HomeMy WebLinkAboutPermit for connection to or use of MWCC Facilities Metropolitan Waste Control Commission
Mears Park Centre, 230 East Fifth Street, St. Paul, Minnesota 55101-1633
612 222-8423
January 21, 1994
Mr. John Gerhardson
Public Works Director
City of Orono 'JAN4
1
P.O. Box 66
Orono, MN 55323-0066
RE: Permit for Connection To or Use of MWCC Facilities
Permit Number 1257
Dear Mr. Gerhardson:
This letter is to inform you that the Metropolitan Waste Control
Commission (MWCC) has approved your application for Permit for
Connection To or Use of Commission Facilities . Enclosed is your
approved MWCC Permit Number 1257 for the connection of a 2" PVC
sanitary sewer to the MWCC' s Sanitary Sewer Interceptor 83-52 at
the intersection of Highway 12 and Stubbs Bay Road North, in the
City of Orono (see enclosed plan sheet) . Also enclosed is an extra
copy of the approved permit. This copy should be provided to the
contractor who will be making the connection so that s/he is aware
of the MWCC' s requirements.
Please note that the connection shall be made in accordance with
the Standard Detail PL100 attached to and made a part of this
Permit No. 1257 .
It is required that the City contact Mr. Wally Wessels' office at
telephone number 612-772-2585 (7 : 30 a.m. to 4 : 00 p.m. ) and make
arrangements to have an inspector on site at the time the connec-
tion is being made. A minimum 48-hour notice shall be given.
Please refer to the permit index number when requesting an
inspection.
PLEASE NOTE: If the Commission' s inspector is not notified prior
to installation of the connection, the applicant will be required
to pay all costs associated with re-excavation and inspection.
nc re�
' on� o hnson
Real _tate Specialist
CLJ:bw
Enclosures
cc : W.R. Wessels, w/enclosures
E.J. Bloom, w/enclosure
Equal Opportunity/Affirmative Action Employer
OWW
Metropolitan Waste Control Commission
Mears Park Centre, 230 East Fifth Street, St. Paul, Minnesota 55101-1633
612 222-8423
Og _
PERMIT NO. / y
INTERCEPTOR
APPLICATION AND PERMIT
FOR CONNECTION TO, OR USE OF,
METROPOLITAN WASTE CONTROL
COMMISSION FACILITIES
(Note: this form must be submitted in duplicate)
APPLICATION
The City of Orono hereby applies for a permit for
connection to, or use of, Metropolitan Waste Control Commission (MWCC)
facilities. A description of the proposed connection or use is attached to
this Application as Exhibit A, Supplemental Data Sheet. By execution of this
Application, the Applicant agrees to:
1. Provide such additional information as is requested by the MWCC in
order to make a determination on permit issuance.
2 . Abide by the permit terms and conditions set forth below and all
applicable state and local laws, ordinances, rules and regulations.
3 . Pay all applicable permit fees (i.e. , Service Availability Charge
and Industrial Strength Charge) in accordance with MWCC rules and
regulations .
4 . Reimburse the MWCC for any damages resulting to the MWCC ' s
facilities as a result of the connection or use of its facilities.
5 . Indemnify and hold harmless the MWCC, its employees, agents, and
contractors from and against all claims, damages, losses and expenses,
including but not limited to attorney' s fees, arising out of or resulting
from the connection to, or use of, MWCC facilities, provided that any such
claim, damage, loss or expense (1) is attributable to bodily injury,
sickness, disease, or death or to. injury to or destruction of tangible
property, including the loss of use resulting therefrom, and (2) is caused in
whole or in part by any negligent act or omission of the Applicant, its
contractors, subcontractors, or anyone directly or indirectly employed by any
of them, regardless of whether or not it is caused in part by the MWCC.
Dated 1-13-94 CITY OF Orono
SIGNATURE
Print Name: John R. Gerhardson 413• '1��
Title: Public Works Director
Page 1 of 3
Equal Opportunity/Affirmative Action Employer _01aL
16, 1
.r,
PERMIT
It has been determined that Applicant has adopted a comprehensive sewer plan,
has submitted it to the MWCC as - required by law, and that the proposed
connection to, or use of, MWCC facilities conforms to the adopted
comprehensive plan or adopted comprehensive plan or adopted revisions
thereof.
Permission- is hereby granted to Applicant for connection to, or use of, MWCC
facilities in accordance with the 'description provided by Applicant. This
permit is issued under the following terms and conditions:
1. The -provisions of the Waste Discharge Rules for the Metropolitan
Disposal System, Minn. Rules, Chapter 5900 apply to activity carried out
under this permit.
2 . This. permit does not replace permits required by the Minnesota
Pollution Control Agency or the necessity of securing other permits and
fulfilling requirements of other governmental units.
3 . The MWCC' s issuance of this permit does not constitute a
certification that the project design and construction proposed by Applicant
meet engineering standards. Applicant remains responsible for design and
construction, including safety, for the, project. Applicant's attention is
specifically directed to the confined space rules adopted by the Minnesota
Department of Labor and Industry, OSHA Regulations, Parts 5202 . 100 through
5205. 1040 and 5207. 0300.
