HomeMy WebLinkAbout1997 - 009416 - fuel storage PERMIT
CITY OF ORONO PERMIT TYPE:
2750 Kelley Parkway- P.O. Box 66
Crystal Bay, Minnesota 55323 Permit Number:
(612) 473Date Issued:
-7357
SITE ADDRESS:
WOOOHILL RD
DESCRIPTION:
STORAGE MAKE
REMARKS:
FEE SUMMARY:
VALUATION
as.,7? $12S . 00
(-)c)
TotL1 Fk7A,! $1, 0 . 00
CONTRACTOR: OWNER:
- Applicant -
WOOOHILL RD
mT\'.
-HE UNDERSIGNED HEREBY REC'UESTS PERMISSION TO MAKE THE REAL IN:-ROYEMENTS
SPECIFIED ANO AGREES CO DO ALL WORK SCRICI COMPLIANCE WITH ALL CITY OF
ORONO : - r r : AND STATE OF MINNESOTA BUILDING :ODE REOURPMENTS .
KT)
APPLICANTPERMITEE SIGNATURE ISSUED BY:SIGNATURE
CITY OF ORONO APPLICATION FOR MECHANICAL PERMIT
Box 66 (2750 Kelley Parkway)
Crystal Bay, MN 55323
GENERAL INFORMATION
1. You may apply for mechanical permits by mail or in person at the City offices. Applications will be
reviewed and a permit will be issued within 2 working days.
2. Permit cards will be sent by return mail after a review is completed. PERMITS ARE NOT VALID
UNTIL YOU RECEIVE A PERMIT. WORK MUST NOT BEGIN UNTIL THE PERMIT CARD IS
POSTED ON THE JOB SITE.
3. Mechanical Designs - Complete calculations, details and specifications are required for each heating,
ventilation, humidification-dehumidification, and air conditioning installation including heat loss/heat gain
calculation, design temperatures, equipment ratings and identification as to type, manufacturer and model.
Data shall be presented on form provided. Identification of and specifications for water heating equipment
shall also be provided.
4. When any new construction or remodeling is involved, a separate building permit must be obtained.
5. All work must be done in accordance with the Uniform Mechanical Code/State Building Code
requirements.
6. All work must be inspected (rough-in and final). Call 473-7357. 24-hour notice required.
7. House Heating Test Record must be submitted before final.
Instructions Complete all items on this application. Compute the permit fee. Sign and date the certification.
INCOMPLETE APPLICATIONS WILL NOT BE PROCESSED. If you have questions, call 473-7357.
Please check one: Liew Addition Repair Replace
Residential '/Commercial
JOB SITE: )-4: w c ''1 ; /( C7 . Zip: cS' i
Owner's Name: w o d A ; l/ lr t l7 C iu Telephone Number: L/.7;-
Mailing Address: Y = C w-� .-'/ ; l� City: )/-e• c,— O Zip: cc
Contractor's Name: �� r r; ,�, �-7 ./,. Telephone Number: y F- 3--
Mailing Address: y & y /mow . S'1' City: L v . Zip:
SYSTEM DESCRIPTION
�� HEATING SYSTEMS
Quantity:
Make:
Model:
Fuel:
Flue Size:
Input BTUs:
Output BTUs:
CFM:
COOLING SYSTEMS
Quantity:
Make:
Model:
Tons:
H. Power •
WOOD BURNING EQUIPMENT
Wood stove with flue
Wood combination or add-on
Factory fireplace with flue
Factory Fireplace (s) Freestanding Masonry
Wood Stove (s) Franklin, other
Brand Name Model No.
Mfgr's MM., Clearances, side , rear , min. flue dia.
