HomeMy WebLinkAboutAbove Ground Flammable/Combustible Liquids Department of Public Safety State Fire Marshal Division 444 Cedar Street,Suite 145 St.Paul,MN 55101-5145 ABOVEGROUND Flammable and Combustible Liquids Plan Review Guideline PLEASE READ THE FOLLOWING INFORMATION BEFORE BEGINNING: ➢ State Fire Marshal plan review is required for aboveground tanks containing Class I and Class II liquids used for dispensing into motor vehicles, aircraft and marine vessels, and for bulk storage (exceeding 6,000 gallons) of Class I liquids. ➢ Fill in the information blanks completely. Where not applicable,mark NA. ➢ Submit all material in triplicate,include one guideline sheet for each plan to be reviewed. ➢ Include plot plan of property showing location of adjacent streets, highways, buildings, surface waters, and other immediate surroundings. ➢ Incomplete information will result in the plans being returned. ➢ All tank installations must comply with the 1998 Minnesota Uniform Fire Code. ➢ Installation is not to begin until a permit has been issued. ➢ Underground storage tanks will not be reviewed by the State Fire Marshal Division. NOTICE: ONE COPY MUST BE PRESENT AT SITE FOR REVIEW Date: Date of Installation: TANK SITE: Company: f,' Address: -Z- city, City, StatZip: 0'r 7�.o M � SS3 Slp Contact: f Phone:5- 7 ` Fax: `f"7�' 3 Z CONTRACTOR: Name: Lj Address: 2-4w W 64-L,, L City, State,Zi : W\vl S503 3 Contact: I^ phone• �2� ( - �,3 7v Fax• 4��.�, Office Use Only SFMD File No. Review Stamp Area Reviewer Comments: Page 1 of 2 All information requested below must be provided.on the plans or described below unless not applicable. Incomplete information will result in the plans being returned. Check all that apply: Dispensing—Bulk Storage Loading Rack Capacity: 1. 700 2. 1000 3. 4. Product: .1. 2. O ta, 34 Construction 1 2. 3. 4. �Wc urn U_ 'W,'b Piping(material): Vent Lines Dispensing Lines Il/A Type: Full Service Self-ServicOpen to Public riva eDike Dimension: � x 1 -7 Dike construction Loading Rack Construction: !�J— A Are tank locations shown on plans? Yes No Are all buildings shown on the plans? Yes No N/A Are property lines shown on the plans? Yes No Are overhead power lines shown on the plans? Yes No N/A What are the tank dimensions? Are emergency controls shown on the plans? Yes No N/A Describe overfill protection4� L,� s�,4 Describe spill prevention, VA!�QCJ Describe material under tank(s). C0�c Describe vent pipe termination and height IV ;460-)e- QXCUw Are dispenser locations noted on plans? Yes_ No N/A Is the piping layout shown on plans? Yes NST No Is required signage/labeling shown on plans? Yes No _ Are any LP tanks within 20 feet of or in the drainage path of proposed tank(s)? Yes No Are fire extinguisher locations noted on plans? Yes No Will there be a canopy above the tank(s)? Yes No_ Page 2 of 2 e ^�'LJ:�Ia .1-i6•"(JI- l�.'I '•v•� a:•+;l";:.:1 lV .•r .t�.c.�l� Y �t'J•:./: "til t LG.- t:.._ ..r. ..�d"!i�.•;Ji;-;•a-.. •' _ x�.• .. a - :�. �:!:?-j���J i l 1 ��, ...r jjy'�Tf E l:i/4,-NE�l%4, 0� SECTIC.ZN-'3.?.� X3—=23 r t ;j lEt tyEP�N "-COUNTY, 'R�s[��dE,.Ufii4 . j I •.'Va/r•(]JK - ./t�• °t j:J., '} �;' -ry..� :b: rib .: _ •,:." .`.. ../ t --2CYso2 Sfi.11.« :; G ,t J:. �9y`„',1,r..w•I•..jt:l••rj j=1.: ..•' :•/'��`� ;':' .AcvihA,ofs:•►r+, • ! •'^'•' .'''•� a: ':t�L:;;:^i�iL_i� _Kiln+•-,'�'<r- •;i i' r:LYa.:YG.O; F - NC !I 'IC ;t15Cia1l•,idS OF Pict::l S-:t GA/ I ::. !': Or the Suulluel ^•,,; it `.1 I 1, t ,,.: ! . (• ; i �1� ,1{, ::, _nsl Qucrlcr of sec.:cm _. ':;,1 i"ai�Slwti� .t north, Rarwic 23 Wiest u! �• ; �•,. i, / i , el Yicrldiari. destr l ed esr. ;.--w!nCit.9 at a p,,,nt on tnc old SuUt11w0%t Gua,ter of the i!�Wif !'�•y--- I. I Quarter, 01stant 1009.3% --et 4! / i i sGu:h+Est corder :hereof; -.heli: Z point on the North line of se Quarter of the tlortneast Quarte LAN 1005.E9 .•u:t :.es: from ule port I I I' !;•=.•=`i thereof; tnEA:E ve' LtOAg SL!C 20 .02 feet Lr, the actual oo:h: {1! y F „ r., of tree land to be iescrib_d; :.. �, I elor.0 a line eareilel wilt ine >Lj� - ' .5 ^•�..,.C�wC {y� Cc5"Ibeo.!ine 440.94 'EEC: tnE I'- 1 I "��• t DY J C It :2 :e. '.1 ti- : u:;• i;ne 1 -- 4 �•� • ��0, r .. � •�? � :,e •Ice. .;uartei of yNOr:ietS: : -► c may, 1 `J , t� i; ;rterse- lanGv.itn ine West �.D.• I ._.. t.%if or Sctc Southwest Qu: 1 ('; i -� �'. , �•,:r, q - ;; azst Gua: .- thence tar_: de_t i!ne to tn_-Hv.':hwds: to �i L• 'I ��' ,�; ��:'�;"•'_' :!. :%p4:l' - ' East na l f Of the Southwest Yue- �/ t; i M:7:; _ ��. +-y •', ..•., I Iy flor:neast Quarter tnertce :est s� i. •1:., ;,,,.,. c !lor:h Itne of aid Soutnwest Ouar:e. to ine ;a;n:.. 4 R, buirdinq :t: yo //a7'o9T3•Id 22"Z i+ra•,.•i Sur. • fi.:e v,at..•r riwL . I i 4C 1..S...7.3 I AfB-0- Z3•N /069.37 --_- I hereoy certify to Duane R. Jacobs, Marquette Bank Widen Valley and Chicago Title Company and to !heir successors and assigns. that I have surveyed, on the ground• the property legally described hereon; that tlAe size, eimeosions and locatiuns of all of the boundaries of Life property• buildings• and other visible inproveaents, casMents (as said eAse- mems are shown In Chicago Title Company's Commitment !b. C 2118925, dated 8-26-94), streets, roads, means of puolic access• rights-of-way which affect said property are correctly inq accurately shorn hereon; 1-14E'there are 110 visible encroachments. easements (as said easements are shown inChicage"YILIe Company's Coamitoent No. C 2«8925, dated 8-26-94), streets. rnade {nAte_nf_.u. .11.1 1....- .-... .af.r ....:1. ..- _... . 'OCT-06-00 09:36 AM F.06-, -. w: Qr lop o 0 o _ cry V 5 o Z., .: I 4 JUL-25-00 12513se PRt Ras �x M., co { f i i r r. D � C � O o � i N V) C O U 1 �I N N ( i tl �-•— MANHOLES & SPILL :CONTAINERS 517 SERIES 3 1/2 GALLON 71/2 GALLON AST SPILL CONTAINER AST SPILL CONTAINER Installed on aboveground store tanks forlhoptaposeo(cootalnipsmaMspft '.. ,' Installed onaboveground storogetanks ;:' purpo$eofcontairtingwrwlsptlta and drips ff+octl the fdl nozzle. 3 1rZ forthe =L.r gallon cepedty. Steel construction. and drips from the till rwrde.-7:.112'_ Lockable, and powder coated white. gallon capaW. Locimble, with drain FIG 517 ULC Usted. RGS18 valve and vented Gd. Connects to 4- male(NPT)riser.and is powder oosted FIG 517-Spill Containment. Male(NPT)riser connection. on the outside surface.ULC Listed. FIG 517 F-Spilt Containment Fermis(NPT)riser connection. CONSTRUCTION DETAILS FIG 517 WO-WASTE OIL CONTAINMENT-Removable screen on Steel body and lid(14 ga.),Brass drain valve.Vkon drain O-ft. inside of container so used fitters etc.can be allowed to drain. Si7E WRIGHT 2"(517.517F.and 517WO)........................__.............................is lbs SIZE WEIGHT ( 1 7F and 51712) ................................15 lbs .............................._._.............................................................. 21.5 lbs 819 &-820 WATERTIGHT NON-PRESSURE MONITORING WELL STORAGE MANHOLE MANHOLE Installed on atmospheric aboveground . Prarniumgrade Monitoring Wed Man- storagelanks providing a mormay hatch hole.Fullywaterllght,one-pieceCast for access Inside the tank All Carbon Steel construction. Bolts,ruts and gas- Iron ring and skirt, Permanent blade ">... kets are available. Double Punched triangle on wWte warning decal with version is also avallable. (819DP and FIG 519 brass well pate for stamping well FIG 819 MOP) number.Buno-Nseai(replaceable). Stainless Steel bolt machined with 819-4'Neck 820-7'Neck O-ring groove,made to may on cover SIZE WEIGHT when removed. Above Liquid Type FIG 619 t 8'...___,...._ . _._. _ _._...__..----.__........._. 55 lbs 9'x7'..... ...................._»..............................................................321bs 2b'..__....._..» ._...._. _._.... __..._._.._...................., ti3 lbs 12"x12'.... .................»................................................................701bs 24'............. ..................................»...............................».....8o Ib3 FIG$19 A-Same as FIG 519,but with Aluminum cover. Below Liquid Type 12'....... ».»..».»..»....._............»........».....»..»........................... 60 lbs 20". .......„..».....»»........._.......................»...........................«-.....71 tbs 356 & 357 B 420 424A 524 FLUSH FILL BOX Tradafonaifafbox.Fastandardriser SQUARE MANHOLE pipe with cover Rush with driveway surface.Gasketprovideswater-tight Square box to provide axess to equip- seal. Wrench famished with box. FIG 420/424 mens etc.on driveway surface. 356 PIG 420&424-Knock-down We For service stations. Requires i7drdmal _Zi....._. .. .. asson”at jobstte. NOTE: U.S. Federal UST Regulation s nxitifro Will con- r FIG.=4-Remedlation type used for tainment for fill pores. These sfw dean-up. Bolt down, gasketed types of M boxes,when used cover.wide 24" deep skirt. Pre-as- ,MRI rmt oompiy. sembled.aii welded construction. FIG 357 8 FIG ue MG 3W B-Seale jroa type•nIh FIG 524 Cast Yen body(rim).Brow ower, lodabke inner brass cep. Cast Mon FIG 4Z0-16 ga.skirt-3/13"4-way Floor Plate(cover) WEIGHT Bur"Gulaat, bodyansae rovergaskar. 