4 . This permit shall .be null and void if the connection proposed by
Application is not made within 90 days from the date of issuance.
5. This permit is subject to modification or revocation and may be
suspended at any time for failure to comply with its terms.
Issuance Date < H2O !�METROPOLITAN WASTE CONTROL COMMISSION
By
Assistant Director, ngineering/
W.
Department
Page 2 of 3
EXHIBIT A
Supplemental Data Sheet
PERMIT NO. 15�
Community Orono Date 1-13-94
Individual Making Application D. Brian Fulmer Phone 473-9026
Representing Who
Location of Connection 3505-07 Wayzata Blvd. (Hwy 12 at SE corner of
Work to be Done by
unknown Stubbs Bay Rd. )
Type of Connection To interceptor with a wet tEUbpth 11 '
Size of Connecting Sewer 2" Pipe Material PVC""sojj�..t(.
CPU 14--7 U-E3oLr THZG:s0Efl ADA prbg: -M Sc1-dr-VULE itn PVC-
Invert
VGInvert Elevation 969 . 0
Area Served in Acres :
Residential 7. 8 acres Commercial
Industrial
Predicted- Flow in Gallons Per day
Initial 1096 Design 1096
Characteristics of Discharge:
Residential normal household use
Commercial dog kennel high animal wastes and wa-r �.atAr
Industrial
Unusual Characteristics of Above ( Strength, Oils , Chemicals ,
Temperature & etc. )
High amounts of animal wastes and wash water
Page 3 of 3
FRE Na
NIt%b STO I 100 1 Note: If a sewer main is connected more than 24' above the invert of
the outgoing sewer, connection shall be by means of an outside drop.
See Plates 103 and 104.
•'• 2 Q
A.
... 'bo
Type A, 8, or C
See PL105
11. SECTION .A_.A,
by
e •'j
-* Groin R2'-0
Grout
10. +
' Grout
VARIES 4• �`
5 W 5' Grout
5'
IFI
10' MIN
13. He Varies
12.
: ..:y�r.•' :..' y :� i 6.
PLAN
1'-0' 15
General Notes:
Neenah R-1733 frame, type "B' lid and concealed ® Lean concrete to bear against firm undisturbed soil.
pick holes for in Roadway Access Structures (IRAS). Provide water tight sleeve or cast—in gasket all pipes.
One (mox.) reinforced concrete adjusting ring Y, C See PL105.
or 6" thick with full 3/8" bed of mortar. ED Provide o—ring rubber gasket per ASTM C-443.
Provide 2 rings of E—Z stick (1/47) gasket material 11 12' wide polypropylene encased steps.
under costing. ED First length of pipe shall be ductile iron pipe or
Precast/reinforced eccentric cone and riser sections as SOR 26 pvc for new connections.
required per ASTM C-478. 13 For connection to existing AS's, core dell opening and .
Use only precast sections. No brick.or block. provide Type B water tight connector. i
8' cast in—place concrete or 6' precast reinforced 14 4' minimum — sand cushion.
concrete (64" min. o.d.). !
15 Underdisturbed soil or compacted subgrode.
Cement mortar all around. 16. Lifting holes which penetrate through section walls are I
not permitted.
GRAVITY SEWER ACCESS STRUCTURE '
�,�,,,� COX. GRAVITY
MP1 METROPOLITAN WASTE CONTROL �cr No'
��By- MVYCC COMMISSION
FB 9 10/93 ENGINEERING/CONSTRUCTION STANDARD INTERCEPTOR DETAILS s PL100
'"PROS
DEPARTMENT
ST. PAUL MINNESOTA
Otto G.Bonestroo,PE. Howard A.Sanford,P.E. Agnes M.Ring,A.I.C.P Miles B.Jensen,PE.
Robert W.
lip Gravel,
E.
Bonestroo Joseph C Andelik,RE Robert R.Pfeffede,PRE. Thomas W.Peterson,P.E. Karen L.Wemeri,P.E.
Rosene Marvin L.Sorvala,P.E. Richard W.Foster,P.E. Michael C.Lynch,P.E. Gary D.Kristofitz,P.E.
Richard E.Turner,P.E. David O.Loskota,P.E. James R.Maland,P.E. F Todd Foster,PE.
MEM Glenn R.Cook,
Anderlik & Thomas E
E.Noyes,RE. Jerry A.Bourdon, tt PE. Robert C.Russek, Sc J.A A.I.A.ganek,P.E. Do.Pertzsch,RE. luglas J.Benoit,P.E.
Robert G.Schunicht,P.E. Mark A.Hanson,P.E. Kenneth P Anderson,PE. Shawn D.Gustafson,P.E.
Associates Susan M.Eberlin,C.PA. Michael T Rautmann,PE. Mark R.Rolfs,PE. Cecilio Olivier,P.E.
