HomeMy WebLinkAbout2012-01007 - addn/remodel/repair CITY OF ORONO ��
� 2750 KELLEY PARKWAY * Z 0 1 2 — 0 1 fd 0 7 *
DATE ISSUED: 10/08/2012
ORONO, MN 55356-
� (952) 249-4600 FAX: (952) 249-4616
ADDRESS : 657 SANDSTONE CIR
PIN : 33-118-23-11-0033
LEGAL DESC : STONEBAY
: LOT 030 BLOCK 001
PERMIT TYPE : ADDITION/REMODEL/REPAIR
PROPERTY TYPE : RESIDENTIAL
CONSTRUCTION TYPE : ADDN/REMODEL/REPA[R
ACTIVITY : 434-RESIDENTIAL
VALUATION : $ 1,935.00
NOTE: REPLACE PIER FOOTING OF SIX DECK POSTS
OK'D BY LYLE OMAN
HIRED BY:TOWNHOME ASSOCIATION
APPLICANT PERMIT FEE SCHEDULE 73.75
DECORAT[VE CONSTRUCTION, INC. PLAN REVIEW 47.94
1 1705 LIVE OAK DR
MINNETONKA, MN 55305- STATE SURCHARGE(VALUATION) 0.97
(612)322-1913 TOTAL 122.66
Minnesota State License#: 20079065 PAID WITH CC# 3874
OWNER
HILDERBRANDT, ROBERT& MOLLIE
657 SANDSTONE CIR
LONG LAKE, MN 55356-
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed according to
the approved plans and specifications,applicable City approvals,and the
State Building Code. This permit is for only the work described and does
not grant permission for additional or related work which requires separate
permits. All provisions of laws and ordinances governing this type of work
shall be compied with whe[her or not specified herein.This permit will
expire and become null and void if construction authorized is not
commenced within 180 days of the date of issuance,or if construction is
suspended tor a period of I 80 days at any time afrer work has commenced.
The applicant is responsible for assuring all required inspections are ��
requested in conformance with the State Building�o�This permit may be �j
revoked at any time for due caus
� � � ��,�i��/`y � . _ '-��l/'� //�� � �
Applican erm' e Sig ur Date � �"�Y
Issued By Signa re Date
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRIBED ABOVE.
%
� . �_� . �E� �� ri ■ ���i �� �r;ffi'p , i� . � �� k� �h�Po���S�;
� p ;pt�
� ������r�g ��C�'i'��� �s�������l�C� '�C9�" �c�E��a��['�C� l ��€����t�a� °� ��
�t� �v�i�e6a�.As, �ioa��, siai��, r�-rQ�f, ��c.}
�
k � M,aiirng Adaress:
��'� %��w�� PO Box oo ' Permit number. ;,��_ �/.�?- �i� 7
' ` � Crystal Bay, MN 55323-DOoo Qate received:
� _ ��' � � \ - �
� ' ' �,r ,t�- � Received bY: �� L- ' �
P
��a N9 �� a���� s, , StreetAddress:
� � � � 2750 Kelle Parkwa � o 0 o a �
�: �,��, � ti �,
�' ���, , �'k� �� Y Y ian.:r..vi..wTe,:: �`
`�s.rrEs�o4w Orono, MN 55356 ��
`�
I To:al Fe�; I g�
� Main: 952-249-4o0D Fax: °52-249-4010 www,ci.orono.mn.us
,. This appfication rorm must be completeo in rull and all required inr'orrr�ation must be suomitted. �
incompiete appficaiions wi(I be returned. (Please print) °�'
u�N=RA� INFORMATIOR: �.� �-� f . /� � �� �".--._.- ���
b �
'° Job Site Address: f5 ��/�.�� ,Q /��✓/'� /' ,�
F�'
Will ti�is be a Parade mf Ffomes, Remodefers S' owcas� Home or other C�isplay Home? i] Yes t�o
�` /f yes, a special event permif is required witn Poirce Department and City Council approval 6G days pnor ro the evenf. Snutfle bus servrce will be `
��: required unless applicant demonstrates sufiicient on-site parking is avarlable. Non-permitted evenfs will not be allowed.
�r
,��, CONTRACTOR!;o.PPLICANT INrORMATl01�!: �
`'` Name: �
�
�� .
