 185 1 289 473 1 1 TOTAL: 1,044 j 289 i 1,332 VENTILATION 0 1CFM 16/251Btu/hr/CFM - I - - 1 TOTAL: l 1,044 1 289 1 1,332 NOTES: Infiltration based on 1/4 air changes per hour "" Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry """Occupants normally in continuous use of area 1 i Sensible and Latent load- based on light activity unless noted otherwisei ; 1 Page 1 207 CLOSET 1 1 McGUIRE RESIDENCE 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1207 CLOSET ' I jHEIGHT: j 8.5 FLOOR 1 21 1 1 ;AREA: j 216 VOLUME: 1,836 OCCUPANTS: 0 j I HEAT LOSS ELEMENT I AREA X MULTIPLIER 1= IBTU/HR ROOF 216 1S.F 2.2.Btu/Hr/S.F� 475 DOORS j 0 57 , - WINDOWS 75 1" 57 " , 4,275 WALLS 1 180 5 " 1 1 900 FOUNDATION i 0 7.5 " I - 1 INFILTRATION* I 8 CFM 1 102.6 Btu/Hr/CFM 785_ TOTAL: 6,435 VENTILATION** I 0 CFM 102.6 Btu/Hr/CFM - TOTAL 6,435 1 I HEAT GAIN SENS. LATENT TOTAL ROOF I 216 S.F. 1 0.92 Btu/Hr/S.F. 199 199 DOORS S&W 0 (" 1 1001 " f ! - ) 1 - DOORS N&E 0 91 " - - WINDOWS S&W 50 " 1001 " 5,000 5,000 WINDOWS N 0 I 91 - - WINDOWS E 25 601 1,500 ! 1,500 WALLS 1 S&W I 103 1 1.91 " 196 I 196 WALLS IN 77 ;" j 0.81 " 1 62 62 WALLS 1E • 0 0.81 - 1 - LIGHTS I 1 0 3.4151*** I - - EQUIPMENT 0 jKW 3415 Btu/kw - - OCCUPANTS 0 I**** 300/3001***** - - - INFILTRATION 8 'CFM 16/251Btu/hr/CFM 122 191 314 j TOTAL: 1 7,078 191 7,270 VENTILATION 1 0 1CFM 16/25jBtu/hr/CFM - - - 1 TOTAL: I 7,078 191 7,270 NOTES: I i Infiltration based on 1/4 air changes per hour *** Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise! Page 1 208 MASTER BEDROOM I ! 1 McGUIRE RESIDENCE 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 208 MASTER BEDROOM 1 1HEIGHT: 8.5 FLOOR 21 1i AREA: 510 VOLUME:1 4,335 OCCUPANTS: 0 I I HEAT LOSS I ELEMENT AREA! X MULTIPLIER = BTU/HR ROOF 510 S.F 2.21Btu/Hr/S.F 1,122 DOORS 0 57 " - WINDOWS 48 " 57 " I j 2,736 WALLS 1 114 5 ! 570 FOUNDATION 1 0 1 7.5 1 - INFILTRATION* i 18 CFM 102.6 Btu/Hr/CFM ; 1,853 1 1 I TOTAL: 6,281 VENTILATION** ( 0 CFM 102.61 Btu/Hr/CFM - I 1 I TOTAL 6,281 1 ; 1 i HEAT GAIN SENS. LATENT 'TOTAL ROOF 1 510 S.F. 0.92IBtu/Hr/S.F. 1 469 j 469 DOORS 1 S&W 0 " 1001 " i - - DOORS N&E I 0 j" 91 " - - WINDOWS S&W t 0 1001 " 1 - - WINDOWS N 48 " 91 " 432 432 WINDOWS E 0 60 " - - WALLS IS&W 1 0 " 1.91 " - WALLS 1N 1 114 0.8 " I 91 91 WALLS 1E 0 0.81 " - - LIGHTS f 0 1" 3.4151*** I - - EQUIPMENT 0 1KW 34151Btu/kw 1 1 - - OCCUPANTS 0 **** 300/3001 - - - INFILTRATION 18 CFM 16/25IBtu/hr/CFM 1 289 452 741 I1 1 TOTAL: 1,281 452 • 1,733 VENTILATION ! 