20'x 2(r x 10-deep akhi.....__. ._. »..».. ........._. 59 Ibt F424-14 ga.1tW-3/8'4-way Fbor P*19(cover) 7S>ZE 3IG_________.._ __.. ......17- 241 x 24! x 104 deep .......».......«.....»... 97 lbs 7.75 bs 3'».........».»»»..«»-„--_.._.._2555 bs RG VA-14 ga.aktrt-3B'4-way Floor Plate(cover) 24'x 14”x 24'deep stint..».................».»..«...._.._»..»_. .....�.»:.NA CIA: TR. AT J11W Tf.4 )AC- II=44TrV9=1 '1146 CC=TC'C7TQ i f S s i ISI � i l 1 � � A I / o � o � A 9 10/g4/2001 14:06 7633237b14 1 owner's Operation & Safety Manual. SERIES 7008 PUMP For models: FR700, FR701 J ` /Y1-IYf't i i I, Model FR701 Model FR700 OUTSTANDING FEATURES •Up to 18 GPM / 58 LPM •UL and C-UL listed pump and motor •Full 113 HP 115 VAC-60Hz motor, optional 2201240 VAC-50160H7_ *Thermal overload protector •Heavy duty double pole switch f •Integral check valve �. •Built-in bypass valve I!ov.119. 2001 2:57PM No.8832. P. 2/ p • . OF STATE OF Nm4mSOTA DEPARTMENT OF PUBLIC SAFETY STATE FIRE MARSHAL DIVYSION 444 Cedar Street,Suite 145 * St.Paul,MN 55101-5145 Phone: 651/215-0500*Fax: 651/215-0525 *TTY:651/282-6555 INSTRUCTIONS REQUEST FOR VARIANCE/ IME EXTENSION REQUEST FOR FIRE CODE VARIANCE: The procedures for fire code variance requests are established under Minn. Stat. §299F.01 I, Subdivision S. When consider a variance the following must be met. The requesting party should show that: A. There is substantial compliance with the provisions of the fire code. B. The safety of the public and building occupants will not be jeopardized. C. Undue hardship will result to the requesting party unless the variance is granted. The following steps must be taken to apply for a variance: 1. Submit a request to the local governing body for a variance to the order issued by the state or local fire inspector. (The local governing body would be the city council,county board,board of supervisors, board of appeals, or town board in the area where the orders were issued.) • Your request should contain specific information on how you meet items A,B,and C above. The local governing body may move to endorse the variance,deny or modi the variance,or defer the matter to the.State Fire Marshal. • REMEMBER,it is up to YOU to present your case to the local governing body. 2. Submit the following items as a package directly to the State Fire Marshal in St. Paul (address above): • A notarized or certified copy of the local governing body's action. In lieu of notarized/cerdfied copies,faxed copies from the governing body are acceptable. • A variance request form(copy attached). • A letter explaining hove your request meets the requirements outlined in A, B, and C Iisted above.Remember:you must supply information to be considered. • Supplemental information such as floor plans, diagrams, contractor bids or estimates,and photographs are encouraged as they assist in making a determination relating to your request. Once items 1 and 2 have been received,your request will be placed on the Fire Marshal's Code Advisory Panel agenda for their consideration. The Panel may solicit comments and information from the involved inspector,the party requesting the variance and/or the local Fire Chief. After a thorough evaluation of the issue, a recommendation will be made to the State Fire Marshal. T• The State Fire Marshal will issue a decision approving,modifying, or rejecting the variance. You will be notified in writing within ten(10)working days after the Fire Marshal has made his/her decision. 5. If the request is not granted, you may proceed before the Fire Marshal as with a contested case in accordance with the Administrative Procedure Act. This consists of a hearing that is similar to a court trial.This request must be made in writing to the State Fire Marshal at the address above.It is suggested that you consult legal counsel prior to commencing a contested case hearing. page 1 of 2 a ` NoY.A. 2001 2:57PM No-8832 REQUEST FOR TMa F. TENSION- The State Fire Marshal is required to give a reasonable time for property owners to comply with fire code orders that are issued.Properties that need additional time must fon nally request a time extension from the State Fire Marshal. In considering time extension requests,the State Fire Marshal Code Advisory Panel will make its recommendations based on an assessment of the following criteria: 1. A good faith effort has been/is being made to correct all violations cited. 1C. The granting of a time extension is an acceptable risk for the building occupants and the State of Minnesota. M. Undue hardship will result to the requesting party unless the extension is granted. The following steps must be taken to apply for a time extension: I. Submit the following items as a package directly to the State Fire Marshal in St_ Paul(address above): • A variswc/time extension request form(copy attached). • A letter explaining how your request meets the requirements outlined in 1,11, and M listed above. • Supplemental information such as floor plans,diagrams,contractor bids or estimates,and photographs are encouraged as they assist in making a determination relating to your request. 2 Once these items have been received,your request will be placed on the Fire Marshal's Code Advisory Panel agenda for their consideration_ The Panel may solicit comments and information from the involved inspector, the party requesting the variance and/or the local Fire Chief. After a thorough evaluation of the issue,a recommendation will be made to the State Fire Marshal. 3. The State Fire Marshal will issue a decision approving,modifying,or rejecting the time extension request.You will be notified in writing within ten(10)working days after the Fire Marshal has made his/her decision. 4. If the time extension request is not granted,you may proceed before the Fire Marshal as with a contested case in accordance with the Administrative Procedure Act.This consists of a hearing that is similar to a court trial. This request must be made-in writing to the State Fire Marshal at the address on page I of these instructions. It is suggested that you consult legal counsel prior to commencing a contested case hearing. page 2 of 2 Nov 1f 2001 2:58PM No-8832 P.`41;/4 - °` STAVE OF MINNESOTA DEPARTIIIENT OF PUBLIC SAFETY STATE FIRE MARSRAL DIVISION 444 Cedar Street,Suite 145*St.Paul,MN 55101-5I45 Phone:6511215-0500}Fax:651/215-0525 *TTY:651/282-6555 APPLICATION FOR VARIANCE/TIlWE EXTENSION Dear State Fire Marshal: Please accept this application for the following matter. Variance "Time Extension Name: Ep- an- .fin.c. Phone: (f) Z173- 113 SIV ;Address' 26 8 !,t f. Gc� /31 c�0./. Fax: (�� - 4 3 City:_ QKO»p State: MA/ Zip: 55 35(0 iA E-Mail Address: SJOCh,mS C-' a0/ Com Relationship to Property:_Owner _Manager _Agent _Other: AA a r` Property Name: .e/y7` ?. �bL,. .;y►.�y(G, Phone: (2L*2= S/73- V35r� Address: 24o,?7 W. lALl Za i Q1 vo( Fax: ( 9SZ) _4 `73 — �l3 3 z City: ©aceto MN Zip: 55 354 File#(if known): Fire Inspector Name: Item number(s): Compliance date: (time extensions only) Date of Order: Item 1: Description of violation/issue: rs VS. eS5e) 6e&//071- s Inf rmation Provided(check all that apply): VS Governing Body Body Action(opinion from City Council,Board of Appeals,County Board,Township Board) photographs ...j4loor Plans/Diagrams _Contractor Bids _Plan of Correction _Otho: Signature of Requestor: Date. /2/6 Z.2 For variance requests,please attach a complete statement explaining items A,B,and C from page one of the instructions. For time extension requests,please attach a statement explaining items I,IL and III from.page two of the instructions. Supplemental items such as floor plans,contractor bids or photographs are encouraged owe° � State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://Www.dps.state.mn.us � L TSTALLATION OF ABOVEGROUND STORAGE TANKS Alcohol& FOR DISPENSING INTO MOTOR VEHICLES Gambling Enforcement The 1998 Minnesota Uniform Fire Code (MUFC) allows the dispensing of flammable (Class D and combustible(Class H) liquids from aboveground storage tanks (AST) into motor Bureau of vehicles including automotive marine, and aircraft.There are predominantly two es of Criminal g � p y � Apprehension AST's that are used for this operation; one is the Underwriters Laboratories (UL) listed 142 Capita security steel AST(both single and double wall) and the other is the listed 2-hour fire protected AST that is built to UL 2085 or other nationally recognized standard. Crime Victim Services The Minnesota State Fire Marshal Division is required to conduct a plan review and Driver&Vehicle i.