1111 A11-1:715C-417:,;777::1.; 4':1L f ?. ` r' Job Number: 1 <br /> Report Description:Residential(1) <br /> Actual Flow Minimum Flow K-Factor Pressure Density Coverage <br /> Device (gpm) (gpm) (K) (psi) (gpmpft2) (Foot) <br /> Sprinkler 100 13.12 12.96 4.9 7.170 0.051gpm/ft2 256ft2 <br /> c> Sprinkler 101 12.96 12.96 4.9 7.000 0.051gpm/t2 256ft2 <br /> b Most Demanding Sprinkler Data <br /> (cyj,©M.E.P.CAD, Inc. ` AutoSPRINK®12 v12.0.59.0 10/12/2016 12:33:02PM Page 3 <br />