0 CFM 16/25TBtu/hr/CFM - - - i TOTAL: 1,281 452 I 1,733 NOTES: , ! i Infiltration based on 1/4 air changes per hour , ***Lighting heat gain based on 1 watt per square foot I **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise Page 1 209 BATHROOM 1 1 McGUIRE RESIDENCE 1 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1209 MASTER BATHROOM 1 .HEIGHT: 1 8.5 FLOOR 1 21 1 'AREA: 1247 VOLUME: 2,100 OCCUPANTS: 0 I _ 1HEAT LOSS ELEMENT AREA X MULTIPLIER = BTU/HR ROOF 1 , 247 1S.F 2.2 Btu/Hr/S.FI 543 DOORS 1 I 0 57 " - WINDOWS 48 " 57 2,736 WALLS 1 114 " 5 " 570 FOUNDATION 0 7.5 " 1 - INFILTRATION* 9 CFM 102.6 Btu/Hr/CFM 1 1 898 1 i j !TOTAL: 4,747 VENTILATION** 494 ;CFM j 102.61Btu/Hr/CFM 50,684 1 TOTAL 55,431 1 - 1 HEAT GAIN 1SENS. LATENT TOTAL ROOF 1 1 247 S.F. 0.92 Btu/Hr/S.F. 1 227 I 227 DOORS 'S&W 0 i 100 - - DOORS 1 N&E 0 " 91 " I j - I - I WINDOWS S&W 0 " 1001 " 1 - - WINDOWS N 48 " 91 " 1 432 432 WINDOWS E 1 0 601 " j - 1 - WALLS 1 S&W 0 I" 1.91 " - - WALLS IN 114 " 1 0.81 91 1 91 WALLS I E 0 1 0.81 " j - j - LIGHTS I 247 1" i 3.4151*** 844 844 EQUIPMENT 0 1KW 1 34151Btu/kw - I - OCCUPANTS 0 '"** 300/3001 ` 1 I ! � - i - INFILTRATION 9 IC FM 16/251Btu/hr/CFM `' j 140 219 359 1 (TOTAL: 1,734 219 1,953 VENTILATION 1 494 1CFM 16/251Btu/hr/CFM I 7,904 12,350 20,254 1 ;TOTAL: l 9,638 12,569 22,207 NOTES: Infiltration based on 1/4 air changes per hour j ***Lighting heat gain based on 1 watt per square foot 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise. j Page 1 210 OFFICE I McGUIRE RESIDENCE I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 210 OFFICE j 1HEIGHT: 8.5 I FLOOR 2 1 !AREA: 178 VOLUME:) 1,513 OCCUPANTS: 0 1 I HEAT LOSS _ I ELEMENT AREA X MULTIPLIER = BTU/HR ROOF 1 178 S.F 2.21 Btu/Hr/S.F1 • 392_ DOORS 1 0 " 57' " 1 - WINDOWS 30 " 57 " 1,710 WALLS 59 5 2951 FOUNDATION 0 7.5 " - INFILTRATION* 6 CFM 102.6 Btu/Hr/CFM 647 1 TOTAL: 3,043 VENTILATION** 0 CFM 102.6 Btu/Hr/CFM - I TOTAL 3,043 1 L HEAT GAIN SENS. (LATENT TOTAL ROOF , 178 S.F. 0.92 Btu/Hr/S.F. 164 164 DOORS 1S &W 0 100 " 1 - - DOORS N&E 0 I 91 " I - - WINDOWS S&W 0 " 1001 " - - WINDOWS N 309 " I i 270 270 WINDOWS E 0 60 " - - WALLS !S&W 0 " j 1.91 - - WALLS N 59 1" j 0.8 i 1 I 47 47 WALLS E 0 1 0.8 " - - LIGHTS 1 178 1" 3.415 *** r 608 608 EQUIPMENT 0 KW 3415fBtu/kw - i ! - OCCUPANTS I 0 **** C 300/300! ! - I - - INFILTRATION 6 CFM 1 16/25 Btu/hr/CFM 101 j 158 258 I 1 I ; ITOTAL: 1,190 158 1,347 VENTILATION 0 1CFM 1 16/25-Btu/hr/CFM 1 ( - ! - - 1 I I !TOTAL: 1,190 158 I 1,347 NOTES: 1 I 1 _ Infiltration based on 1/4 air changes per hour 1 ***Lighting heat gain based on 1 watt per square foot 