HomeMy WebLinkAboutSeptic System Site Plan s75 'Brow Rd5 Westwood Professional Services,Inc. 104 Marty Drive,Suite 3 Buffalo,MN 55313 Phone:612-682-2587 Fax:612-682-2639 Toll Free:1-888-682-2587 April 21, 1999 Email:wps@westwoodps.com Steve Bohl Bohland Development 420 Upland Lane Plymouth, MN 55447 RE: Septic System Site Plan for Lot 1, Carriage Hill,Orono, Minnesota. Dear Steve: This proposed on-site septic system was designed for a 5 bedroom home, with an estimated flow of 750 gallons per day. The system best suitable for this area will be 418 If. of 10"travelless trench installed no deeper than 12" below the existing ground level. The seasonal high water table was found at a depth of 4.0 feet in the Septic area. Two 1300 gallon septic tanks will be adequate for a system of this size. The site in which this system is proposed has an average existing ground slope of 12%. Percolation rates for this particular site were found to be between 14-19 MPI. An alternate septic system has been designed to show that there is enough undisturbed area on the lot to support another septic system. This system was also designed for a 5 bedroom home. The seasonal water table was also found at a depth of 48 inches, this site would also require 418 If. of 10"Gravelless trench. This system will not need to be constructed unless the primary system fails. Certain precautions will need to be made to protect the areas in which the above referenced septic systems are proposed. Both primary and alternate septic areas have been or will be staked off. It is recommended that safety fence be placed around both of the sites for protection during construction of this project. It is critical that the soil is not disturbed before, during, and after construction of the system. These system should treat the septic effluent effectively if the systems are installed properly and are maintained properly. It is recommenced that the septic tanks be pumped once every two years. This will reduce the chance of solids reaching the system. It is also recommended not to use excessive amounts of chlorine, soaps, and chlorine products which can kill bacteria in the septic tanks. This bacteria is needed to treat the septic effluent Designing the Future Today...since 1972 If you have any questions in regards to this design, I will be happy to answer them. I can be reached at (612) 682-2587. Sincerely, WESTWOOD PROFESSIONAL SERVICES, INC. Bernie Miller Septic Site Designer MPCA Lic. No. 43 cc. Stephen Weckman °1999 Westwood Professional Services, Inc. ' / / _- LEGEND �^ ------- ` Z1---_ ex/sting well ,/ soil boring Q percolation test / xpsi • existing fence 1/ \ -------- existing deciduous tree / /%� —� existing coniferous tree • // / �- \ —- — existing elevation contour 92x4 existing spot elevation7/ / \ . \ 192x4 proposed spot elevation / ❑/ Elevations relative and assumed / f (--- '2( Elevations relative to U.S.t S. 1929 N.G VD. / 6 . \) \:) Denotes proposed surface drainage CD PK1MARYSE.T C Y M ,. 1,\I • .