HomeMy WebLinkAboutfire/safety inspections LL v . /� • ' /�//r%� �Gc�t� f;'. ' �j,f:�'-3
EXCELS/OR F/RE O/STl4/CT — F/ E CODE Br SAFETY //VSPECT/ONS
24 7 00 Sn��Th►TOw�v ROAO SH REWO00 M/NNESOTA 5533 1
/NSPECTOR Z KELL/E MURPHY-R/NGATE 952.960.1692 Ianyrphyljn�a��a�ce/aior6re.org
/N3PECTOR 3 LEE BEROLUND 9 2.96Q.1693/ und�aps��jjforl�irao
OCCUPANCY: DATE: KNOX: TYPE:
��f-�wA�T�� SaG.I �T� � 5 �G� 4�E.S
REIN SPR SYS: ALARM:
C�-�/L-L �r4N`T- �j O ' �� �G� {' �4� �S
ADDRESS: y� �Q� %� EME GEN �
O �.SJ� D I`L�,"1� CGNTACT: G��S �
PNONE: C� (� / C/ •y " EMEROENCY
l�� • -( �(. I � ! 3 PHONE #: � . ��� . Y�' lO�`�
Inspection of the occupancy listed above been GEEPHAVEN COM MENTS: �L: R S�. � 7�
completed in accordance with the 2000 IFC and EXCELSIOR � T ' �5��
the MSFC adopted by the city of:»»»» GREENWOOD � 5(,�'r' ��NG1„(
The following violationa and/or deficiencies SHOREWOOD /� � �
r uirin corrective actio�are noted below. ��� ONKA BAY �' V��c�-• � �. �1 �(
EXTERIOR: # FIRE PROTECTION SYSTEMS: #
Address visible and le ible-Front and rear doors 1 S rinkler heads in ood condition- ro er covera e 21
Fire h drants accessible-36" minimum clearance 2 Door to s rinkler s stem control room marked
Fire lanes-Fire De artment access 3 Riser&control valves accessible/current ins ection 23
FDC unobstructed&visible-pro er ca -3'clear 4 Control valves locked open or tam er rotected 24
Horn/strobe o erational-unobstructed &visible 5 Extin uishers ro erl located-current ins ection 25
Knox Box with ro erl labeled ke s 6 Commercial hood s stems-clean &ins cted 26
Dum ters minimum 5' from building 7 Class K extin uisher resent in commercial kitchen 27
Gas meters 8� i ing rotected 8 Fire alarm system in ood condition-ins ected 28
Buildin exterior maintained 9 Door to fire alarm room identifled 2g
EXITS: # INTERIOR/STORAGE: .�qt
Exit doors unobstructed, o erable, ro er hardware 10 Stora e 18" or more below s rinkler heads 30
Exit corridors maintained and unobstructed 11 Stora e 24" or more below un rotected ceilin s 31
Exit si ns illuminated 12 No stora e in un rotected attics or below stairs 32
Pro er exit si ns dis la ed-6" minimum letters 13 No stora e in mechanical or electrical anel rooms 33
Emer enc li htin in ood o erating condition 14 No stora e in boiler or elevator e ui ment rooms 34
Occu an load osted (assembl ) 15 Trash &oil ra s ro erl ke t or removed dail 35
ELECTRICAL EQUIPMENT: # Flammable and combustible liquids ro erl stored 36
Door to electrical room/ anel labeled Hazardous materials ro erl stored and identified 37
30" clear access to electrical anels Com ressed as linders ro erf secured 38
Open spaces in electrical panels-knockout plugs 18 Ceiling tiles in place$undamaged 39
Electrical hazards- ower strips/circuit rotected 19 Wall or ceilin dama e re aired/seal enetrations 40
No extension cords used as permanent wirin 20 Smoke detectors o erational/pro er location 41
C e Violation Summary:
�- �- - poT � �w��vv �D
� ���
' �-�- � �/ ���'� S�G nJ
-- �!-(iv �� i �
^� � � �L�^7T�
The Fire District reaerves the right to enforce the
MSFC if any other violations are discovered during
the compliance process or as they may arise.