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry j 1 ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise! Page 1 211 BATHROOM McGUIRE RESIDENCE 1 I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I ROOM: 211 BATHROOM ! , , !HEIGHT: 8.5 j FLOOR I 21 1 I , ;AREA: 1 132 'VOLUME: 1,122 OCCUPANTS: 10 1 j C1 1 1 HEAT LOSS 1 1 ELEMENT AREA! X MULTIPLIER 1= BTU/HR ROOF 1 132 S.F j 2.21Btu/Hr/S.FI 290 ' DOORS ; 0 i" 571 " I - WINDOWS 18 " 57 " I 1 1,026 WALLS 1 33 !" 5 " ! 165 FOUNDATION 0 ! j 7.5 " I - INFILTRATION* 5 rCFM CFM 102.6 Btu/Hr/CFM 480 !TOTAL: 1,961 VENTILATION** 264 CFM 102.6 Btu/Hr/CFM 1 27,086 : ! !TOTAL 29,047 i I 1 t, HEAT GAIN } ISENS. LATENT TOTAL ROOFROOF 1 132 S.F. 0.921Btu/Hr/S.F. 121 121 DOORS S&W 0 " 100 " I 1 J - - DOORS IN&E 0 I" 91 - ! j - WINDOWS S&W 0 �" 1001 " I - - WINDOWS N 18 I" 91 " I 1 162 162 WINDOWS E 0 1 1 601 " ii - - WALLS IS&W 1 0 1.91 " 1 - - WALLS N 33 1" 0.81 I 26 26 WALLS jE 0 0.81 I - I 1 - LIGHTS i 132 I" 3.4151*** 451 451 EQUIPMENT 0 1KW 3415!Btu/kw - - OCCUPANTS 0 !**** I 300/30011 - - - i INFILTRATION 5 ;CFM 16/251Btu/hr/CFM 75 !. 117 I 192 1 !TOTAL: 1 835 117 1 952 VENTILATION ; 264 ICFM I 16/251Btu/hr/CFM 1 1 4,224 6,6001 10,824 j 1 !TOTAL: 5,059 I 6,717 I 11,776 NOTES: Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry "—Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwisel Page 1 212 BEDROOM 1 1 McGUIRE RESIDENCE 1 i j 1 I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 212 BEDROOM 1 I !HEIGHT: 8.5 FLOOR 2 i 1 1 'AREA: 324 t1VOLUME:i 2,754 OCCUPANTS: 0 1 1 HEAT LOSS ELEMENT AREA X MULTIPLIER = BTU/HR ROOF 324 S.F 2.2 Btu/Hr/S.F 713 DOORS 0 " 57 " 1 - WINDOWS 94 " I 57 " I1 5,358 WALLS i I 229 I" 1 5 " 1 i 1,145 FOUNDATION 0 1 7.51 " I 1 - INFILTRATION* 11 fCFM 102.6 Btu/Hr/CFM J 1 1,177 I i TOTAL: r 8,393 VENTILATION** 0 CFM 102.6 Btu/Hr/CFM - ITOTAL 8,393 1 i I j HEAT GAIN !SENS. LATENT TOTAL ROOF 324 S.F. 0.92 Btu/Hr/S.F. 298 298 DOORS 1S&WI 100 l - - DOORS i N&E j 00 1" 91 " j - - WINDOWS S&W 14 1" 1001 " 1,400 j 1,400 WINDOWS N 80 " 91 " E i 720 1 720 WINDOWS E 0 601 " 1 ! - - WALLS S&W 88 j" 1.91 " 1 167 j 167 WALLS IN 141 " 0.81 1 113 113 WALLS 1E j 0 j 0.8 " 1 - - LIGHTS 0 ," 3.415 *** 1 - - EQUIPMENT 0 KW 34151Btu/kw 1 L 1 - - OCCUPANTS 0 **** 300/3001 - - - INFILTRATION 11 ;CFM 16/251Btu/hr/CFM j 184 287 : 470 ' TOTAL:1 2,882 287 3,169 VENTILATION 0 CFM 16/251Btu/hr/CFM - - - 1 TOTAL: I 2,882 [ 287 I 3,169 NOTES: , 1 Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot I I 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 , ****Occupants normally in continuous use of area *****Sensible and Latent load-based on light activity unless noted otherwise! Page 1 213 BEDROOM j 1 1 McGUIRE RESIDENCE I i , I 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I ROOM: 1213 BEDROOM, 1 1 1 1_HEIGHT: 8.5 FLOOR ! 