HomeMy WebLinkAbout10-08-2014 - compliance inspection for septic system SP TESTING INC. Steven B.Schirmers -951 Katydid Lane NE-St.Michael,MN 55376 Cert.No 627 - State License#394 - Phone 763-497-3566- Fax 763-497-5011 www.sptesting.wastewater(alcomcast.net- schirmerswastewater.com October 8,2014 Natural Environmental Corporation 4550 Wolverton Place Orono, MN A Compliance inspection was completed for the existing on-site sewage treatment system located on this property. The system consists of 2-1000 gallon septic tanks, 1-1000 gallon pumping chamber&a pressurized mound system with a 10'x 55'rock bed for a 4 bedroom home built in 1988. Soil boring#1 found mottled soil(redox features)at 1.5'into the original soil. Soil boring#3 found the original soil at elevation 92.3& bottom of the rock bed at elev. 92.9 leaving .6'of sand below the rock bed&a 2.1'separation from the bottom of the rock bed& redox features. Soil boring#2 found mottled soil at 1.7'into the original soil. Soil boring#4 found the original soil at elev.91.4&the bottom of the rock bed at elev.92.6 leaving 1.2'of sand below the rock bed &a 2.9'separation. The system meets the required 2'separation from the bottom of the rock bed & redox features& is classified as in compliance with Minnesota Chapter 7080 rules. The home has 5 bedrooms which requires a 10'x 63'rock bed. To add to the system, the existing rock bed will need to be removed&raised to elevation 93.8 to meet the 3'separation. The rock bed must be removed with 4"of sand &replaced with a backhoe(excavator)with limited travel on top of the mound (loam topsoil will need to be above the plastic limit). Then replace the rock bed,distribution pipes&sandy loam & loam cover. The rock bed will be added to at the east end of the mound. The topsoil cover removed from the mound may be used to re shape the side slope. Remove the rock&sand from the site. The existing tanks may be used upon completion of a Tank integrity report passing. If the tanks cannot be used,install 2-1250 gallon septic tanks&1-1250 gallon pumping chamber&the existing tanks will need to be abandoned,pumped&filled with soil &a Tank Abandonment report completed by a licensed contractor. The pump tank if used will need to have the hole sealed for a 2"diameter pipe. This onsite sewage treatment system is designed for a Type I system,Type 1,five bedroom home in accordance with the Minnesota Pollution Control Agency chapter 7080&local ordinances. A pumping chamber will need to be installed to lift the effluent to the treatment area. The power supply&switches must be located outside the manhole&pumping chamber In a weather proof enclosure. A warning device must be installed with a light&sound device,this is in case of a pump failure. The manifold&supply line must have back drainage to the pumping chamber. The distribution pipes shall have their ends capped. Be sure the rock&sand fill material are clean. The sod layer below the entire mounded area must be turned over,Just break up the sod. If the tanks have less than 2'of cover,the lids,risers&maintenance hole covers must be insulated to a value of R10. Cleanouts for each lateral must be insulated &be accessible from finished grade in an Irrigation box with a ball valve. All neighboring wells are located greater than 100'away from the proposed treatment area. Keep all heavy equipment off of the proposed treatment area before and after construction. The treatment area should be marked off before construction. This design