Loading...
HomeMy WebLinkAboutCorrespondence from MillerDunwiddie ZULU LA) -147P9 4W MILLER DUNWIDDIE MEMORANDUM 123 North Third St., Suite 104 Minneapolis,MN 55401-1657 telephone: 612.337.0000 fax: 612.337.0031 www.millerdunwiddie.com Date: April 11, 2005 Project: Wayzata Country Club Addition/Renovation RE: Smoke-Control/Draft-Control Devices at Elevators To: Lyle Oman, Building Official City of Orono 2750 Kelley Parkway Orono, MN 55356 From: David Kulich This memo and the attached letter from Tate Halvorson at McGough Contraction is a follow-up to our meeting at the Wayzata Country Club on March 31, 2005 in regard to the smoke-control/draft-control devices at the elevators. We concur with Tate's letter that the smoke-control and draft-control devices are unnecessary at our project and would ask that you further review this situation. Please call with any questions. We will wait for a response from you. Thanks. C:\Documents and Settings\loman.000\Local Settings\Temporary Internet Files\OLK9\memo 041105-Lyle Oman.doc McGough Five Generations Building Confidence TO:David Kulich,Project Architect, Miller Dunwiddie Architecture FROM:Tate Halvorson,QA DATE: 4/4/05 RE: Smoke-and Draft-Control of Wayzata Country Club Elevators We would like to propose to you, for your concurrence,and the Building Official of Orono that the two elevators in the Wayzata Country Club addition and remodel project be allowed to be installed without the smoke-control and draft-control features that were originally anticipated. The State of Minnesota has adopted the 2000 International Building Code(IBC)as the current Building Code. As part of the adoption,a number of amendments were included and one of these amendments has had unexpected consequences. The State Amendment designated as Section 707.7(below)has been interpreted by the State as overriding IBC 707.14(below)which eliminates the requirement for elevator lobbies(and smoke-and draft-control)for sprinklered buildings less that 5 stories via exception 4 in this section. 707.7 Openings. Openings in a shaft enclosure shall be protected in accordance with Section 714 as required for fire barriers and listed in Table 714.1. Such openings shall restrict the movement of smoke through openings using smoke-control and draft-control assemblies in accordance with Section 714.2.3.2 and shall be self-closing or automatic closing by smoke detection. 707.14 Elevator and dumbwaiter shafts. Elevator hoistway and dumbwaiter enclosures shall be constructed in accordance with §707.4 and Chapter 30. §707.14.1 Elevator lobby. Elevators opening into a fire-resistance-rated corridor as required by§1004.3.2.1 shall be provided with an elevator lobby at each floor containing such a corridor.The lobby shall completely separate the elevators from the corridor by fire barriers and the required opening protection. Elevator lobbies shall have at least one means of egress complying with Chapter 10 and other provisions within this code. Exceptions: 1. In office buildings, separations are not required from a street floor elevator lobby provided the entire street floor is equipped with an automatic sprinkler system in accordance with§903.3.1.1. 2. Elevators not required to be located in a shaft in accordance with§707.2. 3.Where additional doors are provided in accordance with§3002.6. 4. In other than Groups 1-2 and 1-3, and buildings more than four stories above the lowest level of fire department vehicle access, lobby separation is not required where the building, including the lobby and corridors leading to the lobby, is protected by an automatic sprinkler system installed throughout in accordance with§903.3.1.1 or §903.3.1.2. We have had a number of discussions with Plan Review personnel, in the State Building Codes and Standards Division,who are intimately familiar with the current code adoption process and they have confirmed that it is their intention and recommendation to delete Section 707.7 from the next code cycle. Per the original intent of 707.7,they will probably develop additional code language that insures that buildings 5 or more stories will be required to have elevator lobbies or other smoke-and draft-control protection,even if fire-rated corridors are not required. We do not think that the State ever intended to be so much more restrictive than IBC Section 707.14 and their proposal for changing 707.7 demonstrates,we believe,that we are correct. The following points may be appropriate for consideration: 1. As you are aware,the Country Club is basically a 2-story building with a basement(called ground floor) and a small sub-basement. 2. Elevator B is the only elevator with more than 25 feet of travel. As a result,this elevator will be vented and have draft curtains with smoke detectors. Interestingly,the draft curtain requirement is expected to also be eliminated in the next code adoption. 