-ispection for both of these AST installations when dispensing flammable (gasoline', or Services combustible (diesel fuel) liquids into motor vehicles. Proposed installations will need local Emergency i approval (permit) and VIN Pollution Control Agency and/or Depanment of Natural R.source� Management% approval when necessary. Code Specialists are available at the State =ire Marshal Division to est nse anency swer any questions on these requirements from the 'Viinnesota Uniform Fire Code. They Commission can be reached at (6_5 1) 215-0510,0 or by email sent to tirecode;w.S ate.:n.us. Marsh ail Reauirements for BOTH the UL 142 and 2-hour Drotected ST Pipeline Safety j 1. Installations are only allowed when approved by the local fire chief. I State Patrol Dispensers shall be located a minimum of 10-feet from buildings and property lines. -raffic safery When the hose is fully extended, the nozzle shall be no closer than 5-'reef from building openings. The dispensers shall also be located twenty feet or more from fixed sources or ignition. This is not the only separation requirement: there are additional rules that apply for seoaration between the tank and buildings and also the tank and dispenser. These can be found onpage 3 or depenainQ on the type of tank installed. f 3. Dispensing hoses for automotive dispensing are limited to 13-feet. At marine or aircraft i fuel dispensing stations, the hoses are allowed to be 'longer. i i -SSTs shall be provided with secondary containment that will heid the volume of the largest AST within the secondary containment area. Examples include dikes, drainage control, listed double wall ASTs, and listed secondary containment built into the AST. Dispensing and fill piping shall not penetrate a dike. 5. ASTs shall be protected by spillage, and overfill as required by the local fire chief. 6. ASTs shall have vehicle impact protection, such as guard posts, to provide protection of connected piping, valves, fittings and storage tanks. When guard posts are installed, the posts shall be(1) constructed of steel not less than 4 inches in diameter and concrete filled, (2) spaced not more than 4 feet between posts on center, (3)set not less than 3 feet deep in a concrete footing of not less than 15 inch diameter, (4) set with the top of the SFMD Fact Sheet INS-FACT 1999-11 November 1, 1999 Pagel of4 J SFMD Fact Sheet INS-FACT 1999-11 November 1, 1999 / Page 2 of 4 posts not less than 3 feet above the ground, and(5) located not less than 5 feet from the tank. 7. Dispensers shall be protected against physical damage from vehicles by mounting on a concrete island 6 inches or more in height or by other approved means. S. There shall be an emergency shut-off device located between 20 feet and 100 feet from the dispense: Activation of the emergency shut-off shall shut down transfer of fuel to the dispenser and shall close all valves that supply fuel to the dispenser. The emergency shut-off shall be distinctly labeled EMERGENCY FUEL SHUTDOWN DEVICE. 9. Within 75 feet of the dispenser,there shall be a portable fire extinguisher rated at a minimum 2-A, 20-B:C. The fire extinguisher shall be inspected annually by qualified personnel. 10. Signs prohibiting smoking, dispensing into unapproved containers, and requiring vehicle engines to be stopped during fueling shall be conspicuously posted within sight of each dispenser. W1�ea open u. the public or when there are empiovees that are under 16 years old. there shall be a sia*1 stating d. e minimum ase to dispense :lammabieicombustibie liquids is 16. 1. Weeds. grass. brush. rmash and other combustible materials shall'_cept at least 10 feet from anAST. _. ASTs snail have a minirlum 3-:pet separation berween ta_nkcs. Larger t ^.!cs may=eauire:r_ore space. .�. Storage vessels for LP-gas an4 CSG stall be iocated=0 feet or more from.SST's. Suitabie-means shall be provided w prevent the accumulation of liquids under adjacent I- gas containers such as b}' dLkeS -Jlversion curbs or_JradinQ When HJT s arm: within a dL�ed area. :ham _?-?'.S containers 3;.a:1 outside the diked area and at least 10 feet away Tom the centerline of the :nail or the diked area. 1-. ASTs shall nave warning si—ps or labels to identif�i the tank contents _o axer^ency personnel. i:. :SSTs require nor-.:mai and emer2encv ents. The normal vent shall to minate at least 12 feet above th Q*ound level and 5 feet from buildins Ot7e.^1n2S OrproDert.v lures that Can aL'llt'1Don. 16. Elec.;cai eauit rrmeat shall be installed in accordance with the liinnesota State =lecarical Code. 17. Dispersing is required to be under the supervision of a qualified attendant at all times. The attendantz primary function shall be to supe^rise, observe and control the dispensing of motor fuels. The attendant shall prevent the dispensing of flammable and combustible liquids and flammable gases into containers not in compliance with the Minnesota Uniform Fire Code. The attendant shall also control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers. A method of communicating with the fire department shall be provided for the attendant. 13. Contact the State Fire Marshal Division for requirements that may apply to situations such as: • Dispensing at a bulk plant,marina or resort • Dispensing of LPG, CNG, etc. • Dispensing inside a building • Dispensing from tank vehicles 0 Dispensing into containers • Unsupervised dispensing 19. Pages 3 and 4 of this information sheet contain additional requirements specific to the type of above ground tank installation used for dispensing. 1 . G SFMD Fact Sheet INS-FACT 1999-11 November 1, 1999 Page 3 of 4 Additional requirements for UL 142 AST UL 142 above ground storage tanks are plain steel tanks that may be either single or double wall. These tanks are not constructed to be fire resistive and thus have requirements for separation between the tank and buildings and also between the tank and dispenser. This page covers the additional requirements for single and double wall plain steel UL 142 tanks.Note the separation required between the tank and buildings plus the separation required between tank and dispenser. 1. A maximum of three ASTs are allowed for dispensing at any single dispensing site.AST shall no; exceed 6,000 gallons individual capacity for Class I liquids (gasoline)and 10,000 gallons individual capacity for Class H liquids (diesel fuel). 2. ASTs shall be separated from the dispenser by at least 30 feet. Exceptions: 1. Operations not open to the public and for resort operations serving re?istered ?uests oniv. dispensing of Class I liquids from one AST of 560 gallons capacity or less may have the dispenser located on top of. or adjacent to, the AST. 2. Operations not open to the public and for resort operations serving registered Quests oniv, Cwo AST of 1,000 gallons individual canacity or less may dispensing of Class II liquids from have the dispenser located on too of. or adiacent to. the AST. 3. Tanks shall be located not less than 50 feet from the nearest side of a public way, property line, building, or combustible storage located on the same property. Exception: ASTs which are separated by 30 feet or more from the dispenser may reduce the distances between the AST and the public way, property line, building, or combustible storaQe to 30 feet. !. Fuel delivery shall be -om the top or the AST with the dispensing line equipped with an approved antisyphon system. 6. Dispensing lines between a diked area or_-\.ST and a dispenser shall be Tocated underground and shall be in an approved secondary containment piping system. 6. Dispensing lines shall have an approved normally closed solenoid valve at each dispenser below the impact valve. 7. Fill pipes between a diked area or AST and the fill pipe opening shall be located underground. The fill pipe shall also be equipped with manually operated mechanical shut-off valve located inside the diked area, but can be operated from outside the dike. 3. ASTs shall be provided with lightning protection in accordance with the National Fire Protection Association Standard 780 (1994 edition). 9. When required by the local fire chief,multiple AST installations shall be protected by an approved fire protection system. SFMD Fact Sheet INS-FACT 1999-11 November 1,1999 Page 4 of 4 Additional requirements for 2-HOUR PROTECTED AST Fire resistive 2-hour protected above ground storage tanks usually include steel tanks that are double wall and encased in some form of protective insulation such as reinforced concrete.These tanks are constructed to be fire resistive and thus have reduced requirements for separation between the tank and buildings and also between the tank and dispenser. A plain steel tank(either single or double wall) is not a 2-hour protected tank and must instead be installed following the spacing requirements for UL 142 tanks found on page 3 of this information sheet. This page covers the additional requirements for double wall fire resistive 2-hour protected tanks.The separation distances given here apply only to this type of tank and do not apply for single or double wall plain steel tanks. 