is not valid&the system will need to be relocated if failure to protect the sites for new on-site sewage systems. MANAGEMENT PLAN: The tanks need to be maintained at a minimum of 1 time every 2 years,check with you pumper to set up a schedule. System inspected for areas by owner&or Inspector as determined by the local unit of Government. Any other requirements as determined by the local unit of Government. With proper installation&maintenance,this system should have no problem in treating septic effluent effectively. Nothing other than human waste,toilet tissue,laundry,showers,water softners etc. should be disposed of into the system. Recommend Iron filters be diverted out of the system. Garbage disposals are not recommended. Excessive amounts of soaps, antibacterial soaps,cleaning agents,shower cleaners used every shower& chlorine agents may kill the bacteria needed to treat septic effluent. Additives are not recommended. Recommend laundering be limited to 3 to 4 loads per day. Thank You Steven B.Schirmers • • Minnesota Pollution •Compliance .inspection Form - Control Agency Existing Subsurfa0e Sewage Treatment Systems 520 Lafayette Road North (SSTs) St.Paul,MN 55155-4194 Doc Type:Compliance and Enforcement Instructions: Inspection results based on Minnesota.Pollution Control Agency(MPONI For local tracking purposes: requirements and attached forms-additional local requirements may also apply. Submit completed form to Local Unit of Government(LUG)and system owner within 15 days System Status System status on date(mmldd/yyyy): °t= \1-1 4 111 Compliant—Certificate of Compliance ❑Noncompliant-Notice of Noncompliance (Valid for 3 years from report date,unless shorter time (See Upgrade Requirements on page 3) frame outlined In Local Ordinance.) --r7t2b-a -Crtin,..wS �f-1\+ L«1 Reason(s)for noncompliance(check all applicable) ❑Impact on Public Health(Compliance Component#1)-Imminent threat to public health and safety ❑Other Compliance Conditions(Compliance Component#3)-Imminentthreat to public health and safety ❑Tank integrity(Compliance Component#2)-Failing to protect gro ater O Other Compliance Conditions(Compliance Component 11`,3)-Falling to rotect groundwater ❑Soil Separation(Compliance Component#4) Falling to protect groundwater ❑Operating permitlmonitoring plan requirements(Compliance Component#5)-Noncompliant • Property information Parcel lQ#or Secrrwp/Renge:y-(�}.t,ta'11.1 6o - Property address: y S S U VJUI.V&ii-' R..41,e1 OW IsS.0 Reason for inspection: 64,a.-- ( '(¢A195c-1fl¢- Property owner: - Owner's phone: . or Owner's representative: 01.1-. 44r14"7, 4-, Representative phone: 1 t.3 -$‘44 `6u o', Local regulatory authority: G`-'S-< o lr D4.91-r-o Regulytory authority phone: °<Z,-Is;01,-1.;k,,00 Brief system description: a-ludo 424e,1 sc .ci_L,-(01-4.Y-S't I 27Ot,a1 4-C#r -fl LSoo>-K, ,wrcor • Comments or recommendations:14. Jo)/`Ss' 7-oz-v--'F7(09, 5`Z(6^' 'F` i4 47O T'‘ 1`i"O1^G Certification I hereby certify that all the necessary information has been gathered to determine be compliance status of this system.No determination of future system performance has been nor can be made due to unknown conditions during system construction, possible abuse of the system.Inadequate maintenance,or future water usage. Inspector name: �j f'e,v6.1 ,- GArNCI-- e\l'iQ'- . Certification number. (a.2,') Business name: 5 ��v4'r!