VENTILATION
No. Kitchen Exhaust ducted recirculating cfm
No. Bath Exhaust (must be ducted outside) cfm
No. Other Fans: Locations cfm
FUEL STORAGE (MUST BE APPROVED BY FIRE MARSHAL)
Z/Installation Removal
Fuel oil: gallons underground inside outside
LP Gas: gallons i,,‘,y
Other //5'c , i L,� u/ t ^-7 Gas opening
<5-o, o P: 5--0 ( /7 , o— Gc /�v i 1_0 )
PERMIT FEE CALCULATION /
1. 1.25% of Contract Price* or Minimum Fee ($35.00)
119100 0 °`2 x .0125 $
(contract price)
2. State Surcharge. ** Add the State Building Code Division
Surcharge to each permit. x .0005 $
or $.50, whichever is greater (contract price)
3. Postage and Handling (Only mail-in applications) $ 1.50
4. TOTAL PERMIT FEE (Add lines 1-3 above) $ /310 , ffb
* CONTRACT PRICE or JOB COST means the actual or estimated dollar amount charged for the permitted
work including materials, labor, profit, and other fixed costs. It is the amount to be charged to the
customer for the work done. If any material, equipment, labor, or installation are furnished by the owner,
tenant or any other party the reasonable market value of such items must be added to the estimated cost
or contract price for permit fee purposes. In the event that there is a dispute on the amount of the job cost,
the City may request the submission of a signed copy of the actual contract.
** The STATE SURCHARGE is .0005 of the contract price under $1,000,000 or $.50 - whichever is
greater. For valuations over $1,000,000 call the Department of Inspectional Services for the price.
The undersigned hereby applies to the City for issuance of a Mechanical Permit, agrees to do
all work in strict accordance with the ordinances of the City and the regulations of the Minnesota
State Building Code, and certifies that all statements made on this application are complete, true
and correct.
Applicant's Signature: Date: 7/x/9
Approved By: 1/ Date: 9 -s--97
U
STATE FIRE MARSHAL DIVISION fer
444 CEDAR STREET
..li
SUITE 145,TOWN SQUARE Ii �= / File No. : 97278
ST. PAUL,MN 55101-5145 t,,Nr...Ee/ M.P.C.A. Certif. No. :
PHONE:612/215-0500 Proposed Date of Install. : 09/29/1997
TDD:612/282-6555 STATE OF MINNESOTADate of Prelim. Approval: 08/26/1997
DEPARTMENT OF PUBLIC SAFETY
August 27, 1997
Westside Equipment Company ' °
902 Hwy 55
Medina, MN 55340
Jim Israelson (612)478-9572
RE: Woodhill Country Club, 200 Woodhill Road, , Orono, MN. 55391, Rick Federickson
(612) 473-5811
Installation of one approved 1,500 gallon aboveground split tank for 1,000
gallons of diesel fuel and 500 gallons of gasoline. Subject to attached
notes, inspection by SFMD, and local approval.
To Whom it may concern:
The plans for the above installation have been reviewed pursuant to Minnesota Statutes,
1984, Chapter 299F.19.
Preliminary approval is given for the aforementioned project subject to compliance with
the provisions of Minnesota Statutes, State Fire Marshal Regulations, and local ordinances
and permits. Construction shall be in conformance with Article 79, Flammable and
Combustible Liquids, contained in Minnesota Uniform Fire Code (1991 edition as amended) .
Final approval will be given following an inspection of the facility by either your area
local fire authority or Deputy State Fire Marshal.
Approval of the project described in this letter does not relieve the applicant of
responsibility to other Federal, State or local agencies regarding adherence to
regulations or the need to obtain necessary approval.
Questions concerning this project should be addressed in writing to our office for a
formal response.
Please refer to the file number listed above in all future correspondence concerning
this project.
Yours very truly,
Tho a- . Brac: , ate Fire Marshal
41
Nathan J. Krey (— WESTSPF Fr)!i(P ,IME T
Deputy State Fire Mars al - Code Specialist
SET 02199/
NJK R :l EIV ED
AN EQUAL OPPORTUNITY EMPLOYER
•
STATE FIRE MARSHAL DIVISION
285 BIGELOW BUILDING
450 NORTH SYNDICATE STREET
ST. PAUL, MN 55104
ABOVEGROUND FLAMMABLE AND COMBUSTIBLE LIQUIDS
PLAN REVIEW GUIDELINZ
PLEASE READ THE FOLLOWING INFORMATION BEFORE BEGINNING:
Fill in the information blanks completely .
Where not applicable mark NA.
- Submit all material in duplicate; include one guideline
sheet for cach plan to be reviewed .
- Include plot plan of property showing location of adjacent
streets , highways , buildings , surface waters, and other
immediate surroundings .
- Incomplete information will result in the plans being
returned.