, � Signature indicates receipt of copy
X and c�operation with compiiance
owr,er a R��ntat� E��s; D�� ��s�ta orders within 3� days.
' tl�CO Fire & Simp/exG/'%/�/�e//
Security INSPECTION CONTRACT
SPECTION REPORT NO. .-.___ '__ :� , _
No. REPORT OF INSPECTION BUREAU FILE _ __ _ ;
CONFERRED WITH NO.
per NFPA 13 & 25
SET 1 OF 2 ,:
� REPORT TO BUILDING OR LOCATION INSPECTED
' STREET INSPECTOR
CITY&STATE ZIP SG OFFICE PHONE NO.
ATT. DATE '
1.GENERAL Yes N.A.$ No"
A. (To be answered by the Owner or Owner's representative)
a. Have there been any changes in the occupancy classification,machinery or operations since the last inspection?
b. Have there been any changes or repairs to the fire protection systems since the last inspection? ''j
c. If a fire has occurred since the last inspection,have all damaged sprirrkler sqstem components been replaced?
d. Has the piping in all dry systems been checked for proper pitch within the past five years? �'`
Date last checked (checking is recommended at least every 5 years)
e. Has th'e piping in all systems been checked for obstructive materials? -�'��
Date last checked (checking is recommended at least every 5 years)
f. Have ali fire pumps been tested to their full capacity through the use of hose streams or flow meters within the past 12 months? —�'
s
g. Are gravity,surface or pressure tanks protected from freezing?
h. Are any of the sprinklers 50 years old or older? (testing and/or replacement is recommended for such sprinklers)
i
i. Are anq extra hi5ti temperature solder sprinklers regularly exposed to temperatures near 300°F?
B. (To be answered by the inspector)
a. Have the sprinkler systems been extended to all visible areas of the building?
; b. Does there appear to be proper dearance between the top of all storage and the sprinkler deflector? !^
c. Are the building areas protected by a wet system,heated,including its blind attics and perimeter areas,where accessible? '
d. Are all visible exterior o enin s rotected a ainst the entrance of cold air?
2.CONTROL VALVES
a. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position?
b. Are all control valves sealed or supervised in the open position?
No. Easily Valve Secured? Supervision
Control Sealed?
Valves of Type Accessible Signs Open If yes, how? (Locked?) Operational
Valves Yes No Yes No Yes No Yes No (Supvd.?) Yes No
CITY CONNECTION q + �( j" � '
TANK
PUMP
SECTIONAL
SYSTEM � �� / �� ,.0 -,: ;
ALARM LWE �
3.WATER SUPPLIES Pressure Fire Pump&Tank
a. Water supply source? Ciry Gravity Tank Pressure Fire Pump&City
Waterflow Test Results Made During This Inspection Pressure Fire Pump&Pond
Test Size Static Static Test Size Static Static
Pipe Test Pressure Flow Pressure Pipe Test Pressure Flow Pressure
Located Pipe Before Pressure After Location Pipe Before Pressure After
�.. , .-.,
4.TANKS,PUMPS,FIRE DEPT.CONNECTIONS Yes N.A.$ No`
a. Do fire pumps,gravity,surface or pressure tanks appear to be in good external condition?
b. Are gravity,surface and pressure tanks at the proper pressure and/or water levels?
c. Are fire dept.connections in satisfactory condition,couplings free,caps or plugs in place and check valves tight?
d. Are fire dept.connections visible and accessible?
5.WET SYSTEMS � 1
f , � -)
a. No.of systems Make&Model
b. Are cold weather valves in the appropriate open or closed posifion?
if closed,has piping been drained?
= c. Has the owner or owner's representative been advised that cold weather valves are not recommended by NFPA?
d. Have all the antifreeze systems been tested?
e. Date antifreeze systems were tested
f. The antifreeze tests indicate protection to:
system 1 2 3 4 5 temperature
.�, � ,
� g. Did alarm vhbes,wa;�rflow alarm indicators and retards test satisfactorily? "
#Nbt Applicable�
� SG4550-R1-1 �z�os> INSURANCE BUREAU COPY "Explain(No)Answers on eaok ot sheet z `�
� -y � Simp/e�rGrinne// BE SAFE.