�•''<11.1 1}S,n , License number: -` Ll- Inspector signature:i'....t7:-C-.6:4, Phone number. ?l03 -49.e)-"4,C.lv(o Necessary or Locally Required Attachments ®Soil boring logs System/As-built drawing 0 Formai local ordinance 0 Other information(list): d 1 WWW,P,Stdtt,mll,US ' 651-196-6300 • 800.657.3864 • TTY651.282'533Z or 800.657.3864 • Available In alternative formats wq•wwists4.31 . 1/24/12 i Property address: \*ot,V 0)-5, Inspector initials/Date: ] c21-A s-,y 1. Impact on Public Health—Compliance component#1 of 5 Corn•Bance criteria: Verification method(s): System discharge sewage to the 0 Yes No 0 Searched for surface outlet around surface, 3 Searched for seeping in yard/backup In homeNO System discharge sewage to drain tile 0 Yes si No si Excessive ponding in soil system/D-boxes?uO or surface waters. 0 Homeowner testimony(See Comments/Explanation) Yes 11 No 'Black soil"above soil dispersal system 140System cause sewage backup Into dwelling or establishment. ❑ System requires emergency'pumping ❑ Performed dye test Any"yes"answer above Indicates the system Is an Imminent Threat to Public Health and Safety. 0 Unable to verify(See Comments/Explanation) 0 Other methods not listed(See Comments/Explanation) Comments/Explanation: 2. Tank Integrity—Compliance component#2 of 5 Corn•fiance criteria: Verification method(s): System consists of a seepage pit, 0 Yes 0 No ❑ Probed tank(s)bottom cesspool,drywell,or leaching pit. 0 Examined construction records Seepage pits meeting 7080.2550 maybe 0 Examined Tank Integrity Form(Attach) corn.lent if allowed In local ordinance. Sewage tank(s)leak below their ❑ Observed liquid level below operating depth ❑Yes 0 No 0Examined empty(pumped)tanks(s) designed o•eratideath. If yes,which sewage tank(s)leaks: ❑ Probed outside tank(s)for"black soil" ❑ Unable to verify(See Comments/Explanation) Any"yes"answer above Indicates the ❑Other methods not listed(See Comments/Explanauon) system Is Falling to Protect Groundwater. Comments/Explanation: cDe I k°0(4)00"C) , » - i).t ,:1t."*C 4,0-64 3. Other Compliance Conditions—Compliance component#3 of 5 a. Maintenance hole covers are damaged,cracked,unsecured,or appear.to structurally unsound. 0 Yes* ®No ❑Unknown b. Other issues(electrical hazards,etc.)to immediately and adversely impact public health or safety. 0 Yes' ®No 0 Unknown "System/s an Imminent threat to public health and safety Explain: c. System is non-protective of ground water for other conditions as determined by inspector ❑Yes' •No 'System is falling to protect groundwater Explain: Yrifff,QCd•Ittlte,mil,US i 651496.6300 800.657.3864 • TTY 651.282.5332 or 800.657.3864 • Available in alternative formats wq•wwlsts4.31 • 1/24/12 • Property address: Lig Inspector Initials!Date:' %2c'S*j 4. Soil Separation—Compliance component#4 of 5 Date of installation: °) r' 0 Unknown • Verification method(s): Shoreland/Wellhead protection/Food Beverage ❑yes No Soil observation does not expire.Previous soil Lodging? observations by two independent parties are sufficient, Com•Hance criteria: unless site conditions have been altered or local For systems built prior to Apr11 1, 1996,and ®Yes 0 No requirements differ. not located in Shoreland or Wellhead MI Conducted soil observations)(Attach boring logs) Protection Area or not serving a food, 0 Two previous verifications(Attach boring logs) beverage or lodging establishment: ❑ Not applicable(Holding tank(s),no dretnfieid) Drainfleld has at least a two-foot vertical 0 Unable to verify(See Comments/Explanation) separation distance from periodically saturated soil or bedrock. ❑ Other(See Comments/Explanation) Non-performance systems built April 1, ❑Yes 0 No Comments/Explanation: 1996,or later or for nonperformance systems located In Shoreland or Wellhead Protection Areas or serving a food, beverage,or lodging establishment: • Drainfleld has a three-foot vertical separation distance from periodically • saturated soil or bedrock.