� \ \ ___\, (4 SF 0 ID11PC • cs) \ Notes:. • • cp GRAVEL' T'E C I P �, �p 1. Avoid compaction in septic area before, during and 00 after construction 56 3 \ \• 'SOP E W 2 Trenches are to be installed parallel to the contours and the V \ pR pPWALL , ' N trench excavations are not to exceed a max/mum depth of 16(1/44:11E TE ATE SEP I C •I T eEDRO M I 12 inches be/ow the existing ground surface. ,3. Verify before drilling that no septic tanks or drain fields (41 L OF 10 I D 1 are within a 50 foot radius of proposed well location. CRAS LE S 'ENCH ` ���� 111 (100 feet for shallow well) \ .:1 S 3 �, 4. Verify before construction that no shallow wells ore within ‘110, . b 100 feet, or deep wells within 50 feet of proposed septic —(( r ' tanks or drain field area. X A\1 40 `\ �� 2 1 5. To extend the life of septic system pump septic tanks a minimum of every 2 years. 6. S 22 \I\ tl \ •L- 300 L�� �� E See attached sheets for additional construction details C s- I , . / SB 1 • , 821 ��R OP BOX T , / 7 Soil Classified as Hubbard loamy sond(HbD) 12-181 slopes, U. according to the S. Department of Agriculture soil Survey ) (---cr \ 8. Site plan prepared by or under the supervision of Bernie Q ��S�` <_}.1)/31F T N D Miller— 4.P.C.A. License No. 43 r g,,. -•-_.,,,„__._____„,,___..,,__,.,,,_ / ,„------------- � 15-f------ �r /✓l Dater—z/--Zr 75 WETLAJ Nit -____ . \..................-----_____ ....------- . , }--- ,, .),_) ---- 0 40 80 120 yr Westwood Property location: DESIGNED BCM REQUESTED BY: DATE Westwood Professional Services, Inc BCM Septic System 4/20/99 104 Marty Drive, Suite 3 Lot 1 CARRIAGE HILL, Orono CHECK Site Plan I [ Bohland Development Buffalo, MN 55313 CHECKED JMc [ 612 682-2587 Job No. Plymouth,MN. 98795 INIet1Ii)uAI. SI:WAk_,L 1KLAlMVit.;\ t >1J1LM 1,‘,01.e• [11.1.1 FLOW Lc.74 / Estimated Sewage Flow in Ballon her Das (gpd) A. Estimated 75C) gpd Number - - measured __x _ ----__---gpd of Type I Type II Type III Type Iv SEPTIC TANK VOLUME Bedrooms 2 300 225 180 13. _:-e %Oo gallons 3 450 300 218 M" 4 600 375 256 die 5 750 450 294 "nuc 111 SOILS (Site evaluation data) 6 900 525 332 7 1050 6()0 370 .4h" C. Depth to restricting layer= 'YO feet 8 1200 675 408 D. Maximum de th of system C-3 ft = A 0 feet L. Texture Percolation rate/S'-/9 MPI Number Minimum Minimum F. SSF 1.61 sq ft/gpd Septic Tank Capacity with Of Liquid Garbage Bedrooms Capacity Disposal TRENCH BOTTOM AREA (gallons) (gallons) H. For trenches with 6 inches of rock below the pipe: 2 or less 750 1.125 A x F= x = sq ft of bottom area 3 or 4 1.000 1,500 I. For trenches with 12 inches of rock below the pipe: 7 or 8 2,000 3,000 7 or 8 2,0(X) 3,000 A x F x 0.8= x x 0.8= sq ft of bottom area over 9 See fig.C-6 (x 1.5) J. For trenches with 18 inches of rock below the pipe: A x F x 0.66= x x 0.66= sq ft of bottom area soil Charanenstics k Requrrwt Area,hit St,age Ireatnn.ni K. For trenches with 24 inches of rock below the pipe: Percolation Rate �•'• cru... Minutes per inch JOa Texture l r;," 4-4,;;, A x F x 0.6= x x 0.6 = sq ft of bottom area (mpi) , BED BOTTOM AREA Faster than 0.1* Coarse Sand 0.1 to 5Sand 083 1.20 L. For Gravity beds