21 1 iI 1 1AREA: 195 !VOLUME: 1,658 OCCUPANTS: 10I 1 1 I 1 !HEAT LOSS ELEMENT AREA X MULTIPLIER 1= BTU/HR ROOF j 195 'S.F 2.2IBtu/Hr/S.FI 429 i DOORS 1 0 " 571 " 1 i - 1 WINDOWS 35 " 571 " i 1,9951 WALLS 93 " j 5` " 1 I 465 1 FOUNDATION 0 7.5 " INFILTRATION* 7 CFM 1 102.61Btu/Hr/CFM I 7091 i TOTAL: 3,598) VENTILATION** 0 CFM ( 102.6 Btu/Hr/CFM 1 - 1 I ITOTAL 3,598 1 1 HEAT GAIN SENS. (LATENT (TOTAL ROOF 195 1S.F. 0.92 Btu/Hr/S.F. 1 179 I 179 DOORS IS&W 0 1" 1001 " 1 - 1 DOORS N&E 0 H 91 " ! , - - WINDOWS S&W 35 " 1 1001 " j 1 3,500 1 3,500 WINDOWS N 0 91 " - - WINDOWS E 0 601 " _ I - WALLS 1S&W 93 j 1.91 " 177 ; 177 WALLS IN 0 H 0.81 " - - WALLS 1E 0 0.81 " - i,1 , - LIGHTS I 1 0 I" I, 3.415*** - , - EQUIPMENT 0 1KW 34151Btu/kw ; - 1 i - OCCUPANTS 0 I**** 300/3001 1 - i - INFILTRATION 7 ;CFM 1 16/251Btu/hr/CFM 111 ! 173 283 11 1TOTAL: 3,9671 1731 4,139 VENTILATION 0 (CFM j 16/251Btu/hr/CFM 1 - 1 - I - TOTAL: ` 3,967 I 173 I 4,139 NOTES: Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area 1 Sensible and Latent load-based on light activity unless noted otherwisei Page 1 215 BATHROOM { � McGUIRE RESIDENCE HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES r ROOM: 1215 BATHROOM j HEIGHT: I 8.5 FLOOR 21 1 i I AREA: 105 1VOLUME: 893 OCCUPANTS: 01 1 1 HEAT LOSS ELEMENT AREA$ X MULTIPLIER 1= BTU/HR j ROOF 1 105 IS.F 2.2 Btu/Hr/S.F 231 DOORS 1 0 " 57 " 1 - WINDOWS 15 57 1 855 WALLS 1 i 28 1" 5 140 FOUNDATION 0 7.5 - INFILTRATION* 4 CFM 1 102.6 Btu/Hr/CFM 1 382 , 1 `TOTAL: 1,608 VENTILATION** 1 210 CFM 102.61Btu/Hr/CFM j 21,5461 ( TOTAL 23,154) ' I 1 (HEAT GAIN SENS. LATENT 1TOTAL ROOF 1 105 1S.F. 0.92 Btu/Hr/S.F. 97 97 DOORS S&W 0 I" I 1001 " I $ - - DOORS 1N&E 1 0 " 9$ " j - - i WINDOWS S&W 0 1" 1 1001 I1 1 - - WINDOWS N 15 �" 9 " 1 j 1 135 135 WINDOWS E • 0 1 601 " i - - WALLS 1 S&W 0 1.91 1 - - WALLS N 28 0.81 " 22 22 WALLS 1 E 0 1 0.81 " I - 1 - LIGHTS I 105 ! 3.4151*** 1 359 359 EQUIPMENT 1 0 1KW 34151Btu/kw L - - OCCUPANTS 0 '**** i 300/300$ INFILTRATION 4 ;CFM 16/251Btu/hr/CFM 60 93 152 , 1TOTAL: 1 672 93 765 VENTILATION 210 CFM 16/25 Btu/hr/CFM 3,360 5,250 8,610 TOTAL: 4,032 I 5,343 I 9,375 NOTES: Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry : **** Occupants normally in continuous use of area 1 !1 Sensible and Latent load-based on light activity unless noted otherwise) Page 1 216 SEWING ' I 1 McGUIRE RESIDENCE I j HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES + ROOM: 1216 SEWING I ! j 'HEIGHT: 8.5 FLOOR 2 AREA: 99 VOLUME: 842 OCCUPANTS: 0 j HEAT LOSS ELEMENT AREA X MULTIPLIER = I BTU/HR ROOF ! 