1. ASTs shall not exceed 12,000 gallons individual capacity or 43,000 gallons aggregate capacity at any one dispensing site. :. ASTs less than or equal to 6,000 gallons shall be located at least 1 feet from property nines that can be built upon, including opnosite sides of a public way. These ASTs shall also be located at least 5 'eet from buildings and the near side of a public way(see the table below) ASTs rezte;than 6.000 gallons shall be located at ;east `ee:from propene✓lines that Carl be built U-con. including opposite sides of a public way. These ASTs shall also be located at least =: fee:from buildings and the near side of a public way(see the table at the bottom of this nage). !. ASTs shall have overfill prevention that will provide notification at 3P'o I-- and automatically slob fuel flow at 90%. �. Disuensina devices can be installed on or adjacent to the AST. 6. nd.sluIlon devices shall be installed on the external piping when the piping e:.te nas below :he licuid level of the AST. 7. Fill openings shall have a spill container at least 5 gallon capacity. Minimum separation requirements for protected aboveground tanks Individual Tank i )Minimum distance from Minimum distance l�linimum Capacity property line which is or from the nearest side of distance (gallons) can be built upon, any public way or from between tanks including the opposite the nearest important side of a public way building on the same ! property Less than or equal' 115 feet 15 feet j feet to 6,000 i Greater than 6,000 25 feet 15 feet 3 feet • Department ofPubfic Safety State Fire Marshal Division • 444 Cedar Street,Suite 145 St.Paul,MN 55101-5145 ABOVEGROUND Flammable and Combustible Liquids Plan Review Guideline PLEASE READ THE FOLLOWING INFORMATION BEFORE BEGINNING: > State Fire Marshal plan review is required for aboveground tanks containing Class I and Class II liquids used for dispensing into motor vehicles, aircraft and marine vessels,and for bulk storage (exceeding 6,000 gallons) of Class I liquids. > Fill in the information blanks completely. Where not applicable,marls NA. > Submit all material in triplicate,include one guideline sheet for each plan to be reviewed. > Include plot plan of property showing location of adjacent streets,highways,buildings, surface waters,and other immediate surroundings. > Incomplete information will result in the plans being returned. > All tank installations must comply with the 1998 Minnesota Uniform Fire Code. > Installation is not to begin until a permit has been issued. `r Underground storage tanks will not be reviewed by the State Fire Nlarshal Division. NOTICE: ONE COPY NMUST BE PRESENT AT SITE FOR REtiZEtiV Date: 10- ` - C Date of Installation: TANK SITE: Company: V Address:LOS-1 t4 I Z _ City, State,Zip: �'r Rte` i%► 5 �� Contact: L,' Phone: Fi�z�7 4!� Fax:S�-�-73--5Z CONTRACTOR: Name: L.jk, —"rc i^ Address: 2tkZ4� W G- �- City, State.ZiD `;, `LIZ Vh - 1 Contac t: .�;�S.z ,a e phone:f�1�1=L-3 70 pax. • Office Use Oniy SFtiID File No. Review Stamp Area Reviewer Comments: Pagel of 2 M All information requested below must be provided..ori the plans or described below unless not applicable. Incomplete information will result in the plans being returned. Check all that apply: Dispensing Bulk Storage Loading Rack Capacity: 1. IDOO 2 000 3. 4. Product: 2. 0-4 3. 4. Construction 16 i I 2. S 3• 4• ice, .,� BchlamukttzL Piping(material): Vent Lines : -, 'W-1b --gzJ Dispensing Lines AJ Type: FullService Self-Servicq�_Open to Public riva eDike_�� Dimension: Z X 1 -1 Dike construction &-%.0 V--�eL Loading Rack Construction: /J Are tank locations shown on plans? Yes No Are all buildings shown on the olans? Yes No N/A Are property lines shown on the pians? Yes_ No .-ire overread Powe:Lines shown. on the plans' Yes No N/A What are the tack dimeasions'. :are emergency controls shown on the plans? Yes No NiA C I Describe ove:nlI protection. Describe spill prevention \ < j Describe mate.iai under tank(s). Describe vent pipe termination and height Z-( ��baJi- l-c'.rcu. -,O Are dispenser locations noted on plans? Yes — No N- /A Is the piping layout shown on pians? Yes No Is required signageilabeling shown on plans? Yes No Are any,LP tanks within 20 feet of or in the drainage path of proposed tank(s)? Yes No Are fire extinguisher locations noted on plans? Yes No 161 Will there be a canopy above the tank(s)? Yes No Page 2 of 2 ' U. S. HIGHWAY Y N0. 12 - Y ur. • k.- /�, ► S 89606'320 E 1086.69 227.36 nom) t o ►,ms)c �1017) �Hctf of SW 1/4.) � s •e I —�j _� cs ('oy 18-23 7 ,u ca, �:csT (,oxo:) coxa I p0�1 (,C=31 .+t..t (,0x31) (tox•.,) BLACKTOP I 5-6 FT. HGH EVERGREENS—"Iv I o i GATE (,cx.,) j I ( �t.o i H SOLD :cNC ti f7FrT - l�_IPos� FUEL,-' (�)^- ARs: c AiL Ln 51 P SIO•:,')•3�:...j .i_ T� 'l �' I SUiLDING i -I I ? n N i I I m I I xe+ �e Wfffi FENC£ 128.80 99.23 toxw) �— °•1D o,°� N 89.09'23" W 22843 "' .tt j�• { '. • .x'•1111 I {' •'• '.'/�•,•_\ ,..,:. ';� ,.{' . .`t.'' -•'tip..- i . 1, 'h 1poo /�-Ak , 1 +11' 1 �u„•.I' � '+'�i) /„•�I„1, nlQc. t\S1.I Ila 44; qY _ • 'f JUL-23-00 12:13 PM 3. ,ci z ;{2 ! : 9:M .1 Mi 14 On i y j J ; i � � ; Ul 6 , MANHOLES & SPILL CONTAINERS • 517 SERIES 518 3 1/2 GALLON 7 1/2 GALLON t AST SPILL CONTAINER AST SPILL CONTAIN i r Installed on aboveground storage tanks ' for the purpose ofcwttalniMsmall spins ' Installed on aboveground storage and drips from the fill nozzle. 3 1R forthepurposeefcontainingsmali gallon capacity. Steel construction. and drips from the 13 nozzle. Lockable. and powder coated white. gallon capacity. Lockable. with FIG 517 UUC Usk• FRIG 51 a valve and vented lid. Connects male(NPT)riser.and is powder c; FIG 517-Spill Containmeru. Male(NPT)riser connection. on the outside surface.ULC UstF FIG 517 F-Spill ContalnneM. Female(NPT)riser connection. CONSTRUCTION DETAILS FIG 517 WO-WASTE OIL CONTAINMENT.Removable screen on Steel body and lid(14 go.),Brass drain valve.Viton drain O-ring. Inside of container soused filters etc.can be allowed to drain. SIZE WEIGHT 2•(517,517F.and 517WO).........................._...._.......................15 lbs SIZE rVS: 4'(517F and 517F).......«..............................................................15 lbs 4•.............................................................................................. 21 r ' 519 819 & 820 WATERTIGHT NON-PRESSURE MONITORING WELL STORAGE MANHO! (MANHOLE Ir-Ataled on atmos&.erc aneve;r ;N. Premium radeMonitorin• Wel Man- stcragetanksprovidingamarnvey g .- ,-, for accass.aside the mnk. All C= Man- We.Fullywatertlght.one-pieceCast ''� Steel construction. 500s.nuts aj-c Iran ring and skirt. Permanent black kats are available. Qcude ?_. triangle on white warning decal with •' vefsion is alsc available. ;fl1 SC= FIG 519 brass well plate for stamping well FiG 818 S470P) number.Buna-Nseal(replaceable), Stainless Steel boit machined with 319- - O-ring groove,made to stay on cover SrZE WE: when removed. Above Liquid Type FIG519 18'...__..:_.....-................................•-••---..........._......................... 9'x7'....................._........................................................................32 lbs 20......-............................... 12'zt2'.............................................._.........................................70lbs 24'................................................................................................ _ Below Liquid Type riG 519 A-Same as FIG 519.but with Aluminum cover. lap............................................................................................. . 12'................................................................._............................. 30 ibs 20'.............................................. ...................................._...... 24'........... «..«.«.............................................._....................... 358 8t 357 B 420 424 & 524 FLUSH ALL BOX ` Traditional its box.Ftts standard riser S..OUARE MANHOL.' pipe with cover flush with driveway surface.GarJcetprovideswater-tight Square box to provide access;o seal. Wrench furnished with box. FIG 4201424 ment etc.on driveway sur'ace. RG 420 8 424-Knock-down str FIG 356 service stations. Requires mir assembly at jobsite. NOTE--U.S. Federal UST Regulations require spill con- , FIG 524 -Remedlatton type use, Wriment for III porta. These site clean-up. ee down. 9asl' types of III boxes,when used cover with 24' deep skirt. P rr * sembled,allwelded construction alone,win not comply. . FIG 357 8 FIG 956 FIG 39713-SeWe-proal Mn-ith FIG 524 Cast Lion body(nin).9rase aowr. todcable mar brags cap. Cast iron 190 420-16 9a.skirt-318'4-wsY Floor Plate(cover) W E! Btms-N Csgfwt body.B acs mvor.Suna-N gasiwL 20'x 20'x 10`deep sIdrL. __-._. «...._...........__ size WEIGHT UM yyiG f RG 424-14 ga.skirt-3r8'4-way Floor Platte 3'.__..._.... _._ _..__. ...... 3.75 los 12.75 Pis 24'x 24'x 10'deep skirt «-.«.....».......��...... «... a 3•........................«..»»........7.75 Ibe 3'..._ «..«««.»».