3. The two elevators are very remote from each other and only have 2 levels in common. Thus there will be very little"stack effect"within the building. 4. Elevator A connects the following: (a)The basement or ground floor area separated by a hallway ramp system from any major use areas. This passage to the elevator and elevation rise would tend to pocket smoke and keep it away from the lower lobby. Smoke gaskets could be added to the 3 doors(normally locked)adjacent to the elevator to further insure that smoke will not likely reach the elevator (b)The west lobby area of the 1st floor. This area is enclosed(though not fire-rated), similar to a lobby and would limit the passage of smoke to other areas of this level. (c) 2nd floor: A very small office area on the 2nd floor which is remote from the exit and the boardroom. The door that separates the elevator from the exitway and the boardroom could be gasketed and have a closer provided if one does not exist. 5. Elevator B (with the draft curtain and smoke detection)connects the following: (a)The small receiving area in the sub-basement. This area is only about 2600 square feet and includes fire-rated enclosures for the Trash Room,Elevator Equipment Room and the Electrical Room. There are also several low hazard freezers. (b)The employee breakroom,on ground floor,which is basically like a large lobby with no direct connection to more populated areas. Smoke gaskets could be added to the doors to the Seasonal Storage,the Laundry and to Door 041 C which connects to the remainder of the floor level. Smoke gaskets could be added to the employee restrooms but everything,except clothes in metal lockers, is pretty much non-combustible in these rooms. (c) The most remote portion of the kitchen. The entry doors to the Ballroom or Casual Dining are over 60 feet away from this elevator. Smoke gaskets could be added to the adjacent Dry Storage Room 120 and Storage Room 121,but it would not seem to be necessary since this is the highest level of this elevator. The kitchen has 6 possible exits for quick escape. Further,all the kitchen surfaces are cleanable should smoke somehow make its way up the elevator from below. CONCLUSION: We believe that special smoke-control and draft-control devices are unnecessary in such a low-rise,sprinklered building. We propose to upgrade the smoke-and draft-control of adjacent enclosures similar to elevator lobbies, in lieu of the apparent,soon-to-be-deleted,code requirement. To provide these expensive devices on the elevators in the Wayzata Country Club seems,to us,to be a real disservice to our client. To have to maintain them or to possibly be able to remove them in less than a year seems to be a totally unnecessary condition. If you agree with this assessment,we would greatly appreciate it if you would concur and pass this on to the Orono Building Official. We think this qualifies as a common sense type of equivalency. Thanks much for your consideration. 0 McGough live Generations Building Confidence TO: Mr. Lyle Oman,Building Official,City of Orono FROM: Tate Halvorson,QA CC: David Kulich,Project Architect,Miller Dunwiddie Architecture Paul Egertson,Project Manager,McGough Dave Krings, State Building Codes and Standards Division Gerry Norman, State Building Codes and Standards Division DATE: May 9,2005 RE: Wayzata Country Club Elevator Smoke-Control Based on your desire to have a State opinion on the issue of smoke control for the Wayzata Country Club's elevators and with the approval of our Architect, I called Dave Krings Monday morning. Dave called me back immediately and very graciously agreed to meet with me in the afternoon. He asked Gerry Norman if he could attend and we all met at 2:00! We discussed the status of the next code adoption cycle and the possible changes to the codes through amendments to the 2003 IBC. Gerry indicated that he is on the committee working on these amendments and the committee has recommended the deletion of the amendment,IBC 707.7. As you know this amendment has, in effect,overridden the provisions of IBC 707.14 which allows the elimination of elevator lobbies and smoke control for low-rise elevators. Gerry indicated that it is highly likely that the committee's recommendation will be upheld but it is not a certainty. There are pending amendments to the 2006 IBC that will be voted on at the ICC Annual Business Meeting(ABM)in September that may affect the final outcome. Additionally,proponents for the present amendment,especially manufacturers of products that achieve the smoke control for elevators,may be successful in seeking a public hearing,during the adoption process,and have this amendment retained. One concern of many Building Officials, including myself, is that the final code adoption should address the issue of smoke control for elevators in buildings with five or more stories even if rated corridors are not required. We discussed the specifics of the Wayzata Country Club while looking at the floor plans