INSPECTION CONTRACT �
A business unit of Tyco Fire&Security Np j 4' : �
' INSPECTION REPORT REPORT OF INSPECTION BUREAU FILE
No. �_ PER NFPA 25 rvo. �
SET20F2
6.DRY SYSTEMS Yes N.A.$ No
a. No.of systems Make&Model
Date last trip tested
b. Is the air pressure and priming water levels normal?
c. Did the air compressor operate satisfactorily?
d. Were all low points drained during this inspection?
e. Did all quick opening devices operate satisfactorily?
, f. Did all the dry valves operate satisfactorily during this inspection?
g. Do dry valves appear to be protected from freezing?
h. Is the dry valve house heated?
7.SPECIAL SYSTEMS
a. No.of sys�ng,,...��Make&Model
Type
b. Were valves tested as required?
c. Did all heat responsive systems operate satisfactorily?
d. Did the superoisory features operate during testing?
Heat Responsive Devices: Type Type of test
Valve No.._ .. , �. 1......2......3......4......5......6...... Valve No. 1.:....2......3......4......5......6...... �c
Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6...... ;.
' Valve No. 1......2...:..3......4......5......6...... Valve No. 1......2......3......4......5......6......
� Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6...... „
Auxiliary equipment: No. Type
Location
Test results
8.ALARMS Yes N.A. No
a. Did the water motors and gong operate during testing?
b. Did the electric alarms operate during testing? !
' a Did the supervisory alarms operate during testing? /"
y.
9.SPRINKLERS–PIPING
a. Do sprinklers generally appear to be in good external condition?
b. Do sprinklers generally appear to be free of corrosion,paint,or loading and visible obstructions? ''
c. Are extra sprinklers available on the premises?
d. Does the exterior condition of piping,drain valves,check valves, hangers,pressure gauges,open sprinklers j
and strainers appear to be satisfactory?
e. Does the hand hose on the sprinkler system appear to be in satisfactory condition?
10.EXPLANATION OF"NO"ANSWERS(For Sections 16 thru 9):
r
11.THE INSPECTOR SUGGESTS THE FOLLOWING NECESSARY IMPROVEMENTS,HOWEVER,THESE SUGGESTIONS ARE NOT THE RESULT OF AN ENGINEERING SURVEY:
.-�
' 12.ADJUSTMENTS OR CORRECTIONS MADE: �
�- i� ,�.._ .It��- l� �.�` � ca �rZle.t�' ��
,;
" 13.LIST CHANGES IN THE OCCUPANCY HAZARD OR FIRE PROTECTION EQUIPMENT,AS ADVISED BY THE OWNER IN SECTION 1A:
/
.�, .
14.INSPECTION AND SUGGESTED IMPROVEMENTS,WfRE DISCUSSED W�H THE NDERSIGNED OWNER OR OWNER'S REPRESENTATtVE?
i �
Signature of owner or owner's representativ��- �--�`�=`�^-- �� -�-+:—�--- Date �_�
, DUPLICATE TO:
STREET
CITY&STATE ZIP
ATT.
$Not Applicable
��. SG4550R22(04/O6)�D' ' � A' �
INSURANCE BUREAU COPY
�
tyCO Fi�e& Grinnell
lSecurity
� FIRE PROTECI'ION INSPECTION CONTRACT
INSPECTION RE�RT NO. ___
No. REPORT OF INSPECTION BUREau Fi�E ___
CONFERRED WITH NO.
SET 1 OF 2 _
REPORT TO BUILDING OR LOCATION INSPECTED
STREET INSPECTOR
CITY&STATE ZIP GRINNELL OFFICE PHONE NO.
ATT. DATE
1.GENERAL Yes N.A.$ No'
A. (To be answered by the Owner or Owner's representative)
a. Have there been any changes in the occupancy classification, machinery or operations since the last inspection?
b. Have there been any changes or repairs to the fire protection systems since the last inspection?
c. If a fire has occurred since the last inspection,have all damaged sprinkler system components been replaced?
d. Has the piping in all dry systems been checked for proper pitch within the past five years?
Date last checked (checking is recommended at least every 5 years)
e. Has the piping in all systems been checked for obstructive materials?