* "Experimenter,"Other,or Performance" ❑Yes 0 No Indicate de•the of elevations systems built under pre-2008 Rules;Type IV s< 5 :9 • tJ y#r p or V systems built under 2008 Rules(7080. A. Bottom of distribbution media 2350 or 7080.2400 (Advanced Inspector gt3+;1• i•fr License required) B. Perlodicall saturated salt/bedrock S'e'a I.0 Dralnfield meets the designed vertical so 1- 'S a.1., separation distance from periodically C. S - = se elation r. a• a•9 saturated soil or bedrock. D. R:.uired cam.iiance se.station' a-D/ Any"no"answer above indicates the system is- "May be reduced up to 15 percent if allowed by Local Falling to Protect Groundwater. Ordinance. )afrrr� -(o w+'4( 4 3.0 SOP rt4vr.S Avv,4x. w am>�v. 5. Operating Permit and Nitrogen BMP*—Compliance component#5 of 5 ®Not applicable Is the system operated under an Operating Permit? ❑Yes 0 No If"yes",A below Is required Is the system required to employ a Nitrogen BMP? ❑Yes 0 No If"yes",B below la required BMP=Best Management Practice(s)specified In the system design if the answer to both questions is"no",this section does not need to be completed. Compliance criteria a. Operating Permit number. Have the Operating Permit requirements been met? ❑Yes ❑No b. is the required nitrogen BMP in place and properly functioning? ❑Yes 0 No Any"no"answer indicates Noncompliance, • Upgrade Requirements(Minn.Stat.§115.56)An imminent threat to public health and safety(ITPHS)must be upgraded,replaced,or Its use discontinued within ten months of receipt of this notice or within a shorter period If required by local ordinance.If the system Is felling to protect ground water,the system must be upgraded,replaced,or Its use discontinued within the time required by local ordinance.if an existing system is not failing as defined In law,and has at least two feet of design soil separation,then the system need not be upgraded,repaired,replaced,or its use discontinued,notwithstanding any local ordinance that is more strict This provision does not apply to systems in shoreland areas, Wellhead Protection Areas,or those used In connection with food,beverage,and lodging establishments as defined in law. m,Q6dStatie,ifli s 651.196.6306 • 800.657.3864 • TTY 651482.5332 or 960657.3864 • Available in alternative ionnats wq-wwists4-31 • 1/24/12 2011 purple code Mound Design www.SepticResource.com (vers 12.6) Property Owner: Natural Environmental Corporation Date: 10/8/2014 Site Address: 4550 Wolverton Place,Orono PID: Comments: instructions: =site specific input *adjust if desired =self-calculated(DO NOT ADJUST) U 5 bedroom Type I Residential System 2) 750 GPD design flow 3) [ No Garbage disposal or pumped to septic existing 3-1000 gallon tanks 4) 3000 Gal Septic tank(code minimum) 3000 Gal Septic tank(design size/LUG req'd) Tank options: none 5) 1.2 GPD/ft2 mound sand loading rate 6) 10 ft rockbed width 62.5 ft rockbed length &rtW--^^ tet,- -"go"3- 7) 3.0 ft lateral spacing 3.0 ft perforation spacing (maximum of 3 for both) end feed manifold connection 5) 3 laterals 60.5 feet long ( 21.0 ,perfs/lateral 63 perfs total (1/2 a perf means the first perf starts at the middle feed manifold) 9) 