and I indicated our desire to eliminate some or all of the"Smokeguard"systems on the elevator openings based on the above possible code changes and the limited nature of any"stack effect"in a low-rise structure such as the Country Club. I also discussed the possibility of providing smoke gaskets on doors adjacent to the elevators area to provide lobbies or lobby"areas". Both Dave and Gerry were reluctant to endorse this approach given the present codes and the uncertainty of changes. However,upon further discussion some other options did develop. I will note,separately,the options that were developed. Elevator A: Elevator A is the elevator being added in the existing building. It travels from ground floor level through the 1st floor to the small 2nd floor office area. The travel is less than 25 feet. It was noted that the 1st and 2nd floors are open to each other via both an adjacent open stair and a large floor opening and it was agreed that it did not make much sense, since smoke and hot gas from a fire rises,to worry about any smoke developed on the 1st or 2"d. Since the elevator at the ground floor level is adjacent to mechanical and storage rooms,both Dave and Gerry were comfortable with supporting the idea of providing smoke-and draft-control at the lowest,most critical level. Since Wayzata Country Club has requested an additional door be added to close off this area on the ground floor level,visually,from the other areas, it is our proposal that we construct this area as an elevator lobby. All the adjacent rooms are sprinklered and have been constructed to resist the passage of smoke per 2737 FAIRVIEW AVENUE; NOR I II sr PA( I.,. MINN1 S0.1 A 551 1;-1 33'%2 MOM':: (651) 633-5050 FAX: (6513 633-5673 McGough Five Generations Building Confidence the requirements of incidental uses.The doors are all 1-3/4 inch solid-core doors and they will be provided with smoke gaskets. 1-3/4 inch doors have traditionally been considered more or less equivalent to 20-minute rated doors and it was pointed out during the meeting that the 2003 IBC has"corrected"the language regarding elevator lobbies by changing the wall requirement from a"fire barrier"wall to a"fire partition"wall. Thus,when the adoption of the 2003 IBC is complete, only a 20-minute door will be required for elevator lobbies regardless of the number of stories. Thus we seek your approval to just construct the described elevator lobby on the lowest level and recognize that the upper two levels,open to each other in this area,can not be effectively separated. Elevator B: Elevator B is the elevator in the new addition that travels from the sub-basement through the ground floor to the 1St floor. The travel is more than 25 feet so an elevator vent has been provided. It was acknowledged that the intent of the smoke-and draft- control provisions for elevators was not necessarily to prevent smoke from entering the elevator shaft but,rather,to prevent smoke from migrating to other floors from the level of development. Therefore, it should be possible to either provide a positive or negative pressure within the elevator shaft to control the movement of smoke. A positive pressure within the shaft could prevent the smoke from entering the shaft and a negative pressure might be utilized in conjunction with an exhaust fan, in lieu of the elevator vent,to send smoke within the shaft out through the top of the shaft to the exterior. Dave and Gerry indicated their concurrence, in principle,of this approach but also noted that it would be up to the AHJ to determine if this was appropriate and what other considerations would be necessary. After consultation with our Mechanical, it was decided that pressurizing the elevator shaft would be the most effective method. If you consider this an acceptable option,the design team will put together a final design for your approval. The system will be designed to only operate when one of the local smoke detectors in the adjacent draft curtain detects smoke. It will then pressurize the shaft with a fan sufficient to keep smoke from migrating into the enclosure. The fan will draw outside air for this purpose and the opening into the shaft will be protected by a combination damper. There will be a keyed control for the fire department. If you agree that we may take the approaches noted,we will work with Miller Dunwiddie to put a final design package together as soon as possible. I have copied Dave and Gerry with this memo so they can let you know if I have not correctly interpreted their comments. Thanks much for your assistance in this matter. We look forward to your response. 