99 S.F 2.21Btu/Hr/S.F 218 ` DOORS 0 " 57111 ! - 1 WINDOWS 25 57 " I 1,425 i WALLS j 60 " ! 5 " I ! 3001 FOUNDATION 0 7.5 " - INFILTRATION* ! 4 CFM 102.6 Btu/Hr/CFM 1 360 j j TOTAL: 2,303 VENTILATION** 0 CFM 102.61 Btu/Hr/CFM 1 - I I !TOTAL 2,303 1 1 I !HEAT GAIN SENS. LATENT 'TOTAL ROOF 99 S.F. i 0.92 I Btu/Hr/S.F. I 91 91 DOORS S&W 0 !" 1001 I - i - DOORS 1N&E 0 1" 91 - ) - WINDOWS S&W 0 " 1 1001 " - I - WINDOWS N 25 " 91 " 225 1 225 WINDOWS E 0 1601 " - 1 - WALLS S&W 0 !" j 1.91 " - WALLS N 60 (" ! 0.81 " ! I 48 1 48 WALLS E 0 0.81 LIGHTS 1 99 3.4151*** I 1 338 338 EQUIPMENT 0 1KW 34151Btu/kw 1 - i - OCCUPANTS 0 **** 300/3001 j - INFILTRATION 1 4 CFM 16/251Btu/hr/CFM j 56 : 88 ! 144 I � I 1 ITOTAL: 758 88 ; 846 VENTILATION I 0 CFM 16/25 Btu/hr/CFM 1 I - - - 1TOTAL: L 7581 881 846 NOTES: I I i Infiltration based on 1/4 air changes per hour 1 ***Lighting heat gain based on 1 watt per square foot ! 1 j 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry j 1 i ****Occupants normally in continuous use of area I ! 1 Sensible and Latent load-based on light activity unless noted otherwisei j Page 1 217 BATHROOM • j McGUIRE RESIDENCE j HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1217 BATHROOM j i HEIGHT: ' 8.5 FLOOR 21 !AREA: 176 VOLUME:! 1,496_ OCCUPANTS: 0 , j HEAT LOSS ELEMENT L AREA X MULTIPLIER = BTU/HR ROOF I 176 S.F I 2.2IBtu/Hr/S.F 387 DOORS t 0 " 57i " I - WINDOWS 40 I 57 „ 2,280 WALLS 96 5 i j 480 FOUNDATION 0 7.51 " j - INFILTRATION* 6 CFM 102.6 Btu/Hr/CFM 640 TOTAL: 3,787 VENTILATION** 352 CFM 102.6 Btu/Hr/CFM 1 36,115 TOTAL 39,902 I HEAT GAIN 1 SENS. LATENT TOTAL ROOF i 176 1S.F. 0.921Btu/Hr/S.F. 162 1 162 DOORS S&W ! 0 I" I 1001 u 1 - — DOORS N&E 0 1" 91 1 - - WINDOWS S&W ! 0 " 1001 " - WINDOWS N ! 40 91 " 360 360 WINDOWS E 0 601 " - j I - WALLS S&W 0 1.9 " - 1 - WALLS IN 96 1 0.81 " f 77 { 77 WALLS 1E ! 0 1 0.81 " - - LIGHTS I 176 1" 3.4151*** 601 i 601 EQUIPMENT 1 0 !KW 34151Btu/kw I ! - - OCCUPANTS 0 I**** ! 