with 6 or 12 inches of rock below the pipe; 0.1 to 5 Fine Sand** 1.67 0.60 6 to 15 Sandy Loam 1.27 0.79 1.5 x A x F= 1.5 x x = sq ft of bottom area 16 to 30 Loam 1.67 0.60 For Pressure beds with 6 or 12 inches of rock below the pipe; 31 to 45 Silt Loam 2.00 0.50l�P 46 to 60 Clay Loam 2.20 0.45 A x F= x = sq ft of bottom area Slower than 60••• Clay (0.24) ROCK VOLUME IN CU FT •soi too coarse for sewage treat men! Use systems for rapidly permiable soil,. M. Rock depth below distribution pipe plus 0.5 foot times bottom area: --Soil baying so•>:,or more of or very tine sand M=Rock depth+6 inches x Area(H,I,J,L,K) -'snit with fan in roandpercendrrlayfor installation of an in round standard system. ( +0.5 ft)x = cu ft ROCK VOLUME IN CU YDS N. Volume in cu ft divided by 27 M+27=cu yds +27= cu yds 6 inches= 0% Reduction* • ROCK WEIGHT O. Cubic yards times 1.4= tons 121nCheS= 20% Reduction N x 1.4=tons x 1.4= tons 18 uncles=.34%D Reduction 24 niches=40% Reduction DISTRIBUTION •*:sizing for graveness trench (Check one based on slope) Bed(<6%slope) Trenches 'Drop boxes(any slope) Distribution box (<3%) SYSTEM LENGTH P. Select width= ft ti....ti.;•ti.%.%•%.ti•ti.ti.S.%.ti.ti T r•r•r•r.r•r•r•r•r•r•r•r•r•r•r•, Q. Divide bottom area by width: (H,I,J,or K)+P=lineal feet jtif sisisiftftf sing ss-istifti 2 mchCover ti•ti•L•ti•1•ti•ti•ti•ti•ti•ti•ti•1•ti•1 _W_ 'r•r'r•r 141.;"'r•r'r•r•:1M.r't jr l�- lineal feet ti•ti•1•ti•1•ti• •ti•ti•L•ti•1•ti•ti 'r•r•r•r•r•r •�•r•r•r•r• Gravelless Pipe ~•~'�• %-%.%•ti•ti 'r•r•r•r•r r•r•r•r• ti•ti•ti•ti• �•ti.ti•ti•ti • •r•r•r• r•r•r•r•, ( 10" :A x F-3)=Lineal Feet(8" :A x F-2)= Lineal Feet rr:}:f Si' ti};•�•ti•ti 4 mchPike r•r-•%' L•ti•ti•ti• ti•ti.ti•ti•ti Chamber(A x F+width of chamber) ".........e...0 ;•r•r•r•r•, ti.ti•ti•ti.ti ti.ti•ti•ti•ti •r•r•r•r•r• r•r•l•r•r•, •1 L•ti•ti•ti•t•S• L•ti•ti.ti•ti-t •r•r•r•r•r•r•r•r•f•r•a•?..5 r•i 7�_x/.67 - -_ lineal feet ti•ti•ti•ti•ti.•..."•ti•....e• ti• ... LAWN AREA 'r•r•r•r•r•r•r-r•r•r-r•r•r.r•r•, it:f:1:f:11.f:f~f:%:fV~f~fyr~f: ****1 '1.•t•t•t., ti•L.ti•ti•ti•ti•ti 'f•r•r•r.r•r•r•r•r•r•r•r•r•;,. 6,24 irwh R Select trench spacing, center to center= 5_ feet ti'�'�'ti'�'�'~'`'~'''~'`'''�'� r•r•r•r-r•r•r•r•r-r•r•r•r•r•r•, ti• a-0- ti•ti• ..,e- ti••.•ti•ti•ti-'Rock Below the Pi, 'r•rvr•r•r•r•r•r•r•r•r•r•r-:-' Multiply trench spacing by lineal feet R x Q = sq ft of lawn area '•%.%•%•%•%•%•%•%-%.%•,•,•%•%•% --.-. x S_.. = Go sq ft rti•.eti."•ti,•1•r•tir•••r•-•r••,rti•r•ti-r•titi•r•ti•:•ti-r•tti•r•-•, tir1:11:= rr:rtirtirti•rtir•rr•r-r- , t••.•ti•ti•ti::::*1•ti•ti•ti•ti•�•ti••- LAYOUT(Use other side) r•rr•r•l•r•r•r•r•r•r•r•r••-.- 1. Select an appropriate scale;one square=.__--_ feet. 2.Show pertinent property boundaries,right-of-way,easements. 3. Show location of house,garage,driveway, and all other improvements, existing or proposed 4. Show location and layout of sewage treatment system. 5.Show location of water supply well. 6. Dimension all set backs and separation distances. 