2737 FAIRVIEW AVENUE NORTH SI'. PAUL. MINNESOTA 55113-1372 PHONE: (651) 633-505O FAX: (651) 633-5673 a d l3 Ao-f -734 �t-1 MILLER DUNWIDDIE MEETING MINUTES 123 North Third St., Suite 104 Minneapolis,MN 55401-1657 telephone: 612.337.0000 fax: 612.337.0031 www.millerdunwiddie.com Copies to: FILE Craig Lau, Jon Jasken, Paul Egertson, Steve Gentilini, Dan Zitzer, Mike Ramerth, Steve Carlson, THOSE PRESENT Code Review/Informational Meeting City of Orono Wayzata Country Club Wayzata (Orono), MN WCC 0301 This Next Minutes Prepared By: Meeting Meeting Date Start End Date Start Time Michael Bjornberg Time Time 02/19/04 9:3I a.m. 10:30 a.m. Attended By: Name Firm/Dept. Phone/Pa Fax Email ger Lyle Oman City of Orono 952.249.4600 952.249.4616 loman@ci.orono.mn.us Janice Grundlach City of Orono 952.249.4623 952.249.4616 jgundlach@ci.mn.us Sherwin Nelson McGough 651.633.5050 651.633.5673 snelson@mcgough.com Tammy Black _ MDA 612.278.7732 612.337.0031 tblack@millerdunwiddie.com Michael Bjornberg Miller-Dunwiddie 612.278.7702 612.337.0031 mbjornberg@millerdunwiddie.com (MDA) A summary of this meeting includes the following items: OLD BUSINESS Item Description Action By none NEW BUSINESS Item Description Action By • February 23, 2004 -2 - MEETING MINUTES Purpose. The purpose of this meeting was to update the City of Orono as to the scope and progress of the Wayzata Country Club proposed project. It was 1.0 noted that the design team is completing the Schematic Design Phase and that a contractor had been pre-selected by the Owner (McGough Construction.) Schedule. MDA noted that the Schematic Design is to be completed in 2 weeks and estimated by 1.1 McGough. We anticipate completion of Design Development in early April 04, with construction to begin in June/July 2004 and complete April 2005. Plan walk-through. City of Orono Tammy Black presented the floor plans of the proposed project, noting that they are works in progress, but expressive of the scope and intent of the project. Included in the floor plans was a code/exiting plan of the 4 levels. There was 1.2 discussion about required exiting of the upper level administrative office area. Lyle indicated that a corridor through the mechanical space may be required. It was noted that it may only require one exit, but the City of Orono was to review this area further and advise the design team. Approval Process. Team MDA inquired about the approval required for this project. Janice Gundlach noted that a Conditional Use Permit/Amendment would be required and that this requires City Council action. The project is in a zoned Residential Area and is a Commercial use. She noted that the following needs to occur: • The City needs a survey, plans and elevations of the intended project from 1.3 MDA. Janice noted the process would require Planning Commission review (one month) and City Council action (2 months.) The following dates were provided for such action: April Planning Commission review (March 17 submittal) provides a May 10 City Council review/approval date, with a permit issued shortly thereafter. MDA noted that the required information was ready for submittal and review. C:\Documents and Settings\Ioman.000\Local Settings\TEMP\WCC Code Review notes 021904.doc • February 23, 2004 - 3 - MEETING MINUTES Review Agencies. MDA inquired as to the other regulatory/review agencies involved in this process. The following was noted: • Health Department: Hennepin County. • Storm Water: Minnehaha Creek 1.4 Watershed. • Mech/Elec: State Inspector. • Sprinkler System: Orono Fire Marshall (Bill Myer.) • Temporary exiting plan: Lyle Oman and the Fire Marshall The above represents the writer's impressions of the meeting. Any errors, omissions and/or discrepancies should be reported to them promptly. C:\Documents and Settings\Ioman.000\Local Settings\TEMP\WCC Code Review notes 021904.doc 1 -3 • MILLER DUNWIDDIE MEETING MINUTES 123 North Third St., Suite 104 Minneapolis,MN 55401-1657 telephone: 612.337.0000 fax: 612.337.0031 www.millerdunwiddie.com Copies to: FILE Craig Lau, Jon Jasken, Paul Egertson, Steve Gentilini, Dan Zitzer, Mike Ramerth, Steve Carlson, THOSE PRESENT Code Review/Informational Meeting City of Orono Wayzata Country Club Wayzata (Orono), MN WCC 0301 This Next Minutes Prepared By: Meeting _ Meeting Date Start End Date Start Time Michael Bjornberg Time Time 03/04/04 9:30 a.m. 10:30 a.m. Attended By: Name Firm/Dept. Phone/Pa Fax Email ger Lyle Oman City of Orono 952.249.4600 952.249.4616 loman@ci.orono.mn.us Janice Grundlach City of Orono 952.249.4623 952.249.4616 jgundlach@ci.orono.mn.us Sherwin Nelson McGough 651.633.5050 651.633.5673 snelson@mcgough.com Tammy Black MDA 612.278.7732 612.337.0031 tblack@millerdunwiddie.com Michael Bjornberg Miller-Dunwiddie 612.278.7702 612.337.0031 mbjornberg@millerdunwiddie.com (MDA) A summary of this meeting includes the following items: OLD BUSINESS Item Description Action By MDA Schedule. MDA noted that the Schematic Design is to be completed in 2 1.1 weeks and estimated by McGough. We anticipate completion of Design Development in early April 04, with construction to begin in June/July 2004 and complete April 2005. 