Date last checked (checking is recommended at least every 5 years)
f. Have all fire pumps been tested to their full capacity through the use of hose streams or flow meters within the past 12 months?
g. Are gravity,surface or pressure tanks protected from freezing?
h. Are any of the sprinklers 50 years old or older? (testing and/or replacement is recommended for such sprinklers)
i. Are any extra high temperature solder sprinklers regularly exposed to temperatures near 300°F?
B. (To be answered by the inspector)
a. Have the sprinkler systems been extended to all visible areas of the building?
b. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector7
c. Are the building areas protected by a wet system,heated, including its blind attics and perimeter areas,where accessible�
d. Are all visible exterior o enin s rotected a ainst the entrance of cold air?
2.CONTROL VALVES
a. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position?
b. Are all control valves sealed or supervised in the open position?
No. Easily Valve Secured? Supervision
Control of Type Accessible Signs Open If es, how? (Sealed?) Operational
Valves Valves y (Locked?)
Yes No Yes No Yes No Yes No (Supvd.?) Yes No
CITY CONNECTION
TANK
PUMP
SECTIONAL
SYSTEM
ALARM LINE
3.WATER SUPPLIES Pressure Fire Pump&Tank
a. Water supply source? City Gravity Tank Pressure Fire Pump&City
Waterflow Test Results Made During This Inspection Pressure Fire Pump&Pond
Test Size Static Static Test Size Static Static
Pipe Test Pressure Flow Pressure Pipe Test Pressure Flow Pressure
Located Pipe Before Pressure After Location Pipe Before Pressure After
4.TANKS,PUMPS,FIRE DEPT.CONNECTIONS Yes N.A.$ No'
a. Do fire pumps,gravity,surface or pressure tanks appear to be in good external condition?
b. Are gravity,surface and pressure tanks atthe proper pressure and/or waterlevels?
c. Are fire dept.connections in satisfactory condition,couplings free,caps or plugs in place and check valves tight?
d. Are fire dept.connections visible and accessible?
5.WET SYSTEMS
a. No.of systems Make&Model
b. Are cold weather valves in the appropriate open or closed position7
If closed, has piping been drained?
c. Has the owner or owner's representative been advised that cold weather valves are not recommended by NFPA?
' d. Have all the antifreeze systems been tested?
e. Date antifreeze systems were tested
f. The antifreeze tests indicate protection to:
system 1 2 3 4 5 temperature
g. Did alarm valves,watertlow alarm indicators and retards test satisfactorily?
� G4550-R1-1 INSURANCE BUREAU COPY $Explan(No)Answers on Back of Sheet 2 .�
�, �
�'yco Fire & Simp/exG�inne//
Security INSPECTION CONTRACT
'. NO. _._
__..
A INSPECTION REPORT REPORT OF INSPECTION BUREAU FILE
; NO. NO. _ _
SET20F2
6.DRY SYSTEMS Yes N.A.$ No'
a. No.of systems Make&Model
- Date last trip tested
b. Is the air pressure and priming water levels normal?
c. Did the air compressor operate satisfactorily?
d. Were all low points drained during this inspection?
e. Did all quick opening devices operate satisfactorily?
f. Did all the dry valves operate satisfactorily during this inspection? -
g. Do dry valves appear to be protected from freezing?
h. Is the dry valve house heated7
� 7.SPECIAL SYSTEMS
a. No.of systems Make&Model
Type
b. Were valves tested as required?
� c. Did all heat responsive systems operate satisfactorily?
d. Did the supervisory features operate during testing?
Heat Responsive Devices: Type Type of test
Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6...... ;
Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6...... ;
_ ; Valve No. 1......2......3......4......5......6...... Valve No. t......2......3......4......5......6......
+ Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6...... ;
Auxiliary equipment: No. Type
Location
Test results
'. 8.ALARMS Yes N.A.$ No*
a. Did the water motors and gong operate during testing?
b. Did the electric alarms operate during testing?
c. Did the supervisory alarms operate during testing?