«.._. :S ZS lbs MG'524.1 A ga.skirt-3/8'4-waY Floor Plate(colrer)4* be _. . _._..... s'..„„._.... . _ _..______.33.s Rn 24”x 24"x 24'deep skht................».«.«.......____._ 10/24/2001 14:08 7,63323751" t , & Safety et owner. s operation y Manual SERIES 7008 PUMP For models: FR700, FRIG Model F 70 Mode! FR7C i OUTSTANDING FEATURES Up to 18 GPM / 68 LPM *UL and C-UL listed pump motor)andmotor k *,Full 1/3 HP 115 VAC.60H optional 220/240 VAC-50160Hz Thermal overload protector •Heavy duty double pole switch •Integral check valve j ;� •Built-in bypass valve Y0/24/2001 . 14:08 7633237614 JP EQUIP PAGE 83 ' r.JLI 66 R -N I &Istems Group The Filf-Rite,700B GL. listed -pumps- are positive displacement, direct drive pumps. Depending on Ticar .FaPPite customer. Installation and product viscosity, these pumps can deliver up to 18 gallons of fluid per minute. Their rugged, yet Congrah,tations on your purchase of Fill-Rite's new Series lightweight design, makes for a long life of trouble-free ;008 pump. we at Fitt-Rite have built our woridwide operation. reputation by designing the finest and most reliable pumps svailsble in today's market Your new pumpwas designed with pride by some of the best and most experienced fluid control experts available.We use Fill-Rite 700B pumps'safety are proven by their listing with: the most advanced technology possible to give you a pump with the superiorityyou deserve and the qualityyou've come to expect from Fat-Rite products. Underwriters Laboratories Inc.,anatfonally recog- nized independent,nroanization for product tast- U L c us ing to ensure public safety. Also recognized 'r 115710 Canada. George P. enklns rresioent Canadian Standards Association, a .Canac.:a^ organization for product testing to ensure Nu�_iic safety. ,� Electrical wiring should be 'B+ A 11 done by a licensed electri •Full 1/3 HP 220/240 VAC-50/60Hz motor uiat+ Tri auuuldance wilh ap- .Flow meters in U.S. gallons or liters proved electrical codes. Pump should be properly -Pedestal adapters for undargrour:d tank.rat2.!2tcrs •Nozz!,atic 1c`!=_s e holders ler automatic nozzles grounded and a rigid conduit d.u'tcr* should tis used wi"en insta!l- • ing elec,ric'al wiring.. !m proper use or installation of -GSRecommended Automatic wez�;es: this product can cause se _ ous bodily injury or death. �--�'v 11-A See flow Curve. t; r -aE:; �- M_ a R 7c ansurs safe and efficient operation, it is essential :c reit and follow eac:1 of these warrincs and 001 ^recauticns. Design Features: •!nlet: male:UFT or.cunc, amaze NFT-.r: o prevent damage to pump, cc not operate -Outlet: %" ,NFT ^ withol;t the dreg!<valve(F_661)Cr the chec%vslve •�uiit ;n C^CC,<vCIVC, cyCCCC .r•C pr�t :rs substitute (F2679) in piece. CAUTION: DO NOT INSTALL ADDITiCNAL =CC =. Do not smoke near pump or use pump neer an VALVE OR CHECK VALVE DURING INSTALr'tTICN open flame. Fire could result. WITHUU I PHESSURE HhLIEF VALVE. HOUSING CF 3 A filter should be used on pump outlet to ensure PLUMBING CRACKING MAY RESULT. that rel)foreign material is transiprred to fue!ianK. •Ft,,rnlshPd With tJL 15.- %°x'G Bose?r C maim I n-_ 7*' Take maters needing service to an authorized Security: Pump enuipoc-e for pacicctln5 repair shop or return to factory to maintain -Overall Dimensions: "explosion proof" integrity. -Models FR700., '14-wlce x 11• Ilgrl x 12"Ceep 5. The pump motor is equipped with thermai -Models r"n'701* 14' Moe x 1'"high x 14'deep overload protection. If overheated,ltwillshutitseif -Explosion proof motor cH without any damage to the windings. Be sure •1/3 HP 115 VAC-60hz dual mctcr, 1725 RFM,5::,amcs to turn off the pump power if this occurs. As the 115 VAC motorcools,itwillstart without warning ifpowcric •Thermal overicad orctcction on. •Bail bearing construction; no greasing or oiling required •Heavy duty switcl 2 10/24/2001 14:08 7633237614 ` JP EQUIP • OZRN ( •� — 1 cil.r 1 O Its,i 12y07/20tl 08:12 6127845236 CHETS SHOESSAGE` '81 iAipn.sot& State Dire Marshal Division File NO. : 00206 444 Cedar St-, Shite 145 M.P.C.A. Certification Number: St. Paul, iW 55101-5145 Proposed Date of Igstallation: (651) 215-0500 - voice, (651) 215-0525 - FM Date of Preliminary Approval: 11/26/2001 (651) 282-6555 - TTY November 26, 2001 LUBE TECH 2420 W. COUNTY ROAD C ROSEVILLE, MN 55113 TIM REHOE (612) 366-6370 RE: WESTERN STEEL, 2687 HWY 12, , ORNO, MN. 55356, LARRY (952)473-4344 western Steel 2687 Hwy 12, Orno, MN 55356. Contact is Larry at (952) 366-6370. Installation of three tanks for dispensing of diesel and gasoline. Approval subject to attached notes, SFMD inspection and local approval. To Whom it may concern: The plans for the above installation have been reviewed pursuant to Minnesota Statutes, 1984, Chapter 299F.19. Preliminary approval is given for the aforementioned project subject to compliance with the provisions of Minnesota Statutes, State Fire Marshal Regulations, and local ordinances and permits. Construction shall be in conformance with Article 79, Flammable and combustible Liquids, contained in Minnesota Uniform Fire Code (1997 edition as amended) Final approval will be given following an inspection of the facility by either your area local fire authority or Deputy State Fire Marshal. Approval of the project described in this letter does not relieve the applicant of responsibility to other Federal, State or local agencies recrarding adherence to regulations or the need to obtain necessary approval. Questions concerning this project should be addressed in writing to our office for a formal response. Please refer to the file number listed above in all future correspondence concerning this project. Yours very truly, Thomas R. Brace, State Fire Marshal &r-k Deputy State Fire Marshal - Code Specialist 12707/2001 08:12 6127845236 C:I$TS SHOES ` p " "82 MINNESOTA STATE FIRE MARSHAL DIVISION ABOVEGROUND STORAGE TANK PLAN REVIEW NOTES Western Steel, Orno, MN - File No.: 00206 - The installation shall comply with the Minnesota Uniform Fire Code, ('98 MUFC). The following are requirements from the '98 MUFC that contain specific instructions applicable to this peoject. These requirements must be complied with. The following are general notes for all above ground tank installations: 1. Installations are only allowed when approved bv the local fire chief. 2. Dispensers shall be located a minimum of 10 feet from buildings and property lines and when the hose is fully extended the nozzle shall not be closer than 5 feet from building openings. 3. Dispensing hoses shall not be longer than 18 feet, unless at a marine or aircraft fuel dispensing station. 4. ASTs shall be provided with secondary containment that will hold the volume of the largest AST within the secondary containment area. Examples include dikes, drainage control, listed double-wall ASTs and listed secondary containment built into the AST. 5. Dispensing and fill piping shall not penetrate a dike. 6. ASTs shall be protected from collision, spillage and overfill as required by the '98 MUFC and the local fire chief. 7. ASTs shall have vehicle impact protection such as guard posts. 8. There shall be an emergency shut-off device located not closer than 20 feet and not farther than 100 feet from the dispensers. Activation of the emergency shut-off device shall shut down transfer of fuel to the dispensers and shall close all valves that supply fuel to the dispensers. The emergency shut-off device shall be distinctly labeled EMERGENCY SHUT-OFF DEVICE. 9. There shall be provided not farther than 75 feet from the dispenser a portable fire extinguisher of a minimum rating 2-A-20:13C. The fire extinguisher shall be inspected annually by qualified personnel. 10. Signs prohibiting smoking, dispensing into unapproved containers and requiring vehicle engines to be stopped during fueling operations shall be conspicuously posted within sight of each dispenser. When open to the public or when there are employees under 16 years old there shall be a sign stating the minimum age to dispense flammable or combustible liquids is 16 years of age. 12707/2001 08:12 _ 6127845236 CATS SHOES `°gyp` x.; AST (UL 142) Requirements Page 2 11. Weeds, grass, brush, trash and all other combustible materials shall be kept at least 10 feet from ASTs. 12. ASTs shall have a minimum separation of 3 feet between tanks. 13. ASTs shall be labeled to identify the contents of each tank. 14. ASTs require nominal and emergency vents. The normal vent shall terminate a minimum of 12 feet above the ground level and 5 feet from building openings and property lines that can be built upon. 15. Electrical equipment shall be installed in accordance with the Minnesota Electrical Code. 16. Not more than three (3)ASTs shall be used for dispensing at any single dispensing site. ASTs shall not exceed 6,000 gallons individual capacity for Class I liquids (gasoline) and 10,000 gallons individual capacity for Class II liquids (diesel). 