1 2 Plan walk-through. Orono Tammy Black presented the floor plans of the proposed March 8, 2004 -2 - MEETING MINUTES Item Description Action By project, noting that they are works in progress, but expressive of the scope and intent of the project. Included in the floor plans was a code/exiting plan of the 4 levels. There was discussion about required exiting of the upper level administrative office area. Lyle indicated that a corridor through the mechanical space may be required. It was noted that it may only require one exit, but the City of Orono was to review this area further and advise the design team. Approval Process. MDA MDA inquired about the approval required for this project. Janice Gundlach noted that a Conditional Use Permit/Amendment would be required and that this requires City Council action. The project is in a zoned Residential Area and is a Commercial use. She noted that the following needs to occur: • The City needs a survey, plans and elevations of the 1.3 intended project from MDA. Janice noted the process would require Planning Commission review (one month) and City Council action (2 months.) The following dates were provided for such action: April Planning Commission review (March 17 submittal) provides a May 10 City Council review/approval date, with a permit issued shortly thereafter. MDA noted that the required information was ready for submittal and review. NEW BUSINESS Item Description Action By Purpose. The intent of this meeting is to conduct the Preliminary Application Meeting for the Wayzata Country Club 2.0 remodeling/addition. Janice Gundlach indicated that the project is in a residentially zoned area and as such requires a Conditional Use Permit. Janice saw it as more of a formality, than a problematic issue. The official address is noted to be: 200 Wayzata Boulevard. Project Review. MDA reviewed the project scope with Janice. Janice noted that 2.1 the project is not in a hard cover zone, nor in shore land zone. We reviewed the existing survey information and noted that the building survey is currently being updated. 2.2 Submittal Requirements. MDA C:\Documents and Settings\Ioman.000\Local Settings\TEMP\WCC Planning-Code Mtg notes 030404.doc March 8, 2004 -3 - MEETING MINUTES Janice requested that: • One full size plan set for Janice, • one 11x17 set floor plans, elevations and site plan clearly indicate the existing and the proposed, • a brief narrative description of the project (including parking,) • the adjacent property owners list ( to be attained from the county,) • legal description (city has already,) • a check for the noted amount, • signature of property owner representative, • to be submitted by March 17, 2004 at noon, • Representative to present project to Planning Commission at April 19 meeting (6 p.m.) Janice noted that the agenda sequence is determined by the sequence which submittals are received by the city. Code Discussion. Orono After the Planning meeting, MDA met with Lyle Oman, Building Official, to review the project and ask for clarifications on exiting issues. Lyle reviewed the elevator exceptions relative to 2.3 the lobby requirement and noted that he felt there are no elevator lobbies required on this project. Lyle is to advise MDA whether a rated elevator shaft enclosure is required. MDA asked about clarification for exiting on the upper level — Lyle to continue his review of this area. The above represents the writer's impressions of the meeting. Any errors, omissions and/or discrepancies should be reported to them promptly. C:\Documents and Settings\Ioman.000\Local Settings\TEMP\WCC Planning-Code Mtg notes 030404.doc i9/ MILLER DUNWIDDIE MEMORANDUM ARCHITECTURE'rf PRESERVATION 123 North Third St., Suite 104 Minneapolis,MN 55401-1657 telephone: 612.337.0000 fax: 612.337.0031 www.millerdunwiddie.com Date: June 4, 2004 Project: Wayzata Country Club Addition/ Renovation RE: Document review by Tate Halvorson To: Paul Egertson From: Tammy Black GENERAL COMMENT: It was our understanding from the initial meeting with the City (Sherwin Nelson attended for McGough), that the City was "OK"with several options. One of the options was to consider the overall building as a V-B (unrated combustible construction) with an automatic fire extinguishing system (sprinklers) throughout to gain an additional story and area increases per the IBC. This is how the height and area allowances appear to be determined on Sheet T102. If this is the case, then we do not understand why the addenda are now calling for all new lumber and plywood in the addition to be Fire-Retardant Treated Wood (FRT). Even though the majority of this addition is steel and precast concrete, the addition can still be classified as V-B construction (and should be since it is not separated from and standard wood should be allowed. The reason for changing to FRT wood was specifically to help reduce the amount of`combustibles"in concealed spaces and therefore reduce the number of sprinklers required. This is a concern in the walls and