1/4" inch perfs at 1 feet residual head gives 0.74 gpm flow rate per perforation for this perf size&spacing,&pipe size on line 12,max perfs/lateral= n,line#8 must be less--> OK lo) 4.0 doses per day (4 minimum) l i) 188 gallons per dose (treatment volume) 12) 2.00 inch diameter laterals(or smaller)will meet"5x pipe volume" 2.00 inch diameter laterals(or smaller)must be used to meet"4x pipe volume"requirement 2.00 inch diameter laterals(or smaller)will meet"3x pipe volume" 13) 25 feet of 2.0 inch supply tine leads to 4 gallons of drainback volume (Tip:"top feed"manifold to control the drainback) 14) 192 gallons TOTAL pump out volume(treatment+drainback) 15) 7 feet vertical tiff t from pump to dispersal area,leads to a: )6) 47 GPM® 14 feet of head, Pump requirement (note:>50gpm may require an extra 3-6'of head) 17) 1250 gal Dose tank(code minimum) 1250 gal Dose tank(design size/LUG req'd) at 13.00 gpi leads to a 18) 14.8 inch swing on Demand float, or timed dosing of 4.1 min ON (confirm pump rate with drawdown (to deliver Average flow, 66%of Peak design flow) 9 hrs OFF test and adjust as necessary) )9) 12 inches from bottom of tank to"Pump OFF'float 20) 27 inches from bottom of tank to"Pump ON"float,or 12 inches to"Timer ON"float if time dosed 21) 30 inches from bottom of tank to"Hi Level"float,or 40 inches to"Hi Levet"float if time dosed 22) 860 gallons reserve capacity (after High Level Alarm is activated) II 23) 0.45 gpd/ft2 Absorption area Soil Loading Rate, which gives a mound ratio of 2.7 (minimum) (this must match the soil boring log) desired mound ratio 2.7 24) 6 percent site slope (0-20%range) 6 (%downslope site slope,if different than upslope) 25) 18 inches, or 1.5 ft.to Redox or other limiting condition (need at least 12"to be a Type I) Treatment zone contains 0 inches of 0%soil credit,and 0 inches of 50%soil credit. Giving a: 26) 18 inch,or 1.5 ft. Sand Lift Mound CRITICAL FOR FUTURE CERTIFICATIONS!!! elev.93.8 -foe o4-sa,+.�, 27) 27.0 ft.Total ABSORPTION width (sand beyond rockbed) 28) 0.0 ft.ups!ope and sideslope 17.0 ft. Downslope Individual slope ratios give BERM widths(topsoil beyond rockbed)of: 29) 4:1 upslope ratio 11 ft.upslope berm 30) 4:1 sideslope 16 ft.sideslope berms 31) 4:1 downslope 22 ft.downslope berm 32) Overall Dimensions: 10 ft.wide by 62.5 ft. long Rock bed 43 ft.wide by 95 ft. long Mound footprint 4"inspection pipe 18"cover on top Upslope berm 11 Downslope berm 22 ) - 12"cover on sides III. amp cap 8 6'topsoil) e...40011111.5 Clean sand lift _ 1.5 Depth to Limiting — LimitingCondition -- -""------------- Absor tion Width Note: For 0 to 1%slopes,Absorption Width is measured from the Bedequatly in both directions. For slopes>1%,Absorption Width is measured downhill from the upslope edge of the Bed. 33) Rock Bed: SScs"-1 9 a.,t. 1 ouu e. a .3,L. avo 1,a' sa r.-� 1 4t 1 it-vie-S1N- 9A•3 4b9 i-5 5,a,,-.\0 10 ft.by 62.5 ft.by [ 9 inches under pipe,plus 20%gives 28 yd'or"1.4= 39 ton 34) Mound Sand: (note:volume is based on 3:1/4:1 slope from top of rockbed,Exchange sand for loamy cap if desired) 33 up + 84-8 downslope + 1A,2-]ends+ 44-c-7-'under rock= 283- yd'or'1.4= 284- ton tY e' h t,_u{' !ti' >t•%.7l-A 1-4 17),t i,2: plus 20% Sea etl 35) Loamy Cap: 39 ft.by i?4-' ft. 6"deep,plus 20%gives .79 yd'or*1.4= 111 ton 1 s-l.' i, '.,n, x a.l 3,9 36) Topsoil: 43 Jft.by 9B ft. 6"deep,plus 20%gives 9-r yd'or*1.4= 121 ton 14 4, l,7 x a1 2.c.> I hereby certify that I have completed this work in accordance with all applicable ordinances, rules and laws. (27' k 5-qeC6--z-<)1.!