: 9.SPRINKLERS—PIPING
a. Do sprinklers generally appear to be in good external condition?
b. Do sprinklers generally appear to be free of corrosion, paint,or loading and visible obstructions?
c. Are extra sprinklers available on the premises7
d. Does the exterior condition of piping,drain valves,check valves,hangers,pressure gauges,open sprinklers
and strainers appear to be satisfactory?
e. Does the hand hose on the sprinkler system appear to be in satisfactory condition?
c 10.EXPLANATION OF"NO"ANSWERS(For Sections 1B thru 9):
11.THE INSPECTOR SUGGESTS THE FOLLOWING NECESSARY IMPROVEMENTS,HOWEVER,THESE SUGGESTIONS ARE NOT THE RESULT OF AN ENGINEERING SURVEY:
12.ADJUSTMENTS OR CORRECTIONS MADE:
� 13.LIST CHANGES IN THE OCCUPANCY HAZARD OR FIRE PROTECTION EQUIPMENT,AS ADVISED BY THE OWNER IN SECTION 1A:
� 14.INSPECTION AND SUGGESTED IMPROVEMENTS WERE DISCUS$ED WITH THE UNDERSIGNED OWNER OR OWNER'S REPRESENTATIVE?
Signature of owner or owner's representative ^k—..-- Date
DUPLICATE TO:
STREET
CITY&STATE ZIP
;:ATT.
#Not Applicable
�: SG4550R1-2 "Explain(No)Answers on Back of Sheet
INSURANCE BUREAU COPY
h �� �[�CO Fire & Simp/exGrin � //
� INSPECTION CONTRACT
tNSPECTION REPORT Security '�.EC'� -- , - �
NO _
� No. REPORT OF INSPECTION A� � 6 1_4Q5 BUREau Fi�E _
CONFERRED WITH '� O��N� NO. _
__ _ __ SET 1 OF 2
REPORT TO BUILDIN R LOCATION INSPECTED
STREET ` INSPECTOR
CITY&STATE ZIP GRINNELL OFFICE ` � PHONE NO. �
-. ATT. DATE '
1.GENERAL Yes N.A.$ No'
A. (To be answered by the Owner or Owner's representative)
a. Have there been any changes in the occupancy classification,machinery or operations since the last inspection?
b. Have there been any changes or repairs to the fire protection systems since the last inspection?
c. If a fire has occurred since the last inspection,have all damaged sprinkler system components been replaced? �
d. Has the i in in all d s stems been checked for ro er itch within the ast five ears? ��'
Pp 9 �Y Y p P P P Y
Date last checked (checking is recommended at least every 5 years)
e. Has the piping in all systems been checked for obstructive materials?
Date last checked (checking is recommended at least every 5 years)
f. Have all fire pumps been tested to their full capacity through the use of hose streams or flow meters within the past 12 months? �
g. Are gravity,surtace or pressure tanks protected from freezing? j-'"
- h. Are any of the sprinklers 50 years old or older? (testing and/or replacement is recommended for such sprinklers) 1%
i. Are any extra high temperature solder sprinklers regularly exposed to temperatures near 300°F?
B. (To be answered by the inspector)
a. Have the sprinkler systems been extended to all visible areas of the building? 1� '
b. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector?
c. Are the building areas protected by a wet system,heated, including its blind attics and perimeter areas,where accessible?
d. Are all visible exterior o enin s rotected a ainst the entrance of cold air?
2.CONTROL VAWES
a. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position?
b. Are all control valves sealed or supervised in the open position?
No. Easily Valve Secured? Supervision
Control of T e Accessible Si ns O en � (Sealed?)
Valves YP 9 P If yes, how. (Locked?) Operational
Valves Yes No Yes No Yes No Yes No (Supvd.?) Yes No
CITY CONNECTION x ,, �. � - t ��
TANK
PUMP
SECTIONAL
SYSTEM L� . _ >L,i , i;j. '
ALARM LINE
' 3.WATER SUPPLIES Pressure Fire Pump&Tank
a. Water supply source? City Gravity Tank Pressure Fire Pump&City
;; Waterflow Test Results Made During This Inspection Pressure Fire Pump& Pond
Test Size Static Static Test Size Static Static
Pipe Test Pressure Flow Pressure Pipe Test Pressure Flow Pressure
Located Pipe Before Pressure After Location Pipe Before Pressure After
, ; -
° 4.TANKS,PUMPS,FIRE DEPT.CONNECTIONS Yes N.A.$ No'
a. Do fire pumps,gravity,surface or pressure tanks appear to be in good external condition?