12,000 gal. capacities are allowed for 2-hour protected ASTs. 17. ASTs, other than 2-hour protected ASTs shall be separated from dispensers by at least 30 feet. (see exceptions) Exceptions: 1. Operations NOT open to the public and for resort operations serving registered guests only, dispensing of Class I liquids from one AST of 560 gallon capacity or less may have the dispenser located on top of adjacent to the AST. 2. Operations NOT open to the public and for resort operations serving registered guests only, dispensing of Class It liquids from two ASTs of 1,000 gallons individual capacity or less may have the dispenser located on top or adjacent to the AST. 18. ASTs shall be located not less than 50 ft. from nearest side of a public way, property line, building or combustible storage located on the same property. 2- hour protected ASTs may reduce separation distances. (see MUFC Appx. II-F) Exception: 1. ASTs which are separated by 30 feet or more from the dispenser may reduce the distance between the AST and the public way, property line, building or combustible storage to 30 feet. 19. Fuel delivery shall be from the top of the AST with the dispensing line equipped with an approved antisyphon system. 12/07/20.01 08:12 6127845236 CIHETS SHOES � 04 AST (UL 142) Requirements Page 3 20. Dispensing lines between diked area or AST shall be underground and shall be in an approved secondary containment piping system. 21.Dispensing lines shall have an approved normally closed solenoid valve at each dispenser below the impact valve (for remote dispensers). 22. Fill pipes between a diked area or AST and the fill pipe opening shall be located underground. The fill pipe shall also be equipped with manually operated mechanical shut-off valve located inside the diked area but can be operated from outside the dike. (For remote fill locations) 23. ASTs shall be provided with lightning protection in accordance with National Fire Protection Association Standard 780 (1994 ed.) 24. When required by the local fire chief, multiple AST installations shall be protected by an approved fire protection system. The following are notes specific to this installation: 1. These tanks are subject to vehicle impact and are required to be protected according to the MUFC: the tank, product transfer station, piping and appurtenances must be provided with protection consisting of metal posts filled with concrete, sunk 3' deep with 15"footings. Posts shall extend at least 3' above grade, be spaced no more than 4' apart, and be at least 5' from the tank and/or appurtenances. Any other design must be approved as an engineering alternate before installation. 12/07/2001 08:12 6127845236 CHETS SHOES " PAGE 05 9 Algal MI 11,V1,I 5 ' t State Fire Marsha! Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 6.51/215-0525 TTY: 651/282/6555 Internet: hfp://www.dps.state.mn.us INSTALLATION-OF ABOVEGROUND STORAGE TANKS FOR DISPENSING INTO MOTOR VEHXCLES Alcohol& Gambling Enforcement The 1995 Minnesota Uniform Fire Code (MUFC) allows the dispens rcing of laminable (Class I) and combustible (Class II) liquids from aboveground storage tanks (AST) into motor Bureau of vehicles including automotive,marine,and aircraft. There are predominantly two types of criminal g Apprehension ASTs that are used for this operation; one is the Underwriters Laboratories(UL) listed 142 capitol Security steel AST(both single and double wall) and the other is the listed 2-hour fire protected AST that is built to U1.2085 or other nationally recognized standard. Crime vlcaim Services The Minnesota State Fire Marshal Division is required to conduct a plan review and Driver&vehicle inspection for both of these AST installations when dispensing flammable(gasoline) or services combustible (diesel fuel) liquids into motor vehicles.Proposed 'installations will need local Emergency approval (permit) and MN Pollution Control Agency and/or Department of Natural Resources Management 1 approval when necessary. Code Specialists are available at the State Fire Marshal Division to Emergency answer any questions on these requirements from the Minnesota Uniform Fire Code. They Response Commission can be reached at(651)'215-0500 or by email sent to t"irecode@a state.mn,us. State Fire Marshal/ _Requirements for BOTH the UL 142 and 2-hour protected AST Pipeline Safety l. Installations are only allowed when approved by the local fire chief. State Patrol 2. Dispensers shall be located a minimum of 10-feet from buildings and property lines. Traffic safety when the hose is fully extended, the nozzle shall be no closer than 5-feet from building openings. The dispensers shall also be located twenty feet or more from fixed sources of ignition. This is not the only separation requirement• there are additional rules that apply for separation between the tank and buildin s and also the tank and diVenser.These can be found on page 3 or 4 depending on the type of tank installed. 3. Dispensing hoses for automotive dispensing are limited to l8-feet. At marine or aircraft fuel dispensing stations, the hoses are allowed to be longer. 4. ASTs shall be provided with secondary containment that will hold the volume of the largest AST within the secondary containment area. Examples include dikes, drainage control,listed double wall ASTs, and listed secondary containment built into the AST. �► Dispensing and fill piping shall not penetrate a dike. 5. ASTs shall be protected by spWage, and overfill as required by the local fire chief 6. ASTs shall have vehicle impact protection, such as guard posts,to provide protection of connected piping,valves, fittings and storage tanks. When guard posts are installed,the posts shall be(1) constructed of steel not less than 4 inches in diameter and concrete filled, (2)spaced not more than 4 feet between posts on center, (3)set not less than 3 feet deep in a concrete footing of not less than 15 inch diameter, (4) set with the top of the SFbM Fact Sheet INS-FACT 1999-11 November 1, 1999 Page 1 of 12107/2001 08:12 6127845236 CHETS SHOES PAGE 06 SFNM Fact Sheet INS-FACT 1999-11 November 1, 1999 Page 2 of 4 posts not less than 3 feet above the ground,and(5)located not less than 5 feet from the tank. 7. Dispensers shall be protected against physical damage from vehicles by mounting on a cotcrete island 6 inches or more in height or by other approved means. 8. There shall be an emergency shut-off device located between 20 feet and 100 feet from the dispenser. Activation of the emergency shut-off shall shut down transfer of fuel to the dispenser and shall close all valves that supply fuel to the dispenser.The emergency shut-off shall be distinctly labeled EMERGENCY FUEL SHUTDOWN DEVICE. 9. Within 75 feet of the dispenser,there shall be a portable fire extinguisher rated at a minimum 2-A, 20-B-C. The fire extinguisher shall be inspected annually by qualified personnel. 10. Signs prohibiting smoking, dispensing into unapproved containers, and requiring vehicle engines to be stopped during fueling shall be conspicuously posted within sight of each dispenser.When open to the public or when there are employees that are under 16 years old, there shall be a sign stating the minimum age to dispense flammable/combustible liquids is 16. 11. Weeds, grass,brush, trash and other combustible materials shall!sept at least 10 feet from an AST. 12. ASTs shall have a minimum 3-foot separation between tanks. Larger tanks may require more space. 13. Storage vessels for LP-gas and'CNG shall be located 20 feet or more from AST's. Suitable means shall be provided to prevent the accumulation of liquids under adjacent LP-gas containers such as by dikes, diversion curbs or gradiztg.When AST's are within a diked area, the LP-gas containers shall be outside the diked area and at least 10 feet-away from the centerline of the wall or the diked area. 14. ASTs shall have warning signs or labels to identify the tank contents to emergency personnel. 15. ASTs require normal and emergency vents. The normal vent shall terminate at least 12 feet above the ground level and 5 feet from building openings or property lines that can built upon. 16. Electrical equipment shall be installed in accordance with the Minnesota State Electrical Code. 17. Dispensing is required to be under the supervision of a qualified attendant at all times. The attendants primary function shall be to supervise, observe and control the dispensing of motor fuels.The attendant shall prevent the dispensing of flammable and combustible liquids and flammable gases into containers not in compliance with the Minnesota Uniform Fire Code. The attendant shall also control sources of ignition, give immediate attention to accidental spills or releases,and be prepared to use fire extinguishers. A method of communicating with the flute department shall be provided for the attendant. 