0 .) I j */', a j m O Q () rr 'i, 7 T ii {. , D (/) IL f uc x Q0 � � 0 ___I Q 0 I a_ W " O u) _ j 'rn E-- 0 LL H Q wJ _J .,:c di it 1- (r) }._ Z U Q Z W N • O Z U ZCrrY Y Q Q L F-_Z M �Q \ F eL WO- - n L'."1 4-I '� - `. n Q 1.4 O W D� w ( ) a 1 d- =O W J a -- Ln 0 O ct� 0 > Q 0 Y W C-LZ71 _ -_ — , _‘ kJ Ln W 1 4'e- " i -: . ? Z Co a t-- II _ - _ __k.,__. ~ \- �i a - o `� Z �^'W z_ w - > m O v til f\ l Uu F- )I I'L l7 CD -- T Z F- ai >- ( ) Y > a Z 1 ) R lit -1 i t O n UL 0. 1�. 1 1, ( 1 ' 1 D-1!i OI BO WJ Z = 0 Z WaZ UQO � >- W F-- = I z D J z W H J Cr Z v �. J W N F- cn a 0 J w Z W > W 4Q W D W ► >- -1W o J1-- J lja --Cr _J (1) O H J I- W W D J O � F- _i O� Q O Z D so O lZ Cr W W - Oa0 �acn0 mcX o �L - WZ m� 5a cc >- WO m I W Q W O� WQ H > m F- - - - 4 --4 - -1 I- m }, W _JW0I DZa JQ L----1 t Z a J . O IF- -li_ 2 Zcc OQ i. Z Cc - Z0 `-'W I-- 4,:f O X - W W I W _11111 0 p cn I� m __i I— = W o a) o H 0 �Q CL Y Z x Q O r---1 i Vl WW O0p Cr wpuWCc O Z (n0 �� ,y �q CL,_ I- HOW = ~ wMJ- � ,_ _,2 =(n p Q._ >Lij ZZ 0> H--OW WIW Z = — -1- Q JWOa: D0 )00 Z-lL0 > Va_ Lill- -1 WZ01— cnQNOv ZZ� F- m O c I qj CO L N M sT H � Z f-Z J cr CL. - z x O ~ O O 1 00 cr -+- O >,_w co -i W H cu F- 0 aJZO - pIll I-i a J _ Qi W w D H 0 f-Z cn _J CC o WW I-- DI- k&-� 1)N. 0 r- 7 v L--J = _ a I� • 1 ► 111.°F 2 ZD I-0 <Ox yI W W W e CL > mli J Uc - Z W I__ 4_ J WCrCr Z cn 0 0 GRAVELLESS TRENCH CONSTRUCTION DETAILS 1/2 lnspechoInlet Pipe to Next 95gd/rl Well Drop Box 1 1/2 Male Adapter - ge t ,6- Iz Soil Backfill Ne it �' I��vIII VLTv v- % V Vvvv - v- Corrugated Tubing Covered 95s.o EXiSfi';9 I with Geotextile FabqchnpnnnnrvLr Psu. fe±3± Drop Box955!3 Trench Length = up to 100 Feet Overfill to Allow NOTES : 1 . Bottom of trench for Settling c must be level. Top / of tubing must be level. 084 Soil / Y, 12" of Soil 2. Scari( trench bottom and Backfill y s�dewalls 24Backfill at least 12 inches above trench bottom , to expose natural soil. 12" v. D, 2 - -O— ' 3. For proprietary products consult Holes Located manufacturers performance criteria 24" at 4 and 8 O'Clock Figure D-29 11 Westwood Proft's�.ton.tl f-;r'tvict'ti Ito LOGS OF SOIL BORINGS O 7599 Anagram Drive Id 104 Marty Drive, Ste 3 Eden Prairie,MN 55344 Buffalo, MN 55313 612-937-5150 612-682-2587 toll free 1-888-687.7587 FAX 612-937-5822 FAX AX 617682 7639 I o,:won of Project' Bohland I>c‘clopineni 9879S 1):uc I' IN):98 Borings tirade by Ruh Swissc Classification System: AASIit1 IISI)A-S('S X Ilnflied Other Auger used(check Iuvo) (land X of Poo et 1-(reeht or Bucket X ( I)(TMBoring Number _ 4, -- I)e pih Boring Number /7 —_-_ ___ in Surface Elevation n Surface Elevation leer Munsell( hart liii NIunscll Chan ,r (I ew.y c,? 3�Z I I ti 60 M 'O5vi, .z./z /Z— — I 6 Lori? 107/! .3/3 L66m 16Y? 3/3 )6, -r 7 S6,nd y Leary for y/y ztp t 0041 2.S Y y/y 3 3.4__ 3 3b-- Loa, 2.sr Y/y Sanity Lsam 2. 