300/3001 - - - INFILTRATION 1 6 !CFM 16/251Btu/hr/CFM 1 100 156 1 256 1 I 1 TOTAL: 1,299 156 1,455 VENTILATION 352 ICFM 16/25,Btu/hr/CFM 5,632 8,800 14,432 1 1 TOTAL: I 6,931 8,956 I 15,887 NOTES: 11 I Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot 1 j j **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area 1 ) 1 Sensible and Latent load-based on light activity unless noted otherwise 1 Page 1 218 BEDROOM I McGUIRE RESIDENCE I 1 I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: ,218 BEDROOMHEIGHT: 8.5 FLOOR 21 , AREA: 324 VOLUME: 2,754 OCCUPANTS: 0 1 I 1 I HEAT LOSS ELEMENT AREA X MULTIPLIER I= BTU/HR ROOF ( 324 S.F 2.2 Btu/Hr/S.F 713 DOORS 0 " 57 " - WINDOWS 50 571 " 2,850I WALLS r 163 5 " 815 FOUNDATION 0 7.5 " - INFILTRATION* 11 CFM 102.6 Btu/Hr/CFM 1,177 TOTAL: 5,555] VENTILATION** 0 CFM 102.61Btu/Hr/CFM - 1 TOTAL 5,555 !HEAT GAIN 1SENS. LATENT TOTAL ROOF ROOF 324 S.F. 0.92IBtu/Hr/S.F. 298 298 DOORS S&W 0 II _ - 100 " - DOORS IN&E 0 I" 9 " - - WINDOWS S&W 0 1001 " I - - WINDOWS N j 50 " 91 " ! 450 450 WINDOWS E 0 601 " I - I - - WALLS S&W0 1.91 , - - �., WALLS N j 163 I' j 0.8 130 130 WALLS 1E 1 0 i 1 0.8 I - LIGHTS ! 0 " 3.415 *** I - - EQUIPMENT ( 0 KW I 3415 Btu/kw - - OCCUPANTS 1 0 **** 1 300/3001 I - - - INFILTRATION 11 CFM 16/25IBtu/hr/CFM 184 287 470 I I j I TOTAL: I 1,062 287 1,349 VENTILATION 0 CFM I 16/251Btu/hr/CFM - 1 - - 1 TOTAL: J 1,062 I 287 I 1,349 NOTES: • Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot ! **Ventilation based on 2 CFM per S.F. Bathroom or Laundry I 1 ****Occupants normally in continuous use of area 1 ! I Sensible and Latent load-based on light activity unless noted otherwise Page 1 219 CLOSET McGUIRE RESIDENCE 1 1 j HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES i , ROOM: X219 CLOSET 1 1 i HEIGHT: 8.5 FLOOR 21 j (AREA: 1 171 VOLUME:. 1,454 OCCUPANTS: 0 j I HEAT LOSS j ELEMENT AREA! X MULTIPLIER 1= j iBTU/HR ROOF 1 171 S.F ! 2.2 Btu/Hr/S.Fj 376 1 . DOORS 1 0 �" 57 " 1 � - WINDOWS 0 " 57 " j 1 - WALLS 77 i" 5 " 385 FOUNDATION 0 7.5 " 1 - INFILTRATION* 6 CFM 102.61 Btu/Hr/CFM 621 TOTAL: 1,383 I VENTILATION** 0 CFM 102.6Btu/Hr/CFM 1 - TOTAL 1,383 I !HEAT GAIN SENS. LATENT jTOTAL ROOF 1 171 S.F. 0.92IBtu/Hr/S.F. I 157 157 DOORS 'S&W 0 I" 1001 " ' - 1 - DOORS N&E 0 j" 91 " 1 - - WINDOWS S&W 0 " 100] " - - WINDOWS N 0 I" 9 " 1 - - WINDOWS E 0 601 I i - - WALLS S&W 0 I" 1.91 " i - - WALLS rN 1 77 1" 0.81 " i 62 ! 62 WALLS ,E 0 0.81 " - 1 - LIGHTS 1 i 0 1 3.415i*** { - - EQUIPMENT 0 !KW 3415iBtu/kw , - I - OCCUPANTS 1 0 - - - 01**** ' 300/3001 i INFILTRATION 6 ;CFM 16/251Btu/hr/CFM 97 151 248 TOTAL: 316 151 467 VENTILATION 1 0 !CFM 16/251Btu/hr/CFM i - ! - - 1 ;TOTAL: j 316 1 151 467 NOTES: i Infiltration based on 1/4 air changes per hour *** Lighting heat gain based on 1 watt per square foot 1 ! **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area i Sensible and Latent load- based on light