roofs of the "attic"spaces we are creating. Other areas that don't fall under this category can be constructed with standard wood. 1. Sheet T102: We noted that the 2003 IBC is indicated as the code this project was designed under and that incidental storage rooms greater than 100 square feet are indicated as just needing sprinklers per the State's PR- 03 memo. Has this code and/or"interpretation" or"equivalency" been approved by the Wayzata Building Official? Also, we assume that the walls of these storage rooms will need to resist the passage of smoke per IBC 302.1.1.1. Is this a correct assumption? Use of the State's PR-03 was mentioned to the local code official. A thorough code review by the city is pending. MDA will make the changes necessary to wall construction and doors as required to resist the passage of smoke. 2. Sheet A100: Does the Sump Room SB10 require a rated door and "front"wall as indicated? No. The door and north wall of the Sump Room do not need to be rated. 3. Sheet A101: A. We noted that Doors 020 and 021 are indicated as 45 minute doors and the"front"wall of these spaces are designated as 1-hour fire-rated construction. Based on the above item 1, can any or all of these ratings be eliminated? Yes. Doors 020, 021, and 016 can be standard doors without a rating. The walls can be standard construction without a rating(similar construction to wall type 4 without insulation). B. It appears that a gate or barrier and discharge identification is required by IBC Section 1005.3.2.3 in Stair C. If so, please provide details. Both the ground floor and sub-basement are considered a level of discharge. Therefore a gate or barrier is not required. WCC0301 June 4,2004 Wayzata Country Club Addition/Renovation Page 2 C. We have not noted a water fountain in the women's locker room. Is a water fountain to be provided similar to the men's locker room area? No. It is not required. Ice water and cups are provided at the sink in the Women's Lounge#026. 4. Sheet A102: A. Has the exit plan and door swings shown from the Bar Deck been approved by the City? No comment has been made to date with preliminary code reviews by the City. Final code review by the City is pending. B. Are the rated doors and enclosure required for the closet adjacent to"corridor" 122? This appears to meet the requirements for exiting through an intervening room and may not need to be rated. (Sprinklers in the closets have been noted, appropriately, in one of the addenda.) The rated doors and enclosure are required due to the electrical panels and equipment housed within. C. The glass in the W06 frame adjacent to Door 111A appears to need safety glass. Please review. The panel of glass immediately to the west of Door 11A should be modified to include safety glass. D. The glass adjacent to Door 111B and the W04 glass on the landing of Stair C may be subject to interpretation. Has this been approved by the City without safety glass? No comment has been made to date with preliminary code reviews by the City. Final code review by the City is pending. 5. Sheet A103: The 2nd exit from the Northwest occupied office area appears to have been eliminated. Has this been approved by the City? Yes. The code official approved it as long as the total occupant load at this level is less than 50. 6. Sheet A130: A. Detail 4B: (1) Per our previous letter it still appears that an ambulatory stall is required in Men's Locker Room 032. Mn Accessibility Code Section 1341.0460, Subpart 4 requires an ambulatory stall when there are 6 water closets or a combined total of 6 water closets and urinals. We have had this issue on many previous projects and believe this detail should be changed so that all trades involved will be aware of the changes needed. (Please note: the depth of the stall varies by type of w.c. [Figure 30b] and horizontal and vertical bars have been required on both sides.) Unfortunately, I never received a letter prior to this one. One of the toilet stalls will be modified to conform to the requirements for an ambulatory stall with required grab bars. New detail pending. (2) Has the City approved a separate accessible lavatory setup for the disabled? Will it have all the same amenities as the other 2 stations? The lavatories on the west wall of the Men's locker room are to be accessible per the note on 4C/A631. They will have the same amenities as the other 2 stations and will be similar to 4D/A631 with two accessible lavatories.. B. Detail 6B (Typical): The accessible stall may not have a"to scale"toilet in the drawing but we would recommend that a dimension of 4 feet from the front of the water closet to the front toilet partition be provided in order to eliminate possible errors during ordering, etc. (MN Accessibility Code 1341.0450, Subpart 3) The 4'-0"dimension will be added as a typical note in all accessible stalls. C. Detail 2C (Typical): We would recommend, for the previous reason, that