'Senior Consultant Ted K.Field,P.E. Mark A.Seip,P.E. Paul G.Heuer,P.E.
Thomas R.Anderson,A.I.A. Gary W Morien,P.E. John P Gorder,P.E.
Engineers & Architects Donald C.Burgardt,P.E. Daniel J.Edgerton,PE. Charles A.Erickson
Thomas E.Angus,P.E. A.Rick Schmidt,P.E. Leo M.Pawelsky
Ismael Martinez,P.E. Philip J.Caswell,P.E. Harlan M.Olson
October 13, 1993 Michael P Rau,P.E. Mark D.Wallis,P.E. James E Engelhardt
Mr. Lyle Oman, Building Official
City of Orono
Post Office Box 66
Crystal Bay, Minnesota 55323
Re: D. Brian Fulmer Sewer Plan
File No. 139Gen
Dear Lyle,
We have reviewed the proposed sewer plan submitted for the D. Brian Fulmer property
located at the southeast corner of U.S. Highway No. 12 and the Burlington Northern
Railroad, in the Northeast Quarter of Section 32. We would recommend the following
modifications.
The pump should be designed for a Total Design Head (TDH) of 115 feet. This allows
for the static head when MWCC's Maple Plain Lift Station is pumping (1079 - 967 =
112 feet) and approximately 3 feet of head losses due to the 2" forcemain, check valve
and gate valve. The developer's engineer should check with the pump manufacturer
(Aurora/Hydromatic Pumps, Inc.) to determine of the motor will be overloaded if it is
pumping against a lesser head. For example, if the MWCC station is pumping at 1150
GPM or if it is not operating. The proposed lift station wet well depth should be a
minimum of 2' below the inlet pipe and 3' below the discharge pipe as shown on the
enclosed manufacturer's detail. The developer's engineer should check with the MWCC
regarding their tap connection requirements and should complete an "Application and
Permit for Connection to, or use of, Metropolitan Waste Control Commission Facilities".
Please contact me at this office if you have any questions regarding this matter.
Yours very truly,
BONESTROO, ROSENE, ANDERLIK & ASSOCIATES, INC.
J" b - )d�
Shawn D. Gustafson, P.E.
cc: Ms. Jeanne A. Mabusth,
Building and Zoning Administrator
Enclosure
2335 West Highway 36 • St. Paul, MN 55113 9 612-636-4600
oo�
PAGE ` OF
FLASHING ALARM LIGHT
N (OPTIONAL)
DUPLEX NEMA 3R OR 4X
CONTROL PANEL
(SHOWN our of POS/TION) OUTLINE O(' TANK BOTTOM
6
DETERMINED BY HYDR-O-MATIC
SUMP
SEAL FAILURE
LIGHTS(OPTI
TE VALVE EXTENSION
'DIA.FOR A8'O�l U. PE OESTA+- HT Pw`�TO�D fOR C"SCN CFFA'EP YNPT
K'DIA FOR 60 AA TA'i( V-r rr'?FAi 71.A+, 2 FR:..(701' V SAy1,-
NTERME-TE BRACE RE
---'iE'OIA ISTD) FOR EXTENSIONS LONGER • -r.,\
I iC Ocl pPTKHiAU � 'r
pTHER�K _ THAN K)'-0'
FTFIG -
CHA//I '
-L SUMP
ChIL L 11
QJIDE WIVE Cl)
i 6AL1L P4F'E - 0
STD GAIY.
PIPE D154H.
••�� CD NSTALL D BY TE `
WAM PE- ARED (.D MN H-O-M .O VALVE al
GLIDE RAILS LONGER V"0*wa TH R
THAN C'-0� QQ HB DIA.UXKI DISC 14.
RM B
NFU.0 NT 1 LµEV�L
16.0•MAX, FOR PIPING MPL HYDRV I raI i y .
(6�DiATA,N IU SEALED
H STD] T _ DISCHARGE - 4-J.1+ LG HOLD OWN BOLT SLOTS ON 31'DBC FOR 46 DVA SUMP
ON 6i;DBC FOR 60 DLA SUMP
-PUP FA1t111iE
RECd/L70Eo I Z-0"UK LEVEL — I
►LOATKW aamT
E�'TTOM (BY.OT HE115)
, �. DOR'M A046 SLC"FORo. Hi}OIA ANCHOR DOLTS
toy
SECT1014 B'B _ sECTcN A-A
f1/OTE : ufF O.(/LY UtiF PU�9f' Faf J/�1.�CFX D/0EkTiGA",, euT
Q/.4, 7:-�1./k Fob S7-".4a6- CX o er/rr,
.voo Fx7R4 z " �.r« c%/Flr� vivs,oF r,�.(ik , HYDROMATIC
/;DO EX7-44Z" GArF UA a W/T,y STil�iV P/� AU�CPUM S DROMATIC
OF r1,vi<
DUPLEX SPGH-G2HX FIBERGLASS INSTALLATION
WITH PEDESTAL MOUNTED CONTROL PANEL