/ )wc.- 3cl y 10/8/2014 Designer Signature Company License# Date I Installer Summary 3000 gallon Septic tank(minimum) Tank options: none existing 3-1000 gallon tanks 1250 gallon Dose tank(minimum) at 13.00 gpi 47 GPM @ 14 ft. of head, Pump required 14.8 inch swing on Demand float or 4.1 minutes ON time a 9 hours OFF time 27 inches from bottom of tank to"pump ON"float,or 12 inches to"timer ON"float 30 inches from bottom of tank to"Hi Level Alarm"float 25 ft. of 2.0 inch supply line with end feed manifold connection (Tip:"top feed"manifold to control drainback) 18 inch,or 1.5 ft. Sand Lift Mound 10 ft.wide by 62.5 ft. long Rock bed 3 laterals 2.00 inch diameter 60.5 ft. long 3.0 ft. lateral spacing 1/4" inch perfs 3.0 ft. perforation spacing No Effluent filter a alarm • 3 clean out a valve box assemblies 27.0 ft.Total sand ABSORPTION width (sand beyond rockbed)(minimum) 0.0 ft.upslope and sideslope 17.0 ft.Downslope Specific slope ratios give BERM widths(topsoil beyond rockbed)of: 4:1 upslope ratio 11 ft.upslope berm 4:1 sideslope 16 ft.sideslope berms 4:1 downslope 22 ft.downslope berm 4"inspection pipe 18"cover on top Upslope berm 11 Downslope berm 22 12"cover on sides r (6"loamy cap&6"topsoil) 1.5 Clean sand lift 1.5 Depth to Limiting LirniLinQ condition —"__ __._--- Absorption Width 127.0 _ Note: For 0 to 1%slopes,Absorption Width is measured from the 119c/equally in both directions. For slopes>1%, Absorption Width is measured downhill from the upslope edge of the Bed. Rock Bed: 28 yd3 or'1.4= 39 ton 9 inches under pipe Mound Sand: 203 yd'or'1.4= 284 ton calculation based on 3:1/4:1 slope from top of rockbed Loamy Cap: 79 yd3 Or*1.4= 111. ton 6"deep Topsoil: 91 yd3 or"1.4= 127 ton 6"deep INSPECTOR CHECKLIST - mound 4550 Wolverton Place,Orono nWELL setbacks: 20'to pressure tested sewer line (5 psi for 15 min) 50'to everything 100'to dispersal area with shallow well - PROPERTY LINES setback: 10'to everything Road setback: outer ditch,or 33'from center of township road,or 65'from center of cnty road LAKE/BLUFF setback: 20'for bluff. Lakes:GD_,RD_,NE_. Protected wetland . Building setbacks: 10'for everything, 20'for dispersal area. WATER LINE under pressure se 10'to bed,tank&sewer line. (else sewer line>12"below) 11 Sewer line ft baffle connection (no 90's, 3'between 45's, slope min 1"in 8',max 2"in 8') (no depth req's, clean out every 100', Sch 40 D2665 or F891) n Septic tank and risers (water tight,insulated,proper depth,existing verified by pumping) mfe 3000 gallons none - Riser over outlet, riser over inlet, 6"+inspection pipe over any remaining baffles. — No effluent filter a alarm Dose tank risers and piping (water tight,insulated,proper depth,drainback) mfe 1250 gallons n dose pump 47 gpm 14 head VERIFY PUMP CURVE 4.1 min ON 9 hr OFF • float setting drop 14.8 inches _ LABEL pump requirements and drawdown on riser or panel _ Cam lock, weep hole, supply line access (no hard 90,pipes reachable from grade-30") _ supply pipe sloped 1/8"+, supported by sch40 sleeve, and buried 6"+. _ splice box/control panel/electrical connections flow measurement:CT,ETM,time dosed,home water meter mound rock dimensions 10 X 62.5 Sand lift depth 18 inches. (Jar test:2"sand leaves<1/8"silt after 30 min) n Absorption Sand beyond rock 0.0 upslope 17.0 downslope n Bermed topsoil beyond rockbed 11 upslope 16 sideslope 22 downslope n cover depth of 12-18"+ VERIFY 3 laterals (1-2'from edge of rock) 2.00 inch pipe