the dimensioning of the door opening into the accessible stall clearly indicate that the 32 inch clearance is to the door when the door does not swing 180 degrees out of the way. This comment is confusing. I will note the required width at accessible stall doors be 32"min. from the face of the door to the opposite jamb. (This should apply whether the door swings 90 or 180 degrees...?) U:\WCC\WCC0301\Documentation\H-Prime Contr\H1 Contractor Correspondence\Document Review.doc WCC0301 June 4,2004 Wayzata Country Club Addition/Renovation Page 3 r7it-D. Detail 6C: This may be subject to interpretation due to the wall "jog"adjacent to the door in this detail, but it does not appear to meet the 18 inch side clearance required by the MN Accessibility Code. Section 1341.0442, Subpart 6 requires a door to have no more than an 8 inch recess. MDA will shift the north bay areas of the room 2"south. This will alter the `jog"to a 7%"recess, therefore meeting the intent of the code. It will also create a plane difference or a step between the first and second floor, which is fine. As this is Alternate A2, no further details or modifications will be drawn until the alternate is accepted. o•kc- E. Details 1D and 1 E: Do these reception desks fall under the requirements of MN Accessibility Code Section 1341.0720, Subpart 1? If it is believed that they do not, has the City approved this design? Will there be other"desks"or similar in our scope of work that may need an accessible portion? These counters do not fall under the noted requirement since they are more a "security"counter than"assistance" counter. No comment has been made to date with preliminary code reviews by the City. Final code review by the City is pending. There are no other"desks"in this project, only two bars and two pieces of furniture used as host stations at the restaurants. 7. Sheet A330(Typical), also 5D/A650: What are the deflections that we should expect in the new construction? We like to check w/structural in order to provide the most efficient design of the fire stopping systems. Detail 5D/A650 indicates a typical wall joint in plan view. No substantial deflection is expected along wall panels. A detail similar to this showing the top of a stud wall meeting a precast plank structure should show a slip joint capable of allowing for 3A"max. vertical movement on this project. MDA to issue typical detail for clarification. 8. Sheet A331, Detail 2E and 1A/A350: How should the vapor barrier be maintained continuous at this section? This detail should be modified to show the vapor barrier continuing down past the floor on the south side of the laminated wood beam and under the 2X10 wood joists, until it connects with the vapor barrier that exists (hopefully) in the existing north wall of the Pro Shop. Batt insulation will be removed and rigid applied on the underside of the vapor barrier with plywood, metal lath and stucco finish. MDA to issue detail. 9. Sheet A380, Details 3D and 6D: Please clarify the extent of vapor barriers and/or waterproof membranes in these details. Please Note: Detail 2D/A382 indicates a typical detail with a vapor barrier continuous over the precast. This does not seem to be appropriate for 3D. If a vapor barrier is to be "exposed", does it need to be a Class I flamespread material? The vapor barrier at the `floor"level will continue from the roof area under the concrete topping and terminate at the wall assembly. The concrete topping will be considered more of a "walking"surface than a structural surface. The detail should be modified to cover waterproof membrane at the wall with gypsum board. This should eliminate any exposed material in this area. MDA to issue detail. 10. Sheet A381: A. Details 5B and 4E indicate that these spaces are vented per 4E/A382 and 5E/A382. Please clarify venting, insulation, vapor barrier and waterproof membrane. Modified details will be issued by MDA. B. Detail 6E: If this floor is a walking surface, should additional protection be provided at the edges or should the flooring be wider? The plywood"flooring"should extend to the walls of the "dormer". 11. Sheet A382: A. Detail 2B: Should the flashing in this detail be above the standing seam roof such that it will prevent water from entering beneath the roof system? Yes. The flashing should be above the standing seam roof, and the building wrap should lap the vertical flashing. MDA to issue a detail for clarification. B. Detail 4E: It is not clear to us how venting is achieved. Is attic venting intended? Shall the plywood, membrane and flashing be held back? If so, how much? U:\WCC\WCC0301\Documentation\H-Prime Contr\H1 Contractor Correspondence\Document Review.doc WCC0301 June 4,2004 Wayzata Country Club Addition/Renovation Page 4 This detail is not intended to be an attic venting detail. The venting is provided for the breathable shingle underlayment only. C. Detail 6B: Please explain the purpose of this "Area Separation Wall"and the extent of this closure per the initial discussion point of this letter. Is this essentially a draftstop? Are other draftstops required per IBC Section 716.4? This wall is acting as a draftstop to separate existing combustible and new noncombustible construction in the attic. Sprinklers will be provided in the combustible concealed attic spaces, but not in the noncombustible spaces. Draftstopping is not required throughout this building as it is provided with an automatic sprinkler system and the new areas are constructed of noncombustible construction. 