. S�ate License � � p p '�xpiration Qate: p�� ���9��G� �
'r Lead Certificafion Number: Expiration Qate: � � �
(Tor work on homes that were construcfec'prior to 1978
Phone: _ 'ofiice) (cell)
' Maiiing Address: ' � � City: ZI�: —o
�- C�ntact Person: c � - Appiicant i : ontractor / Homeowner (Cirde Une)
��. �mail and/or Fax: � �����
�Ry
�, �
PROPcR7'Y OWN�R INrORMl�TIO�
,;.t, Name: �/ , �
�� Phone(�ay): ,�� � �
��;�' Addr�ss: ���/Y- ��,`��% �������,����/QJ CG�/�' 'c�ja�-���--9��Gfd
� � icy. Z{P: �
��; �mail and/or Far. �
w�
�M1� ��
k-� �T
�,: PRC3J=�T IfV=ORM�I'IDR: �
� Type of Project, I i I {�ny earth movement rra�require �
� ,�
� MCWD review&permits: �
❑ Door(s) ❑ Remodel � ❑ Fire Qamage Ninnehana CreekVUatersned District(M�WD} ��
¢. ' ❑ Re-roof, asphalt �Reaair ❑ Storm Damage 1E2G2 Ninnetonka Bivd
�.�
x>'i
�.. ❑ Re-roof, ce�ar ❑ Restoration � o A Deephaven, MN 55391 ��
❑V�at.,r Damag.. �
Pnone: 952-471-Q590 k�
❑ Re-roaf, other(speci'ry) ❑ Sidin � : A ` o `�
g ❑ Oth..r (sp.,cify, � Fax: 52-471-Oo82 �
� ❑Window(s) � www.minnehahacreek.orq ,�
;= �:
,� . , � ��
��= Ove�all Froject �escripiiart: ���' /� r
�� � � ��� ��
,i' �siirratec# Corzs"truciion �afuaiivn of ?roject (ezciuciina �and) � � ��� �
�~s AP� „af ^ �� � _ /_ � �� �.� � l",�7--j��U�.,� /�/�I/�"� � ��
�I�AI�T ��.F�iV01IV_�Q:��M�P�€T. � ;�;
� Aaress to provide ali inrorma'cion required or requested by tne Building Depariment; '��
�~ ,�;:
�~` • Certifies tnat the informaiion suppiied is true and correct to the best of his/her knowledge. Tne applicant recognizes tra: tney � �
�} are solefy responsiole for submitfing a compfete apqficafion being aware t�at upon �ailur� to do so, tne staff has no alternaiive �"
but to reject it unfif i�is complete;
,�
�'`' �
�, � Some or all of tne informafion that you are asksc to provide on tnis appiication is ciassiried by State iaw as eitner private or j �
� confideniia;. ?rivate data is inrorrration wnicn gene;aliy cannot oG qiven to the pubiic but can be given to the subiect of the I ,.;
�° da:a. Confideniial data is inrormafior whicn peneraliy cannot be qiven to eitner the public or tne subiec� o` tne ca�a. Gur I ��
�, i purpose and intended use of this information is to annualiy update our recores and re�ords o� otner povemmen;al agencies I �
�_ ' reauired by taw. If ou retuse te sup�iv tne inrormaiion.tne aopiicatiq mav not bG issued.
�" �/' /� �3,
�.� I�Dpii�anf'S Sigra'ture: �G , . G�i'� � � Cate: ��� ����� �
�Yw: ��t
a;, �ast Updaied: 08-Q9-2011 �
�, ,
„
��,' a
�
. ,
�
� �
September 28, 2012 E n c o m � S S
P
engineering �o�sultants
Ms. Kate Grutzmacher forensi� analy�is
Gittleman Management Corporation � � '
1801 American Boulevard East, Suite 21 / �j �'� /��
Bloomington, MN 55425
�� / �
Re: StoneBay Townhomes ��/,��� ��''� �?,��//7C:.vi�
StoneBay Drive ° .
,.�.
Orono, MN 55144
Enc. Project#: 12-5038
pear Kate:
1.0 INTRODUCTION
1.1 At your request, an investigation of the supporting deck columns at three units
(657, 659, and 661) at StoneBay Townhomes has been conducted.