Date: 7 / 29 / 97 Date of installation: 9 / 29 / 97
mo day year mo day year
Tank Site:
Company: Woodhill Country Club
Address: 200 Woodhill Road
City/State/Zip: Orono, Minnesota 55391
Contact: Rick Frederickson Phone:( 612 ) 473-5811
Contractor:
Name: Westside Equipment Company
Address: 902 Highway 55
City/State/Zip: Medina, Minnesota 55340
Contact: Jim Israelson Phone:( 612 ) 478-9572
MPCA Contractor Certification Number: 0011
Tank Information: One (1) 1,500 gallon dual compartment
Capacity: 1 1000 2 500 3 . : 4
Product: 1 Unleaded 2 Diesel 3 4
Construction:1 Vaulted 2 Vaulted 3 4
Steel/concrete Steel/concrete
Piping (material): Vent Lines Galv. Dispensing Lines Rubber •4
Type: Full Service Self Servic0.t x Storage
Dike Dimensions: Dike Construction:
Loading Pack Construction:_ _
THE FOLLOWING INFORMATION MUST BE PROVIDE1 FOR MPCA USE.
Leak Detection Method: Tanks visual Piping N/A and
Spill Prevention (Containment Basin): Yes X No
Overfill Protection: Type Extractor Vent
Material Under Tank: Concrete
All plans submitted must show at least the following information on plot plan. Give measure-
ments from tanks and dispensers to: property lines buildings_, driveways and surface waters.
YES N/A YES N/A
(X) ( ) Property Lines (X) ( ) Vent Pipe Termination Type
(X( ( ) Building(s) (X) ( ) Vent Pipe Size
(X) ( ) Tank Size (Gals.) ( ) (X) Piping Layout
(X; ( ) Product in Tank ( ) (X) Location of Dispensers
(X) ( ) Tank Dimensions ( ) (X) Waterways
( ) (x) Dike Dimensions ( ) (X) Dispenser Protection
(X) ( ) Tank Fill Opening (X) ( ) Signs: No Smoking-Shut Off Motor
(X; l 1 Driveways Minimum Age for Self Serve -
(X l 1 Lightning Protection 16 Years Old
Emergency Controls (X) ( ) Fire Extinguisher
( : (X) Loading Rack ( ) (X) Self Serve Attendant Location
(X l 1 Overfill Protection (X) ( ) Tank Location and Clearances
(X; ( ) Spill Prevention ( ) (X) Piping Protection
(),(i ( ) Material Under Tank ( ) (X) Tank Spacing (sholl to shell)
Remarks:
NOTICE: ONE COPY MUST BE PRESENT AT SITE FOR REVIEW.
OFFICE USE ONLY AOPLAN
Review Stamp Area Stamp In Area
1';1
REVIEWED
• SUBJECT TO FINAL NOTED
AND ANY CHANGES .ON
I • CONTACT LOCAL FIRE AUTHORITY
• •10- TO Pi •JECT START• Process Completed-Date Mailed Out
tM NN `,� ST IRE -ARSHAL
VI
By: Miscellaneous Information
Date:
4" emerger vent 4" emergency vent
o �1
Extractor vent valve, gauge
Tank gauge---4) 6" Emergency valve 2" vent terminate 12' above grade -
Extractor vent valve I
2" vent terminate 12' above grade
(:12)\
Overspill containment
110
Overspill containment
1000 gallon unleaded
500 gallon diesel
t
0 O
Suction Pump Suction Pump
t I
II
i
4" bollards on drive
Concrete tank pad, 16'x8'x8" sides of tank 5' from tank.
Tank dimensions
12'6"Lx5'8"Wx4'9"H
Owner
Woodhill Country Club
200 Woodhill Road
Orono, Minnesota 55391
..._._;„)..ti ( ,. ,
p� Ori Z
1p
\..\\\‘ '' c \
\ 2
CC\CS 1... .................)
1-
A A
0
\ N,
\ o
aL
......vi .. .. , „v. ligribmiwavivkainkviev
Cf\,\\
'''cg-
o / 11 \1
iillif/ \, //I,
O , 70 m� 3 - Z m
\ Z
1 O + �\ 1
Ip �' I bit
I.
\ +►\ 00; 1v+ ':I 2 � \
7
11
_ m m —r § At
4
/
, \
ti ,\. \ 1
71io _
I .
gI
CO x lb
- . Z All ----) C-:3) ‘.
<itte
\ \• \ 's, \ i ,,,,, , i i ii
il i 2
� ��\ \\ .
,,,
� '
I. 41. ,-,...7 / .....---/ ,/
• ,..