5-r 5,/,/ a dlSI 2..5r s/2 'i H-fes 'if — ,1 Av-,dy L.Oani z,SY `7/</ > 5 'dr'sf z,.sr <ehz rna}flr^s 6 6 7 7 8 8 End of Boring at Lib d -C�st— End of Boring C.04 -1.4;et Standing water table: Standing water table: Present at: feet oI depth. ('resent ai feet of depth. hours after holing hours after boring — Not present in boring hole \ Not present in boring hole X 1 t,gri,-,J. ,it/ r it„coved at ” iafc„ni in holing hot,. \rel 1,;",, ;,f „na'l• h.,Ir I ;ii.;'i,;a,,,n•:,ilii,v,iluacei i , iii, i � • Westwood Professional Servicers lrt LOGS OF SOIL BORINGS ❑ 7599 Anagram Drive M 104 Marty Drive, Ste.3 Eden Prairie,MN 55344 Buffalo, MN 55313 612-937-5150 612.682-2587 tall bee. 1-888-682-2587 FAX 612 93/ .`i8:'; FAX 612-682-2639 Location of Pioico lioltland I)e clopnu•nl 9x7'15 I)ate I2/(19/')X I3orings made by Rob Swissc Classification Sv',iem AASII ) l!SI)A-S('S X Unified Other Auger used(check too) I land X or I'u,aei Flight or Bucket X (hhei • I) Depth Bonn,' Nuinhei i�{ _—_- epih I3oring Number — 7I in Surface Elevation in Surface Elevation feet Munscll Chan fret !Munsell Chart 0 Jarwri toGiYj /G9q z/Z (1 .5 4n I- oGr✓/ Z.sf 3/2 1 e Saner 1,e441 //PM' 3/3 I � 54ry Lbarrt z,Sl' d/3 7 2 i8^ tea Sty Sarro�---- --- z.5-r H/y --------------- sanay leaf/ z.Sr y/y 28-- I .30— / 3 L ca.vty S a rFQ !9Y>? '113 3 S4I 2.5i- y/i! Hz s>1 Gd 4 /0r4 ,ilii a 18— - S6 n d 2.5--Y yra( sw / lz ,rYr/ySanad�f2.5-i- / .,esr H e,s+ z.sr.512 raffes 140 6 6 7 7 8 8 End of Boring at 4.0N -feet- End of Boring (,Q" +ect Standing water table: Standing water table: Present at feet of depth, _- Present at: feet of depth. hours after boring. hours after boring Not present in boring hole X Not present in boring hole X i1,liil,',/vuri ;1 11i/l',l NM/ ()b\l I\ -,l:11 ' 'l of depth Ohx rued al r 1,;Idi N,n i, ,-.,•i;; is ;; Ii 6 in ? . N..1 I,Ic;rnt hunnt' hair (11).crv.,1t,,;,. .,,;,1 ,,,;!'u,,u!_, . Westwood Professionni Services. Inc LOGS OF SOIL BORINGS CI 7599 Anagram Drive EA 104 Marty Drive, Ste 3 EE den Prairie. MN 55344 Buffalo,MN 55313 612 931 5150 612-682-2587 toll free 1-888.682.2587 I AX (,1:' 93/ 5822 FAX 612-682-2639 1.ne.uum ill I'ioicii 14ii111;uul I)e‘clol,n,eni 95795 I)die I.!(i') ')X Hornig,',madc by Rob Swiss,: ClassificationSystcm AA-d10 t(SI)A-SCS X Unified (Ether Auger used(check two) I land X or Power Flight of Bucker X Other 1)cpih 13oring Number -, • Depth Iiorinc Number Z f _ in Surface klcvation in Sill I,k-e lae\atioil feet J Munsell Chilli Ire, Nlim,ell Chart ----------- - — 0 �oa.ny San ieo Z/Z 0 Sandy Loa rvi /PO z/z 1 /O 1 4F/- .S4nsir I-camiovi 3/3 L6amY sc.nd am 3/3 2 fg SGndr /...6,,,,,e1 f8y4 3J-f 2 21— i. `f— L oary Sant( 10'Pe (// 32- / 3 3 Loa.ny 54/IA 2.sr ibi 4 y2• 64nof 2,51' 'fig 4 5 SE 5 S� 1-1-60P17-756111T:/,'$iz.sr s/H— tPC _ 2.sr slz n,#,os 6 6 7 7 8 8 End of Boring at "B '' feet. - End of Boring G,0" -feet-. Standing water table: Standing\valor table: Present at: feet of depth. Present at feet of depth. hours atter boring hours after boring. Not present in boring hole X Not present in boring hole X 1li,nlr,/Nord. ! l i)h.ei\edat OI , Aldcpili ,,i rie:ent in hol mit b,il, li„Ic (ln..,,vltoinX and eolltin,'ni'� .i ()1 :. , t ; l . Westwood Professional Services Inc LOGS OF SOIL BORINGS [1 /599 Anagram Drive 171 104 Marty Drive,Ste.3 Eden Prairie,MN 55344 Buffalo,MN 55313 612-937-5150 612-682-2587 loll free 1-888-682-2587 1 AX 612-93/ 582; FAX 612-682-2639 I ovation of hoick I Iiohl:utd I)evclopmenl 98795 I)ate I'/09/98 Ilorint'',made h\ Koh S'vtsse Classification System AASI10 USDA-SCS X Unrlied Ulhet Auger used(check th of I land X or PoV,cr Flight or Bucket \ Diller Depth Iioru)g Number z 3 I)epth Boring Number — -Z in Surface Elevation III Surface Elevation feel NIunsell-t-hart feet NIunsell Chart _ u SQ�df Lmak7 IO /? 