1.2 Movement of deck support columns was reported.
2.0 OBSERVATIONS
2.1 The columns supporting the rear elevation decks above garage entry doors
were found to be significantly out of alignment and appear to not align properly
with the Sonotube concrete footings installed below grade.
2.2 This condition was confirmed by excavating at three locations. The below
grade footing for the decks do not align with the above grade decorative stone
bases, which consist of concrete and stone veneer, with a hollow fiberglass
composite square post set atop of the stone veneer base and supporting the
deck header. See attached photos 1, 2.
2.3 Encompass also observed no mechanicat connections between the fiberglass
composite posts and deck header, and in one location the fiberglass post
appeared to be deteriorating. See attached photo 3.
2.4 At the time of our visit to the site, two columns were found to be significantly
out of plumb and in an unsafe condition. These columns were temporarily
shored by others.
, �
' • New Sonotubes to be 16" minimum diameter and 48" deep.
• Soil at base of excavation to be verified for appropriate bearing
capacity. A 6" depth of compa�ted aggregate to be placed below
Sonotube.
4.2.3 Column/Stone Base ,
• A new 6x6 treated post should be installed and properly attached at
the base footing connection and at the top at post/header connection
per current IRC and Minnesota State Building Code requirements.
• Construct new stone veneer base around post to match existing.
4.3 Other Units: Based upon cursory obsenration of the other decks, it is our
opinion that similar unstable condition likely exist elsewhere. It is
recommended that all other similar decks and support conditions be evaluated
by a licensed Engineer.
This report is prepared based on observations and review of the material available as of
this date. Our opinions may be revised based on the availability of additional data. The
conclusions contained herein represent our professional opinions.
These opinions were arrived in accordance with accepted engineering practices at this
time and location. No other warranty is implied or intended.
Should you have any questions, please call.
Sincerely,
__.---.�,
'��
�
�; `
. ,�`" � , �
>� �y�
! �
a
Jim Manfted Curt Isemhagen, P.E.
Project Technician Principal
CERTIFICATION
I hereby certify that this plan, specification, or report was prepared by me or under my
- direct supervision and that t am a duly Licensed Professional Engineer under the laws
of the state of Minnesota.
_ � �
�-- ,
Signature: =~�i ---
Date: September 28i 201�_ � Registration Number: 40423
, ,
` 2.5 One column at unit 657 continued to move away from below the deck; this
column assembly was ultimately removed by Encompass personnel for safety
and also to inspect the connection befinreen the column and Sonotube
concrete footing. See attached photo 4.
2.6 The column constructed on the concrete footing was ofFset considerably and a
rebar dowel was set on the very outside edge of the below grade Sonotube
footing. See attached photo 5.
3.0 ANALYSIS/CONCLUSIONS
3.1 It is our opinion that the columns constructed at units 657, 659, and 661 are
constructed incorrectly. The improper placement of the concrete footings
created an offset condition where concrete bases had to be built partially off of
supporting Sonotubes to accommodate post alignment w�h the deck headers.
3.2 The above condition has led to incorrect footing and base connections; along
with a large overhanging base that is misaligned, creating eccentric loads into
the footing, causing the rotation of the columns and the footings. The offset
base is also susceptible to frost heave which is evident due to the observed
damage to the asphalt driveways around the columns.
3.3 Encompass betieves the supporting deck posts at units 657, 659, and 661 are
structurally inadequate and pose an unsafe condition. The significant offset
and improper connection befinreen the post base and footing, and the absence
of a mechanical connection at the top of the post and header is allowing
further deformation of these support columns.
3.4 Based upon cursory observation of the other decks, it is our opinion that
similar unstable condition may exist elsewhere. An evaluation of additional
units beyond 657, 659, and 661 is outside the scope of this analysis and
report.
4.0 RECOMMENDATIONS
4.1 All rear deck support columns and supporting footings at un�s 657, 659, and
661should be immediately removed and replaced.
4.2 Permanent repairs should generally consist of the following:
4.2.1 Shoring: Shore each deck in order to remove the decorative stone and
fiberglass column.
4.2.2 Footings:
• Remove and replace each Sonotube footing
;,,
av
� ,'..
�?
. . tR . ..;tip'
' �L ' .� �'�_�' .. � �' L��P�'."� K . • � .