. -<
,, , , .), \
\ s
0 ,
' \''' \
\\\ \ \\\ ; 1
,\\ \ \\ \
lii .,„ .0 --- 7` C--,
• -0 / N c -A
\-, \X.
cc-
/ b r
1 v„, T... -\\,.......„1-- //z)\ •
c.,,---7.,
1 / ::i,./.
*4 ,
/11.0%\ / ( , j / /�90) i n'rppp
_ / /
)/
___ + -----/L" l 114k % — 4 ritf: -=_ /
co
•• 7 .r, 1
sv
-10
\ z ▪ s � °D o
: :. • < < 3 2
p OD • o. .D 1)
co
in
ALit
N .I
W 1
n
o g
0
U, I Jit III C
. ('''
r 1=' A +
M11 11 I •
. T 0 Nwmn• \
1 _
j _
0 I
�� T ) •
V
CD
-4m
o
.-=i
71
---''''N\s
1
. 1 /
•
,r _
1, i
II.,
I ��
Aboveground Dispensing of Flammable/Combustible Liquids
Notes
The installation shall comply with the Minnesota Uniform Fire Code .
The following are reference notes from the Minnesota Uniform Fire Code
which contain specific instructions applicable to this project . These
requirements must be complied with.
1 . The installation must be approved by the local fire chief .
M.R. 7510 .3440 Subp. 5
Sec. 79 . 903 (a)
When approved by the chief, the dispensing of Class I and
Class II liquids from a fuel dispensing system supplied by
exterior aboveground tanks may be permitted . . .
2 . Unless the tank is listed as meeting the requirements for
secondary containment, the tank must be provided with a
dike.
3 . The tank system must be listed for aboveground use .
M.R. 7510 .3440 Subp. 5
Sec. 79 .903 (a) 2 :
The tank system shall be listed as meeting UL 2085
requirements or approved for such aboveground use .
4 . Tanks must be provided with lightning protection.
M.R. 7510 .3440 Subp. 5
Sec. 79 . 903 (a) 10 :
Tanks shall be provided with lightning protection as
specified in National Fire Protection Association Standard
78, Lightning Protection Code, 1989 .
5 . Safety rules and signs .
Sec. 79 .903 (d) :
Conspicuous signs prohibiting smoking, prohibiting
dispensing into unapproved containers, and requiring vehicle
motors to be stopped during fueling operations shall be
posted within sight of each customer being served.
6 . The location and size of the required fire extinguisher shall be
shown on the plot plan.
Sec. 79 . 908
A fire extinguisher with a minimum rating of 2A2OBC shall
1
Aboveground Dispensing of Flammable/Combustible Liquids
be provided and located such that it is not more than 75
feet from any pump, dispenser or fill-pipe opening.
7 . Unsupervised Dispensing.
Sec. 79 . 903 (f) 1 and 2 :
The dispensing of Class I and Class II liquids into the
fuel tank of a vehicle or into a container shall be under
the supervision of a qualified attendant at all times .
EXCEPTION: Unsupervised dispensing complying with Section
79 . 903 (f) 2 .
A. The owner or operator shall provide and be accountable
for:
(i) . At least daily site visits,
(ii) . Regular equipment inspection and
maintenance,
(iii) . Conspicuously posting instructions for safe
operation of dispensing equipment, and
(iv) . Posting the phone number of the owner or
operator,
B. A sign, in addition to that required in Section
79 . 903 (d) , shall be posted in a conspicuous location
stating:
IN CASE OF FIRE OR SPILL
1 . Use emergency pump shutoff !
2 . Report the accident !
Fire Department No.
Facility address
C. Dispensing equipment shall comply with one of the
following:
(i) . The amount of fuel being dispensed is
limited in quantity by a preprogrammed
card,
(ii) . Dispensing devices shall be programmed or
set to limit uninterrupted fuel delivery
to 25 gallons and require a manual
action to resume continued delivery,
2
Aboveground Dispensing of Flammable/Combustible Liquids
(iii) . Product delivery hoses are equipped with
a listed emergency breakaway device
designed to retain liquid on both sides of
the breakaway point . Such devices shall be
installed and maintained in accordance with
manufacturer' s instruction.
D. During hours of operation, the system' s site shall
be provided with a fire-alarm transmitting device .
A telephone not requiring a coin to operate is
acceptable .
3