<br /> Rhvac-Residential&Light Commercial HVAC Loads it Elite Software Development,Inc.
<br /> - Sabre Plumbing&Heating 2345 Oliver Hill Orono
<br /> Plymouth.MN 55447 Page 4
<br /> Total Building Summary Loads y,
<br /> -tfro0 0 ci •�'�� .r � `�.t°�°t�. #F.-� cY�Ym Y X � ��'f'� �L�s��� �� x n � "'d �,M M ���t }� a'�,o x �'3 �.
<br /> LOW EE: Glazing-Builder Grade Low E Windows& 487.3 13,564 0 14,180 14,180
<br /> Sliding Door.32 U value .30 SHGC, u-value 0.32,
<br /> SHGC 0.3
<br /> 11J: Door-Metal-Fiberglass Core 37.8 1,972 0 544 544
<br /> 15A-10sffc-8:Wall-Basement, concrete block wall, R-10 1104 4,034 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> R-20 12F-Osw:Wall-Frame, Custom, no board insulation, 2071 11,892 0 1,817 1,817
<br /> siding finish,wood studs
<br /> RJ R20 Closed Cell:Wall-Frame, Custom,Spray Foam R- 444 1,932 0 344 344
<br /> 20
<br /> R49- 16B-49: Roof/Ceiling-Under Attic with Insulation on 1810 3,622 0 1,998 1,998
<br /> Attic Floor(also use for Knee Walls and Partition
<br /> Ceilings), Custom, R49 Blown Insulation-vented
<br /> attic, asphalt shingles
<br /> 21A-20-c: Floor-Basement, Concrete slab, any thickness, 1344 3,157 0 0 0
<br /> 2 or more feet below grade, no insulation below floor,
<br /> carpet covering, shortest side of floor slab is 20'wide
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 240 731 0 67 67
<br /> R-30 blanket insulation,any cover
<br /> Subtotals for structure: 40,904 0 18,950 18,950
<br /> People: 5 1,000 1,150 2,150
<br /> Equipment: 901 4,116 5,017
<br /> Lighting: 1250 4,263 4,263
<br /> Ductwork: 2,143 174 438 612
<br /> Infiltration:Winter CFM: 0,Summer CFM:0 0 0 0 0
<br /> Ventilation:Winter CFM: 190, Summer CFM: 190 7,057 4,409 1,054 5,463
<br /> Humidification (Winter) 17.10 gal/day: 6,270 0 0 0
<br /> Total Building Load Totals: 56,374 6,483 29,971 36,454
<br /> .i.,:",'. RO' I
<br /> Total Building Supply CFM: 1,352 CFM Per Square ft.: 0.301
<br /> Square ft.of Room Area: 4,498 Square ft. Per Ton: 1,481
<br /> Volume(ft3)of Cond. Space: 37,328
<br /> :Q
<br /> Y: .a rx''-` Y -5.t'�vp 'e• :�^'4, s Y s i .- '*'S %31'v "r`.. 'r¢yt^ 1 ?" ,,.. >
<br /> � a ? � a .�u :�: '+ ,tJ ,.. :t_..� a,. ,. 4 . S�`x. s�z��r. �r .,�tr� � �+. ��i h,'�.®m,.•� ., . . .-� . �,s� .7�.„
<br /> Total Heating Required Including Ventilation Air: 56,374 Btuh 56.374 MBH
<br /> Total Sensible Gain: 29,971 Btuh 82 %
<br /> Total Latent Gain: 6,483 Btuh 18 3/0
<br /> Total Cooling Required Including Ventilation Air: 36,454 Btuh 3.04 Tons(Based On Sensible+ Latent)
<br /> M52.:k c,0 :Fad':
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.