1. Installation shall comply with the Minnesota Uniform Fire Code.
2. Dispenser shall be located a minimum of 10 feet from building and property lines and
when the hose is fully extended the nozzle shall not be closer than 5 feet from building
openings.
I
LAKE 3. Install (1) AST 500 gallon double wall tank UL142.
M I N N ETON KA 4. Tank will be placed on an concrete pad supplied by owner.
5. AST does not need vehicle impact protection because it is a none drive area.
6. There shall be an emergency shut-off device located not closer than 20 feet and not
SMITH BAY
0�9 �
farther than 100 feet from the dispenser. Activation of the emergency shuit-off device shall
co o
shut down transfer of fuel to the dispenser. The emergency shut-off device shall be distinctly
'a 'o LO co = o
labeled EMERGENCY SHUT-OFF DEVICE.
'� z
` 7. There shall be provided not farther than 75 feet from the dispenser a portable fire
extinclusher of a minimum rating2TA-20:BC. The fire extinguisher shall be inspected annually
U M a) M
CU4-
Gauge by qualified personnel.
v m NU
8. Signs prohibiting smoking, shall be conspicuously posted within sight of tank and
o U) CU
4" E-vent dispenser, 9. AST's require normal and emergency vents, The normal vent shall terminate a
Im L Q
Overfill alarm minimum of 12 feet above the ground level and 5 feet from building openings and property
`-
Spill container 2" vent lines that can be built upon.
Fillrite Pump 10. Electrical equipment shall be installed in accordance with the Minnesota Electrical Code.
Ball Valve 11. AST shall be provided with lightning protection in accordance with National Fire
1-1/2" Ball
Solenoid Valve Valve 75' Hose Reel Protection Association Standard 780 (1994 ed.)
12. Install Fill-Rite transfer pump on top of tank equipment with anti-siphon device. (N/C
1-1/2" Flexible DW pipe solenoid valve)
inside 4" containment pipe 13. Pipe (1) 1-1/2" double wall flex piping inside a 4" containment pipe from pump location
4
to dispense reel located by the dock.
13. All nozzles to have automatic shut-off, WY OF 01100
Scale 1" = 4' SITE PLAN GRADING PLAN
A A PHOV D Fez 7om<
To reel at dock on shore C.1�MMOVE0 WITH R� � Ns
D-09535-A
EJ 01d VED
y _ �.'lw�s VA" C