size 3.0 ft lateral spacing 1/4" inch perforations (smaller is ok) 3.0 ft perforation spacing Air inlet at end of laterals, and at top feed manifold. VERIFY clean outs (no hard 90's) - 4"inspection pipe to bottom of rock,anchored VERIFY Abandon existing system if necessary Re-use existing tank certification _ monitoring plan and type well abandonment form if necessary • SP TESTING INC. Steven B.Schirmers —951 Katydid Lane NE—St.Michael,MN 55376 Cert.No 627 — State License#394— Phone 763-497-3566 — Fax 763-497-5011 www.sptesting.wastewater@comcast.net— schirmerswastewater.com SOIL BORING PROFILE Natural Environmental Corporation 4550 Wolverton Place Orono, MN Soil borings completed with a bucket auger on 9-24-14 SOIL BORING #1 - ELEV.93.6- MOTTLED SOIL PRESENT AT 18" INTO THE ORIGINAL SOIL-NO STANDING WATER PRESENT IN THE BORING. 0 - 6" Fill soil loam 6" - 14" Fill medium sand 14" - 20" Original soil dark brown loam 10YR 3/3 20" - 28" Brown clay loam 10YR 4/3 28" - 32" Brown clay loam 10YR 5/3 32" - 40" Brown clay loam 10YR 5/3- distinct mottles 10YR 6/8, 10YR 7/1 SOIL BORING #2-ELEV.92.8-MOTTLED SOIL PRESENT AT 20" INTO THE ORIGINAL SOIL-NO STANDING WATER PRESENT IN THE BORING. 0 - 8" Fill soil loam 8" - 28" Fill soil medium sand 28" - 36" Original soil dark brown clay loam 10YR 4/2 36" - 48" Brown clay loam 10YR 5/3 48" - 54" Brown clay loam 10YR 5/3- Distinct mottles- 10YR 6/8, 10YR 7/1 SOIL BORING #3-ELEV.94.5-through the mound. O - 12" Fill soil loam 12" - 26" Fill soil medium sand 26" - 30" Original soil dark brown loam-distinct mottles 10YR 6/8 SOIL BORING #4-ELEV.94.2 SOIL-through the mound. O - 16" Fill soil loam 16" - 34" Fill soil medium sand 34" - 40" Original soil dark brow loam-distinct mottles 10YR 6/8 BORING #5- ELEV.91.4-MOTTLED SOIL PRESENT AT 22"-NO STANDING WATER PRESENT IN THE BORING. O - 12" Topsoil dark brown loam 10YR 3/3 12" - 22" Brown clay loam 10YR 4/3 22" - 36" Brown clay loam 10YR 5/3- distinct mottles 10YR 6/8, 10YR 7/1 / • -... .: . 1 \ NO � \•49ek\ \ ,1 IA a t kI..tSL "A•11✓ yx/./306 I . ---0*AN----fACS.NSOSI'S..II\ .\I\ Sf • i./.Z.7---- . 21 K. 1 'MA.>\CO.o �oY cN \•11 C.0•01 b o' ` wo -ti t9 Perco6o!gn Tats Scok= i`'''Ik(3 / , , �s.\' c q+ `,�"` x y Hole=-114system is k be cautnucted to mert i • the t�cnesota Pot u5on Coci'icl: A ency ,. • •••-•-• . �' .). Chapter 7080 & Local Ordinance 1'7 -„ ma - S' 92.P- /� Check- all underground utilities 1 $c•q=i f PROPERTY OF=is�L:�,o�o1.�I. - la4. . S-P TESTING/ Ocsigned By:-�.4 ---- - co:e=LWT/lc}. PH 763-.497-3-566 1°1 cf 1 "sl S s 9, A- 0f . lw ' .1k9� & � _ i ir + �' R 14 69 — o -SDI - ,1 i i , i fi 12. . i ' o16 � s o y $ It\iot_4. L1'6- g $ P i _ -4.tgli 6 N � l' ii 164''') ISS oli of -- 1 — '` ill i"' II X 1S INV Nr• g.3.4 5L). '. rifk - ‘11 I rillill cos ' 1,,,. t.._ci Mrd ti'' Ak _b 11. .6 . ....:-k IR .... qiii- .� 1.•. ,, ,: , , o , o 0 G ao i , tt• 1 la 1 11 ;1 , i: • � ii v. NI 0. t V1 i 1. ;.41 1 I --_ � ;. . f ` 6tt r I ._ ,R o O o " 7.. t. tv " a1, • t 3 G 11 ��WN+r s. -1. isCII ;- t G i'r);35_ V (7' cj3 i rit .. V _A & 1, --,. x -vii th o SP TESTING INC. Steven B.Schirmers—951 Katydid Lane NE—St.Michael,MN 55376 Cert.No 627 — State License#394 — Phone 763-497-3566 — Fax 763-497-5011 www.sotesting.wastewater@comcast.net— schirmerswastewater.com October 8, 2014 INVOICE Natural Environmental Corporation 4550 Wolverton Place Orono, MN Compliance inspection $350.00 Design addition to mound $300.00 TOTAL $650.00 PAID IN FULL Thank You Steven B. Schirmers