12. Sheet A400, Detail 3E (also 2E/A401): We believe the guard spacing should be less than 4 inches per IBC Section 1003.2.12.1 (such that a 4 inch sphere can not pass through). However, drawing does not appear to be to scale; please provide revision as necessary. Details 3E/A400 and 2E/A401 should be modified to indicate guard spacing at 4"o.c. in lieu of 4"max. spacing between guards. 13. Sheet A401: A. Detail 1D and 2D: With more than 25 feet of travel, it appears that an elevator vent is required. Elevator B travels between the sub-basement and the first floor, totaling 25'-8" A vent is required. B. Detail 3B: What is the assembly we should provide to achieve the top closure of the elevator shaft? Are there options other than spray-applied fireproofing? The assembly is required to be 1-hour rated. This assembly can be achieved any way you would like, be it precast plank, metal deck with fire-proofing, or light gage studs with gypsum board. 14. Sheet A500 Door Schedule: The secondary exit doors (Drs 26 and 43B) from the locker rooms have panic hardware but the main exit/entry doors do not. Do these doors require panic hardware (if latching)? (The code analysis indicates more than 100 occupants.) These are latching doors and panic hardware should be added at Doors 024 and 036. 15. Sheet A501, Detail 1C: It appears that a header is required in this wall section. Shall we provide? Yes. Please provide as required. 16. Sheet A630, Detail 2D: On what levels should pictorial emergency exit signage be provided by the elevator call button? No signs should be required. 17. Sheet A631: A. We have not located any detail for accessible urinals. Please provide detail and location of accessible urinals in each restroom that has at least one urinal. The urinals we have selected will meet ADA requirements. Details will be provided by MDA indicating mounting heights and locations. B. We have not located details for the accessible showers including grab bars, length of adjustable shower hoses, etc. (?) Detail will be provided by MDA. 18. Sheet A632, Detail 2B: The sconces in this detail appear to be too low to meet the requirements of MN Accessibility Code Section 1341.0424, Subpart 1 for protruding objects; in that they protrude more than 4 inches and are lower than 80 inches. Can they be raised or revised? Once the final fixtures are chosen, we are intending to set back the wall above the chair rail as required to make sure the sconces do not protrude more than 4"into the arched area. U:\WCC\WCC0301\Documentation\H-Prime Contr\H1 Contractor Correspondence\Document Review.doc WCC0301 June 4,2004 Wayzata Country Club Addition! Renovation Page 5 19. Sheet A670, Detail 2B: The employee's lavatory counter does not appear to meet accessibility requirements. Has this been approved? MDA to issue a revised detail indicating 29"min. clear from the finished floor to the bottom of the apron and 34"to the rim of the sink above finished floor. 20. Sheet F101: It has been our recent experience that an elevator inspector has objected to a single sprinkler pipe serving the elevator equipment room and then continuing through to serve the elevator pit. Please verify that the proposed design is acceptable. Also, please clarify locations of sprinkler heads in Stair C. Comments from Mechanical pending. 21. Sheet M101: A. No ventilation appears to be provided for the elevator equipment rooms. Is ventilation required? (Typically we have been required to provide mechanical ventilation to maintain ambient temperature and humidity per manufacturer's specifications per 2000 ASME 17.1 Section 2.7.5.2 or similar.) If so, are combination Fire/Smoke dampers required? B. Do the ducts entering the shaft at approximately Gridline 11 between L and M require dampers? This may be subject to City interpretation of IBC 715.6.3 and related sections. Comments from Mechanical pending. 22. Sheet M103, Detail 2: It appears that piping, which does not serve the stair enclosure, is passing through the enclosure. Should this detail be revised? Comments from Mechanical pending. 23. Sheet E101: Is emergency lighting to be provided in the elevator equipment room and is said lighting adequate in the employee break room? Comments from Electrical pending. U:\WCC\WCC0301\Documentation\H-Prime Contr\H1 Contractor Correspondence\Document Review.doc