' b. Are gravity,surface and pressure tanks at the proper pressure and/or water levels? `�
3
� c. Are fire dept.connections in satisfactory condition,couplings free,caps or plugs in place and check valves tight?
d. Are fire dept.connections visible and accessible?
i
t 5.WET SYSTEMS
3 a. No.of systems_�Make&Model '
b. Are cold weather valves in the appropriate open or closed position?
If closed, has piping been drained?
c. Has the owner or owner's representative been advised that cold weather valves are not recommended by NFPA?
d. Have all the antifreeze systems been tested?
e. Date antifreeze systems were tested
f. The antifreeze tests indicate protection to:
system 1 2 3 4 5 temperature
g. Did alarm valves,waterflow alarm indicators and retards test satisfactorily?
#Not Applicable
'�SG4550-R2-1 ����R���+E BUR��� .�.4%�.�, 'Explain(No)Answers on Back of Sheet 2
:: � ��! tyco Fire & Siinp/exG�inne//
Security INSPECTION CONTRACT
NO. _.
___ _
INSPECTION REPORT REPORT OF INSPECTION BUREAU FILE _
NO. NO. __
SET 2 OF 2 �
6.DRY SYSTEMS _ _ _ Yes N.A.$ No"
__
_ _ __- -- _ -
a. No. of systems Make&_'1Godel
; Datelas�tri�tested ____..._. __ •
b. Is the air pressure and priming water levels normal?
c. Did the air compressor operate satisfactorily?
d. Were all low points drained during this inspection?
e. Did all quick opening devices operate satisfactorily?
f. Did all the dry valves operate satisfactorily during this inspection?
g. Do dry valves appear to be protected from freezing?
h. Is the dry valve house heated7
7.SPECIAL SVSTEMS
a. No.of systems Make&Model
Type
b. Were valves tested as required?
- c. Did all heat responsive systems operate satisfactorily7
d. Did the supervisory features operate during testing?
Heat Responsive Devices: Type Type of test
� Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6......
; Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6......
` Valve No. 1......2......3......4......5......6...... Valve No. 1......2......3......4......5......6...... e
Valve No. 1......2......3......4......5......6...... Valve No 1......2......3......4......5......6...... `
Auxiliary equipment: No. Type
Location
Test results
8.ALARMS Yes N.A.$ No'
a. Did the water motors and gong operate during testing?
b. Did the electric alarms operate during testing?
a Did the supervisory alarms operate during testing? -
9.SPRINKLERS—PIPING
a. Do sprinklers generally appear to be in good external condition?
b. Do sprinklers generally appear to be free of corrosion, paint,or loading and visible obstructions?
c. Are extra sprinklers available on the premises? -
d. Does the exterior condition of piping,drain valves,check valves, hangers, pressure gauges,open sprinklers
and strainers appear to be satisfactory?
e. Does the hand hose on the sprinkler system appear to be in satisfactory condition?
10.EXPLANATION OF"NO"ANSWERS(For Sections 16 thru 9):
� 11.THE INSPECTOR SUGGESTS THE FOLLOWING NECESSARY IMPROVEMENTS,HOWEVER,THESE SUGGESTIONS ARE NOT THE RESULT OF AN ENGINEERING SURVEY:
72.ADJUSTMENTS OR CORRECTIONS MADE:
13.LIST CHANGES IN THE OCCUPANCY HAZARD OR FIRE PROTECTION EQUIPMENT,AS ADVISED BY THE OWNER IN SECTION 1A:
i
14.INSPECTION AND SUGGESTED IMPROVEMENTS WFRE bISCUSSED WfTH THE UNDERSIGNED OWNER OR OWNER'S REPRESENTATIVE?
Signature of owner or owner's representative � ;`" Date
DUPLICATE TO:
STREET
CITY&STATE ZIP
ATT.
#Not Appiicable
SG4550R1-2 � 'Explain(No)Answers on Back of Sheet
INSliRAlVC� 3J�i�AU COF'�°