18. Contact the State Fire Marshal Division for requirements that may apply to situations such as: • Dispensing at a bulk plant,marina or resort • Dispensing of LPG,CNG, etc. • Dispensing inside a building • Dispensing from tank vehicles • Dispensing into containers • Unsupervised dispensing 19. Pages 3 and 4 of this information sheet contain additional requirements specific to the type of above ground tank installation used for dispensing. 12/07/2001 08:12 6127845236 CHETS SHOES �p�'�"748 SFNID Fact Shcct INS-FACT 1999-11 November 1,1999 Page 3 of 4 Additional requirements for UL 142 AST UL 142 above ground storage tanks are plain steel tanks that may be either single or double wall. These tanks are not constructed to be fire resistive and thus have requirements for separation between the tank and buildings and also between the tank and dispenser. This page covers the additional requirements for single and double wall plain steel UL 142 tanks.Note the separation required between the tank and buildings plus the separation required between tank and dispenser. 1. A maximum of three ASTs are allowed for dispensing at any single dispensing site.AST shall not exceed 6,000 gallons individual capacity for Class 1 liquids (gasoline) and 10,000 gallons individual capacity for Class II liquids (diesel fuel). 2. ASTs shall be separated from the dispenser by at least 30 feet. Exceptions: 1. Operations not open to the public and for resort operations serving registered guests only, dispensing of Class I liquids from one AST of$60 gallons capacity or less may have the dispenser located on top of, or adjacent to,the AST. 2. Operations not open to the public and for resort operations serving registered guests only, dispensing of Class II liquids from two AST of 1,000 gallons individual capacity or less may have the dispensez located on top of, or adjacent to, the AST. 3. Tanks shall be located not less than 50 feet from the nearest side of a public way, property line, building, or'combustible storage located on the same property. Exception: ASTs which are separated.by 30 feet or more from the dispenser may reduce the distances between the AST and the public way, property line,building, or combustible storage to 30 feet. 4. Fuel delivery shall be from the top of the AST with the dispensing line equipped with an approved antisyphon system. 5. Dispensing lines between a diked area or AST and a dispenser shall be located underground and shall be in an approved secondary containment piping system. 6. Dispensing lines shall have an approved normally closed solenoid valve at each dispenser below the impact valve. 7. Fill pipes between a diked area or AST and the fill pipe opening shall be located underground. The fill pipe shall also be equipped with manually operated mechanical shut-off valve located inside the diked area,but can be operated from outside the dike. 8. ASTs shall be provided with lightning protection in accordance with the National Fire Protection Association Standard 780(1994 edition). 9. Wizen required by the local fire chief,multiple AST installations shall be protected by an approved fire protection system. 12/07/2001 08:12 6127845236 CHETS SHOES PAGE 88 SFMD'Fact Sheet TNS-FACT 1999-11 November 1,1999 Page 4 of 4 Additional requirements for 2-HOUR PROTECTED AST Fire resistive 2-hour protected above ground storage tanks usually include steel tanks that'are double wall and encased in some form of protective insulation such as reinforced concrete.These tanks are constructed to be fire resistive and thus have reduced requirements for separation between the tank and buildings and also between the tank and dispenser.A plana steel tank(either single or double wall) is not a 2-hour protected tank and must instead be installed following the spacing requirements for UL 142 tanks found on page 3 of this information sheet. This page covers the additional requirements for double wall fire resistive 2-hour protected tanks.The separation distances given here apply only to this type of tank and do not apply for single or double wall plain steel tanks. 1. ASTs shall not exceed 12,000 gallons individual capacity or 48,000 gallons aggregate capacity at any one dispensing site. 2. ASTs less than or equal to 6,000 gallons shall be located at least 15 feet from property lines that can be built upon,including opposite sides of a public way. These ASTs shall also be located at least 5 feet frond,buildings and the near side of a public way(see the table below) 3. ASTs greater than 6,000 gallons shall be located at least 25 feet from property lines that.can be built upon, including opposite sides of a public way_ These ASTs shall also be located at least 15 feet from buildings and the near side of a public way(see the table at the bottom of this page). 4. ASTs shall have overfill prevention that will provide notification at 85% fill and automatically stop fuel flow at 90%. 5. Dispensing devices can be installed on or adjacent to the AST. 6. Antisiphon devices shall be installed on the external piping when the piping extends below the liquid level of the AST. 7. Fill,openings shall have a spill container at least 5 gallon capacity. Minimum separation requirements for protected aboveground tanks Individual Tank Minimum distance from Minimum distance Minimum Capacity property line which,is or from the nearest side of distance (gallons) can be built upon, any public way or from between tanks including the opposite the nearest important side of a public way building on the same property Less than or equal 15 feet 5 feet 3 feet to 6,000 Greater than 6,000 25 feet 15 feet 3 feet 1W07/2001 08:12 6127845236 CHETS SHOES Deparunent ofPublio Safety - State Fire Marshal Division 444 Cedar Street,Suite 145 St.Paul,MN 55101-5145 ABOVEGROUND Flammable and Combustible Liquids Plan Review Guideline FFLEASEEAD THE FOLLOWING INFORMATION BEFORE BEGINNING: re Marshal plan review is required for aboveground tanks containing Class I and Class II used for dispensing into motor vehicles, aircraft and marine vessels, and for bulk storage (exceeding 6,000 gallons)of Class I liquids. ➢ Fill in the information blanks completely. Where not applicable,mark NA. ➢ Submit all material in,triplicate,include one guideline sheet for each plan to be reviewed. ➢ Include plot plan of property showing location of adjacent streets,highways,buildings, surface waters, and other immediate surroundings. ➢ Incomplete information will result in the plans being returned. ➢ All tank installations must comply with the 1998 Minnesota Uniform Fire Code. ➢ Jnstallation is not to begin until a permit has been issued. ➢ Underground storage tanks will not be reviewed by the State Fire Marshal Division. NOTICE: ONE COPY MUST BE PRESENT AT SITE FOR REVMW Date: Z --- Date of Installation: TANK SITE: Company: Address: -Z- City, Stat ,Zip: Contact: ��tr',r Phone: Fax: CONTRACTOR: Name: LAe- Address: ZO �- City, State,Q S Contact: hone: - 3 Office Use Only. SFMD File No. RevirWkaft EM I EWE ED Reviewer Comments: rUB1ECT TO FL44 INSPEC110N AND ANY CHANGE$NOTED, " • :ITAC7 LOCAL.FIRE ALRHORITY .,:OR TO PROJECT START, 30TA STATURE MARS ��z 1 DATED)kW a • LDO*.:;M Pagel of 2 12/07/20'01 08:12 6127845236 CHETS SHOES?,, p All information requested below must be provided on the plans or described below unless not applicable. Incomplete information will result in the plans being returned. Check all that apply: Dispensing Bulk Storage Loading Rack Capacity: 1. IDOO 2• 1000 3•- 4. Product: I. A- 2. `O` 3. 4. Construction l 2 3. 4. ��ft �. llsA piping(material): Vent Lines Dispensing Lines—AJ A 'Type: bull Sezv'� Self-ServicOpen to Public riva,Dike Dimension: � � � Dike construction Loading Rack Construction: N- A Are tank locations shown on plans? Yes No Are all buildings shown ou the plans? Yes No N/A Are property lines shown on the plans? Yes No Are overhead power lines Shown on the plans? Yes No N/A What are the tank dimensions' - Are emergency controls shown on the plans? Yes No N/A Describe overfill protection. 6� Describe.spill prevention Uej. -- Describe material under tank(s). , ,, A-0— Describe vent pipe termination and heigh 1 Z' 4 cxje— Are dispenser locations noted on plans? Yew No N/A Is the piping layout shown on plans? Yes_L M! No Is required signage/labeling shown on plans? Yes No Are any LP tanks within 20 feet of or in the drainage path of proposed tank(s)? Ye` No Are fire extinguisher locations noted on plans? Yes No Will there be a canopy above the tank(s)? Yes No_. Page 2 of 2 12/07/2001 08:12 6127845236 CHETS SHOES PAGE 11 U. S. HIGHWAY N0. 12 S 89006'320 E 1086.89 - !! � 227.36 •�I � (t � nes�+> ` (,mh)o o Hctfof SM 1/4, 'g' \\ �J �i -410=7) _�j �� in c,om IMO.0 RvO:C•7" (,o:..n {, . 1 (ta2U) • (,OiIG► �t02•.1 BLACKTOP 8� FT. hlGt EVE o (tom..) 0 Ito�s.'. • �, 0020, (taJs,) GATE 1 xt> (toxa.t) 2�.O TOLD Pfl(CE `,�� (t0:3a) S;AeJ'-,- (/a ) (la2ao)' �ATEA O.o IrZ ' (mxx.v) �� /I at.d!O ( 26Ii0?S ' m E=TNG WWF FENCE- Cp i yc TO GE ftuOVED ,t7 W 75 �• ToDa`E1°(RE►wvEJ BLAct(TOP�(� I C 6 OONC�STE U` y N m 2d.o I 3 I Cv� o z21 2 8 Z 9 30I, y) 91, (t02•At X02•? �� 1� (i02z1) ;,RAVEL EXISTING I Y BUILDING r in n d •i ! f ,•, 128.80 +• ' N 89'09'23" W 22403 Una porQW with ........... a,...d). 