Laserfiche WebLink
BUILDING LEAKAGE TEST <br /> ;�= ���: ,�,,,���'E w <br /> a.,: ir�, �" t' <br /> Date of Test: 1/31/2016 Test File:559 Park Lane <br /> Customer. Technician: <br /> Project Number. <br /> Buiiding Address: 559 Park Lane <br /> Test Results <br /> 1. Airflow at 50 Pascals: 1178 CFM50 <br /> (50 Pa=0.2 w.C.) 1.19 ACH50 <br /> 2. Leakage Area: 64.8 in2 LBL ELA�4 Pa <br /> 3. Building Leakage Cunre: Flow Coefficient(C)= 92.6 <br /> Exponent(n)=0.650(Assumed) <br /> 4. Test Settings: Test Standard: RESNET One-Point Test <br /> Test Mode: Depressurization <br /> 5. Accuracy Level StandaM Level of Accuracy Test <br /> Infiltration Estimates <br /> 1. Estimated Average Annual Infiftration Rate: <br /> 2. Estimated Design Infiltration Rate: <br /> Coat Estimates <br /> 1. Estimated Cost of Air Leakage for Heating: <br /> 2. Estimated Cost of Air Leakage for Cooling: <br />