activity unless noted otherwise! Page 1 220 STORAGE I 1 1 McGUIRE RESIDENCE j HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 220 STORAGE (HEIGHT: 8.5 FLOOR 2 ` 1 AREA: 450 VOLUME: 3,825 OCCUPANTS: 0 1 HEAT LOSS ELEMENT AREA X MULTIPLIER = ;BTU/HR ROOF 450 S.F I 2.2 Btu/Hr/S.F I I 990 DOORS I 0 " 57 " I - . WINDOWS 75 " 57 " j 4,275 WALLS I 1 445 " 5 " 4 2,225 FOUNDATION 0 1 7.5 " I - INFILTRATION* 16 ,CFM 102.6,Btu/Hr/CFM 1,635 { I ;TOTAL: 9,125 VENTILATION** 0 CFM 102.6 Btu/Hr/CFM I - TOTAL 9,125 I HEAT GAIN ISENS. LATENT TOTAL ROOF ! 450 S.F. I 0.92 Btu/Hr/S.F. 414 414 DOORS I S&W I 0 " 1001 1 - - DOORS I N&E 0 I" 91 - j - WINDOWS S&W I 60 " j 1001 " I 6,000 1 6,000 WINDOWS N 1 15 " 91 " I 135 1 135 WINDOWS E i 0 601 1 - - WALLS S&W 331 1., L 1.91 " 629 629 WALLS IN ! 112 0.81 " I 90 ! 90 WALLS I E 0 0.8' " I I - - ' I I LIGHTS I j 0 " 3.415 *** - I - EQUIPMENT I 0 IKW 34151Btu/kw ! - - OCCUPANTS 0 1**** 300/3001 I - - - INFILTRATION 16 !CFM 1 16/25IBtu/hr/CFM 1 255 I 398 653 I ITOTAL: 1 7,523 398 ' 7,921 VENTILATION I 0 CFM 1 16/25IBtu/hr/CFM I - - - I j TOTAL: 1 7,523 I 398 1 7,921 NOTES: 1 Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot I **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise) I Page 1 221 TOYROOM j 1 I 1 McGUIRE RESIDENCE I 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1221 TOYROOM ! � 1 1 '1 HEIGHT: 8.5 1 FLOOR 1 21 ;AREA: 234 VOLUME:I 1,989 OCCUPANTS: 10 I 1 1 HEAT LOSS 1 ELEMENT AREA I X MULTIPLIER 1= BTU/HR I ROOF I 234 S.F j 2.2 Btu/Hr/S.FI 1 1 515 1 - DOORS 1 0 " 57 " i - WINDOWS 1 30 " 57 " 1 I 1,710 WALLS I 200 1" 1 51 " I 1,000 1 FOUNDATION 0 j 7.51 ' - INFILTRATION* 8 CFM 102.6 Btu/Hr/CFM j 850 I I (TOTAL: 4,075 VENTILATION** 0 CFM 1 102.61 Btu/Hr/CFM 1 I - j 1 I i 1 l ;TOTAL 4,075 1 I 1 HEAT GAIN 1SENS. LATENT TOTAL ROOF F 234 S.F. 0.921Btu/Hr/S.F. i 215 j 215 DOORS jS&W 0 1001 " ', - 1 DOORS j N&E 0 f" 91 " - I - WINDOWS S&W 30 1" 1001 3,000 1 1 3,000 WINDOWS N 0 1" � 91 " - i - WINDOWS E 0 I 601 " , - 1 1 - WALLS 1S&W 200 1.91 " 380380 WALLS iN 0 '" , 0.81 " - - WALLS 1E 0 I 0.81 " I ' - - LIGHTS 0 I" 3.4151*** .. - EQUIPMENT : 0 IKW I 34151Btu/kw i - 1 - OCCUPANTS 0 **** 300/3001 j ' INFILTRATION 8 1 CFM 1 16/251 Btu/hr/CFM 133 1 207 I 340 1 ;TOTAL: 3,728 207 j 3,935 VENTILATION ! 