2/Z (1 54nety Loa 10Y" z/27 I w �.5andy Lean1 am 3/5 i boanti 344 torr/? 3/3 2 L60,7 Sind 16“fk .41,./ ' �--- 2 I-oanmy sand Z.sr y/y 3 3 4 4 SO 5 bQ-- dlSf /07q 92- "7104)0,5 5 6 6 7 7 .8 8 End of Boring at &O a -feet:— End of Boring y.e feet. Standing water table Standing water table Present at. feet of depth. _ Present at: feet of depth. hours alter boring. hours ahcr horinu Not present in holing hole X Not present in boring hole X \1u111c,i>r v' 11,ir7/<'<l.sod. ()h'e r ved .If al). of depth t)hx•rvcd al Not plc>rin n, hog mi!, ','6 X'.,t lnrmrnt in bormp !)„d, ( >1 .r:'.ili ac .,n.,` . .,nn;;,-11• _.--------- l u,_.:.'r 111(11ls and��un :ti;: I , . Westwood Professional Services. Inc • � 0 7599 Anagram Drive IA 104 Marty Drive, Ste.3 PERCOLATION TEST SHEET Eden Prairie, MN 55344 Buffalo, MN 55313 612-937-5150 612-682-2587 FAX 612-937-5822 FAX 612-682-2639 Test hole location: Carriage Hill (Bohland Dev) Lot- Depth of hole bottom: 12 inches Hole No: /6 4- 11 Diameter of hole: 6-8 inches Date test hole was prepared: 04ZZ19th, Soil Data from Test Hole depth, inches soil texture soil color see logs Method of scratching sidewall: hub w/nails Depth of pea size gravel in bottom of hole 2 inches Date and hour of initial water filling: t zi asj 7 t t7 Depth of initial water filling: 12 above hole bottom Method used to maintain 12"of water depth in Hole for 4 hours: Automatic siphon Percolation test conducted by: R. Swisse Percolation test started at CC 2.-"7 /9jV I Maximum water depth above hole bottom during test: 8 inches Date (0/2.-as/913 WATER WATER INTERVAL WATER DROP DROP PERC RATE TIME (Minutes) DEPTH (fraction) (decimal) CALCULATION ci;17 START 0 19 -,' •- -«'-Z-• A 91: 417 i�L 6 ? ^)t�y I t/4 I *ZS TIME DROP = PERC 6/ REFILL _Q_ ( 10..01 I S 1 ) ( TIME _ DROP = PEC .Q B 10;03 REFILL _0 1 ' t ,l J , �C IID Li i (�y 1 /14 1 .z.s Tl = DROP = PERC ,9: 'V_ REFILL 01_2 Zr A/s f 7 D /pt OL Z J�i !B /.lJ TIME - DROP = PERC /D.'Q3_ 1 _ I REFILL _ 0 9 E 17 /Od Z Z I I TIME — DROP = PERC !0:2.3 REFILLQ — 0 _ S-- 7 F /01 Si `"U I /Z 1 , 2 I.c TIME ± DROP = PERC A, B, C B, C, D Laws,gof)413(' Smallest X of A/3C !kit-gest#of U('I) Smaller(k<f IWO X 0.10 1 0.10 Smallest s 4 ABC Smallekt e of H('U C, I), E I), F, F 1...�•..t nol c'l)l( Smut Lotaof CI V- X 0.10 X 0.It) • . Westwood Professional Services. Inc ❑ 7599 Anagram Drive ECJ 104 Marty Drive, Ste.3 PERCOLATION TEST SHEET Eden Prairie, MN 55344 Buffalo, MN 55313 612-937-5150 612-682-2587 FAX 612-937-5822 FAX 612-682-2639 Test hole location: Carriage Hill (Bohland Dev) Zo1 Depth of hole bottom: 12 inches Hole No.: /5*(7 Diameter of hole: 6-8 inches Date test hole was prepared: fZ/2-2_,79 e Soil Data from Test Hole depth, inches soil texture soil color see logs Method of scratching sidewall. hub w/nails Depth of pea size gravel in bottom of hole 2 inches Date and hour of initial water filling: /e/Z3, trio Depth of initial water filling. 