0_ ..# " t/s 12/07/2001 08:12 6127845236 CHETS SHOES x pAGE,' .12 i V13 i i � 55o GAS � f SSS C�a-� /000 te-Se_ r P�s'r U C vc�r o S i rz�` 12/07/2001 08:12 6127845236 CHETS SHOES PAGE 13 • '- JUL��3'-00 12:1 P� � . • I 1 �i�� Y,.t . �• �iiiSSSS� . f � :I 1 i i J Cl. � I � V O � I = N V i � 1 r G p Cn 3 E \ CD f CD p . t C �• c m f-• 2'' 1)t 4"i� l Tnp t CD 1 I� cn - _ _ -- _ � A N / \ w • \ I I m I I00 � � I � r � I \ IN 29" 1 60 " 1� 72 " FS- 512UL DW 550 gallon 12 gauge A-569 - I �w■■■.>i■■■■rw�w������■■■i■r���� f oco LbS, LURE ■ TECH :D UL142 STI 321 Listed and app-oved LUORICAT-Off tECHAOLOGIES, INC. im Double aro I, -iec;or)dary cooh)inrrrerit t mik 600 Me WelswhnAvenve Vodh 2420 WsltCam*Road C GordenV&%y,MH 55121 Ro As.MN 55113 12%07/2001 08:12 6127845236 _ CHETS SHOES .: - MANHOLES & SPILL CONTAINERS 517 SERIES 518 3 1/2 GALLON 7 1/2 GALLON 't ,t AST SPILL CONTAINER AST SPILL CONTAINEF it hn v"pu nabovegroundetaapetat staladonabovegrounddorapetmW lorlhepurPOYeoioOMlllNnps►r�eMsp it � �:.•;:• and wpa man the fill nozzle. 3 112 fa purposeofo0ntaillingast�spl0. gallon cspadly. $till consImcdon, trend drips from tba fE Mazza. 7 11 •� drai Laafeable, linen powder cooled whlbe. gallon capacity. Lockable, with 10 d FIG 517 ULG Usbed. FIG 518 v9Ne WW vented lid. Connects mels(NPT)dger,and is powder coats FIG S17-Spm ContdnmeriL Mate(NPT)Beer eonnedbn. on the ou bade surface.ULC Usted. FIG 517 F-Spa ConlalnmenL Female(NPT)river con nadlOn. Co"STRUCnON MIMAll.S FIG 317 Wo-WASTE OIL CONTAINMENT-Rwr 4W*swell on $"body seri Ikt(74 go.).Brass drain valve.Vltan drain O rig. n inside of oumok er sagged Mare ata.can be alknwed to drdn. GFff 2"0517,517F.and 517WO).........................---............ _....,.�•is ft SIZE wEIGFf 4-(517F and 517F)..... ..._......_... --.-..... . .._.. .15 on 4'...................................................._....................W..., ._........ 21.5 ..�;•� ' , 519 819 dc6Z0 WATERTIGHT NON-PRESSURE MONITORING WELL STORAGE MANHOLE MANHOLEWt W on Onaspheric SOW"rour .:„ ..^ s6orapelankeprwlangamanwayiwtc Promiwrlgradamwaboringv"Iman- for access trnskla nna tank. All Carbc holo.Furry` ght.on*'p1evA Cast s'. Steel vonswation, Bohm.muss and ga. Iron ring and skirt, PennwwR alrAck k kets are avaiabit. Double Punas w1angie an whim wtlr"decal with version is deo avaltabla. (912DP ar FiG Sts brans wap piste ler stamping well FIG 81st 8200p) numbw. Stainless Steel bolt machined with Sig-s-Neck 820-;Yeo a-ringgroove,rrise+to$myonovver gJZE wMah wizen removed, Aube"L10tfd Typs Regis1E'...-- ................................................................------ --55 4t 9*x7'......_........_......_...........N.Y.......__..._................................3z No 20-.._....................•---•-................._................................-..._._S3 It 12-:tr.... ................w.. .. ...._..__.....................................70IM 2A...... .................•... .......................... ....._._ .....�....ao�t .... Dales U"141TYPE d2 It PIG$19 A-$Wm as FIG$19.but whin AluMkWM cover. 18',.,,N....._._.........................................••........•-� .�»••.. .. ....• 1r................._.....•.1.................._..._.N..N,........,...........N.N,N..... so lbs 20-N...._................................,.....,..........._....... ......................._. .....71 !t ....Y.w.•N•_...•._Y..,nN.._.w....._.......N.r.•N• `w.__..•..•..ur•N••.___-9�i.t 356 & 357 B F420 424'Ee 524 FLUSH FILL BOX ; TradasonolfEbox.Posttendardriser SQUARE MANHOLE pips with cover 11oft w th driveway surface.Gaaketpmvldeswater-dghl Square box to provide moose to equ. sed. Wrench Atnnislved wiM box. FIG A2014U mem ek.on driveway surface. RG 4m&424•Knodadoom style FIG 3% "Vice at d"*, Rowfires riWtirr .�........._ . . ..._— aasvatbly at jobslbe. NOTE: U.S. Fd ' 'v U5T R*Fjwww roWke spill son- R3 324- . GOlon type used tainrrNnt far fid pow These T oho dew-up. Boit down, gosk-e b't�ee at fill bmes,when used locover v/ITh 2 e deep SM. Pre-e *Ww.wit no comply. seretbled,all welded eonetruabn. FIG 357 ID NG 334 MQ an s-seslaiDrooi leve Wife now CAU nen inose(rim►.ons coverat Iron 1lMfl M-to Qi.>5rirt-3W 4-way Roar Plata fcwe) iN1<m Burs"0101041. Do*often cosier,9una44 0AK Zp'x IIO'x 10'dsnsp skirl•.._ �. _ sat sin WE KW no waleff AG 424.14 ilL sldit-3"4-way F1W Plate Owen 7._..__.N.._....... 3_111 as 2-�..N_._--_-----«»„_Y 12.75 pe u'=2e x 1a'deep skirt........_...._.._.__.........N.N......_._._..N 97 ..«..N.,. to •� .�.ps be pili 04-14 ga,s W-3W 4�y Rdw Ptote(cover) ..ww•_,•••,•••••rN••.INNNI•MI.M T.7a Res ��••NN•._YNMM.rNNMMYMN•w.. � 4•_ _ _t3 b 4'-,...•..-..-......_.N........33.i aK W x W X 24.4WD otdtt..N«.N............_._... 30 12/'07/2001 08:12 6127845236 CHETS SHOES 4 _. 10/24/2001 14:087633237614UT 1 1 1 JF ion & Safety Manual Owner S OpeTat S 1008 JMP SEBIE For models, FR700, FR701 a !' rte'• � ...+� 1 t t t Model FR701 Model FR700 OUTSTANDING FEATURES I } •Upto18GPM168LPM •U L and C-UL listed pumprn d motor optional 220/2 *Fu!! 1/3 HP 1 14O VAC•50160Hz *Thermal overload protector i •Heavy duty double pole switch •Integral check valve !� -Built—in bypass valve 12/07/2001 08:12 6127845236 CHETS SHOES � 1 `e y0/2A/2001 14:08 7633237614 JP EQUIP PEtGE e3 _ � I Gip Lmi�M i•,i;;t,Tm� The f ill-Rite.7008 UL' listed pumps' are positive U displacement, direct drive pumps. Depending on ` installation and product viacoaity, MGM pumps can deliver ueerFill-kite customer. up to 1a gallons of fluid per minute. Their rugged, yet congratulations on your purchase of Fill-Rite's new Series lightweight design, makes for a long life of trouble-free TOOK Pump, we at p&-Rite have bunk our wor•1dwide operation. reputation by designing the finest and roost rellabte pumps available in today's ma"l. Your new pump was designed with pride by some of the best and most experiencedfluidcontrolexpertsavailable.Weuse Fill-Rite 700E pumps'safety are proven by their listing with: the most advanced technology oossible to Give you a eump with the superiorityyou deserve and the quAtyyou've come Underwriters Labo ratories Inc.,anational►y recog- to expect from Fitt-Rita products. O nized indenendwntorganiz,-ttion for product test- >n ing to ensure publio safety. Also recognized in 111511110 Canada. George P. enkins Co Yresiaent Canadian Standards Association, a Canadian organization for product testing to ensure public Safety. Electrical wiring should be done by a licensed eiectri- .pull 1/3 HP 220/240 VAC-50/60Hz motor until if, etc:uurUariut: will'i ap- -Flow meters in U.S. gallons or liters proved electrical codes. .Pedestal adapters for underground tank installations pump should be properly .Nozzle holders for automatic nozzles grounded and a rigid conduit -Automatic nozzles should be used when install- ing electrical wiring. Im. Recommended Automatic Nozzles: proper use or installation of Husky 1-GS, 1-A & 1+Vill this product can cause seri- OPW 11-A& 7-11 ous bodily injury or death. NOTE: Lasing an automatic nozzle will reduce flow rate. See flow curve. To ensure safe and efficient operation, it is essential WIN to read and follow each of these warnings and precautions. Design Features: •Inlet: Z'male NPT on bung,1"female NPT on suction ripe 1. To prevent damage to pump, do not operate -Outlet: .%•' NPT without tho chock valve(F2661)or the check valve -Built in chock valvo, bypacc and preceure relief valvee substitute (F7_679) in place. CAUTION: DO NOT INSTALL ADDITIONAL FOOT 2. Do not smoke near pump or use pump near an VALVE OR CHECK VALVE DURING INSTALLATION open flame. Fire could result. WITHOU I PHhSSUHE HtL1tF VALVE. HOUSING OR 3. A filter should be used on pump outlet to ensure PLUMBING CRACKING MAY RESULT. that no foreign material is transferred to fuel tank. •FI irnished with 111..listed-%'x 12'hose and manual nozzle 4. Take motors needing service to an authorized *Security: Pump equipped for padlocking repair shop or return to factory to maintain -Overall Dimensions: "explosion proof' integrity. -Models FR700: 14-wide x 'I 1"nigh x 12"deep 5. The pump motor is equipped with thermal -Models FR701- 14"wide x 11"high x 14,deep overload protection. If overheated.Itwill shut itself ,Explosion proof motor off without any damage to the windings. Be sure •1/3 HP 115 VAC-60hz dual motor, 1725 RPM,5:5 amps st to turn off the pump power if this occurs. As the 115 VAC .motor cools,it will start without warning if powcr io -Thermal overload protcction on. •Ball bearing construction; no greasing or oiling required •Heavy duty switch _ 2 12/07/2001 08:12 6127845236 -- n CHETS SHOES -0P4 k '1:7 • -10/24/2001 14:08 7633237614 JP ECdUiP PACS. ( 0 sl tog ., 4;.zH.�� O' / `� ` .vii-1_ � �=•� _ \� 5' / r . LIJ LL 0 k �,r a ;\ W