0 1 CFM 16/251 Btu/hr/CFM - - i - ' TOTAL: I 3,728 I 207 I 3,935 NOTES: 1 I Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise 1 Page 1 222 LAUNDRY I I McGUIRE RESIDENCE 1 1 >_ I HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 222 LAUNDRY I I HEIGHT: I 8.5 FLOOR 2! ; AREA: 100 VOLUME:1 850 OCCUPANTS: ip 1 HEAT LOSS ELEMENT 1 AREA! X MULTIPLIER j= BTU/HR ROOF I 100 I S.F 2.2 Btu/Hr/S.F 220 ' DOORS 0 1" 57 " - WINDOWS 30 57 " 1,710 WALLS 1 174 " 1 5 " 870 FOUNDATION 0 I 7.5 I i - i INFILTRATION' 4 CFM 102.6 Btu/Hr/CFM i 363 TOTAL: 3,163 VENTILATION** j 200 CFM 102.6 Btu/Hr/CFM j 20,520 11 I TOTAL 23,683 1 !HEAT GAIN SENS. LATENT TOTAL ROOF ' 100 S.F. 0.92IBtu/Hr/S.F. 1 92 ! 92 DOORS S&W 0 " 1001 " - DOORS N&E 0 1 91 " I - - WINDOWS S&W 30 " 100 " j 3,000 1 3,000 WINDOWS N 0 9 " I - - WINDOWS E 0 1 601 " I - j - WALLS 1S&W 174 1.91 " I 331 1 j 331 WALLS IN 0 j 0.81 " I - - WALLS IE I 0 1 0.81 " - j - LIGHTS , 100 j" 3.415 *** 342 342 EQUIPMENT 0 !KW I 3415�Btu/kw i - i - OCCUPANTS 0 1**** 300/3001***** j ' - - - INFILTRATION 4 CFM 16/251 Btu/hr/CFM 1 57 j 89 145 I !TOTAL: 3,821 89 3,909 VENTILATION 1 200 CFM ! 16/251Btu/hr/CFM 1 I 3,200 ! 5,000 I 8,200 !TOTAL: I 7,021 J 5,089 1 12,109 NOTES: 1 Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot 1 1 **Ventilation based on 2 CFM per S.F. Bathroom or Laundry i ****Occupants normally in continuous use of area Sensible and Latent load-based on light activity unless noted otherwise' Page 1 223 STAIRWAY-HALL 4, 1 McGUIRE RESIDENCE 1 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES ROOM: 1223 STAIRWAY/HALL I 1 HEIGHT: 8.5 FLOOR 2 AREA: 264 'VOLUME: 2,244 OCCUPANTS: 0I HEAT LOSS j ELEMENT AREA X 1MULTIPLIER = IBTU/HR ROOF 264 S.F 2.21 Btu/Hr/S.FI 581 j • DOORS 0 " 57 " 1 - WINDOWS 1 15 p" 57 " 855 WALLS 180 j" 5 " I 900 FOUNDATION 0 7.5 " - INFILTRATION* 9 CFM 102.6 Btu/Hr/CFM 959 I I 1 I TOTAL: 3,295 VENTILATION** 0 CFM 102.61Btu/Hr/CFM 1 - j � TOTAL 3,295 I (HEAT GAIN !SENS. (LATENT 'TOTAL ROOF 264 S.F. 0.921Btu/Hr/S.F. 2431 243 DOORS 1 S&W 0 I" 1001 0 I 1 - - DOORS IN&E j 0 l" 1 91 " - - WINDOWS S&W 15 1" 1001 " L 1 1,500 1,500 WINDOWS N 1 0 1" 91 " I - - WINDOWS E 0 1 601i - 1 - WALLS I S&W 180 1" 1.91 " L I 342 ! 342 WALLS IN 0 1" I 0.81 I I - I - WALLS 1E 0 1 0.81 " I 1 - 1 - LIGHTS '1 1 0 1" 3.4151*** 1 - - EQUIPMENT 0 1 KW 1 3415 Btu/kw 1 - - OCCUPANTS 0 i**** 300/300 1 - - - INFILTRATION 9 1CFM 16/251Btu/hr/CFM ! 150 ; 234 383 1 j 'TOTAL: 2,234 234 � 2,468 VENTILATION i 0 CFM I 16/25IBtu/hr/CFM 1 - 1 - 1 - I !TOTAL: 2,234 I 234 I 2,468 NOTES: , Infiltration based on 1/4 air changes per hour ***Lighting heat gain based on 1 watt per square foot ; **Ventilation based on 2 CFM per S.F. Bathroom or Laundry ****Occupants normally in continuous use of area 1 1 Sensible and Latent load-based on light activity unless noted otherwise! ! ; Page 1