12 above hole bottom Method used to maintain 12"of water depth in hole for 4 hours: Automatic siphon Percolation test conducted by: R. Swisse Percolation test started at ch 4S--/9;y6 Maximum water depth above hole bottom during test: 8 inches Date 1'Z f-ZZAi8 WATER WATER INTERVAL WATER DROP DROP PERC RATE TIME (Minutes) DEPTH (fraction) (decimal) CALCULATION 7:4i 6.— START/0:016. Z _ '-/b 2/ � /_38----- . / S .Z A 1 /p:/0:016. ( 1 3/6 / /.,� TIME ± DROP = PERC An O 6 REFILL -17-y— d_ 0 • [. ZS 16 .0 _ B /D,'it 6 2-0 1 '-y I 1-ZS TIME - DROP = PERC /D; Z Z REFILL Q / / l o t $3 eQ 6, ^l .4- I /8 1-f3 TIME AQ 6 _ DROP = PERC O C 9'96 REFILL O / /O.�D7 2l l%Z /r! 1,5-- TIME DROP = PERC tet /n'07 REFILL //L_ J ,,n 8 g/ `� ��2 / $ TIMEIM 1 DROP = PERC d E (c, — REFILL ,26 _O _ /3 elE - / 7 1 Yy FfD,S �G /y /y 7�r DROP = PER - A, B, C B, C, D Larges(Wof ARC ,Cmallec(H of/e'I) X 0.10 = x 0.10 = Smallest#of,413(' .\n,U.„-of li('l) C, I), E 1), 1:, F /urge,'Oaf('1 N. ,t'At ., ,!f 41 Smallest au/I UCF X 0.10 0.10 Snru11,-sr a J(7V` cm.illr„a,,/Ulir - T Westwood Professional Services. Inc LI 7599 Anagram Drive II 104 Marty Drive,Ste.3 PERCOLATION TEST SHEET Eden Prairie, MN 55344 Buffalo,MN 55313 612-937-5150 612-682-2587 FAX 612-937-5822 FAX 612-682-2639 Test hole location: Carriage Hill (Bohland Dev) Ld'1' Depth of hole bottom: 12 inches Hole No a ( -I 2 3 Diameter of hole: 6-8 inches Date test hole was prepared: /2/z 27/f6 Soil Data from Test Hole depth, inches soil texture soil color see logs Method of scratching sidewall: hub w/nails Depth of pea size gravel in bottom of hole 2 inches Date and hour of initial water filling: /2,/2.' 9;/5 Depth of initial water filling: 12 above hole bottom Method used to maintain 12"of water depth in hole for 4 hours: Automatic siphon Percolation test conducted by: R.Swisse Percolation test started at 4?.'V9, VSZ. Maximum water depth above hole bottom during test: 8 inches Date 1223/F8 WATER WATER INTERVAL WATER DROP DROP PERC RATE TIME (Minutes) DEPTH (fraction) (decimal) CALCULATION 9;179_ START 0 i 2_6Df• 13 a A /Q;C,1 Ac:, t'fpj I ' � •) 3 TIME ± DROP = PERC FE /D.'/() REFILL O 2 f lD:2-7 1 7 IVIb - /6 Q.5 3 TIME - DROP = PERC pRC C' 28 REFILL — 0 _ ,__Z6 . f- `I(-f ..18- 0 C ID: 51 2 6 [7/16 1 -7/16 I• Ht.{ TIME - DROP = PERC 9;5Z REFILL o , 10%. 5- a3 —i 7Z `�� /. E ._ _. D 1 IZ f.S— TIME - DROPP = PERC /J 10,15— REFILL _(/Z 3 / �in ._1!3i3 ._ f`l°�. E 22 10:35 zo �lQ� f l8 3f TIME - DROP = PERC /,:36 REFILL _b _ /6 /0 6 /64 F /0:5 Z /6 /�(� / /6 ,Q4 TIME ± DROP = PERC A, B, C B, C, D Largest tio[ABC Smallest N afA/JC 1,1-gest 4e4-13(1) Smallest 4 al 1}(7) X 0.10 = X 0.10 = Smallest 4(1.4111. Smallest N,,f BCD C, D, E D, E, F Lllg.•,a aaf(7V SrualleSI P,f(W. largest qo f/ll:l on„u. P •d UI J X 0.10 — X 0 IO .N1naRrsta of rnl- Smallewk f1)1/