R'
.
a . �
. . r ��.�:.. � .. .���� ti�/ Hr'� � _ ` ..
. y{�' .•�� �
'a . . , . f,. ye� �. . .
�. `�.y . . .. ^ �}r �# � �.T ::�..
.� � �
P
! _', ...'.4., f�-� !� 1 F�.��� � � �� � k�•�': A.. � — •
-
�,. . ,;ti , � . , ' ..� .., .
"* .!,� ,Y`,; ' �, � .
. .�`. . � {. ` .
• ,,t . "'. `"�,�,t^a �~, - � , ._,.
. �_. . ..t. . ' . ' � .. ,Yx ! . � . � 'i.. . .., .
, ^ . , �� .. ' .�e ., � � ...
. ' H�e� ' " . - ~��, .
� '•� k 4� ���
. ' � ' ' � ' .. � � .. •. � - d� `'��t. .
i ; �' .. ` ' . � � . �,., � � �s�'� ...
` .. � F,J . ♦� � •. J. ,. � a}; �u4 1. . J'�•'•. � •.> •
; . •,� ' • .'' r••
. .�,... ;'„ �� . • . . � ' "i, .tti, ... - , , r �
Photo 1 showing offset column from footing.
r
Y
!
; •
�.
6 � '
� �
N ��,� '
� ^ �� � . ��
� `� . ,
�,�"' �,z
�
��:
�
��
Photo 2 showing hollow fiberglass composite post.
��,� r1{ 1 � .C�_i�.l..•� � � - s ^" .
, .
.: .
•�•w� jti4,' •4� . . t��.
R i 6'""� :�i>{; � �, ,
�" � ��'�' '•�"'� " ��.`�;�,�✓". ,:�3~? . �,�
;� .
.S,�- .. j�f r . �� ..i�� � �
t �. .� ' �t..".
��`�! ,�. s . \ _� �
�` : . �
a� ' °�'2� ~ . j'�.�.' a �
`� � ,.�'.. .":�,. . .� � ,,,
.; . . �, �
_ ��t,- ,-�x�. � ,.
. � , .. .;�r..-
� � ' :: �, .
�
.
� � , .� .1•! I ;� .,� p '`�. � a
, � -' � ;;,#
� :� ��
�+ �` '{ ' .
-. "� �+.
•�� ! t` ,�� �
� �.:_.,�r� , 42 �.2. ;t. .R: f � � t . '`, �• �
� jl��� �t 's_ , Ar'�� e;
O �LV 3 r
. /'~ '3" ` � ��l�� ��`�•l �+:•�t�.
' L J � �" 'S� ��' �� V ' . 6 ..' . .
, r ��At r•� � t ..S � 'Jr� l +•�.
Y r i
��• r � .r.£':'
�•r�, ,s�"•'
Qa` +.�' *`��
��� � w{���,t�{�:��,. J � �t 1 ,•�,r'•���� � 3�.
.�-.� w.,'�.: . � .IJ.:.s:'�_ .. r` , � _ ..�.:. �. . �-� � nf��..
Photo 5 showing offset location of pin installed in concrete footing.
��:
.:�,
��
�
�
i
f
;�;<�...
��.
Photo 3 showing no mechanical connection befinreen post and header.
.�1� � �� �
x��:.
..
" ' r-
;
- �..� w,.
�. �� f�,�;
�,,y,.. .". 'e q ,\ �:. M;:Z.. . �/'+.., ��.
. '''�wMJn"r'- "�'�.. . �,�' '_.-,��M�et_.
. . _ '��.. � - . .
_ ,. , . , .
��� s
k� ~ � .u+..X.:Adt� `
. �' j �` .�,,, • ��,';
' y- ..�� • _ 'x�'.
. ' � � -� __.�— • " '- $ �4� �;����
. . , .. . •��I��.�: . . "�� , . , � �, \ �4-f'✓'
. ,a . " : .� • � .i 3 :"*,.
, � .s � � _�
. �t r� x� � * � � �
' ' '�F ' M , . t� ���e'ph,� f •_ � �4� `q, `.
� A ,�J
;d�` �Y���_ �-� . � � � . . " .. a.f . . . ? ..v`�+R_a-
Photo 4 showing column that was removed.