<br /> Total Building Summary Loads
<br /> LOW EE: Glazing-Builder Grade Low E Windows& 487.8 13,580 0 12,807 12,807
<br /> Sliding Door.32 U value .30 SHGC, u-value 0.32,
<br /> SHGC 0.3
<br /> 11J: Door-Metal- Fiberglass Core 37.8 1,972 0 544 544
<br /> 15A-10sffc-8: Wall-Basement, concrete block wall, R-10 1312 4,794 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> R-20 12F-Osw: Wall-Frame, Custom, no board insulation, 2544.5 14,612 0 2,234 2,234
<br /> siding finish, wood studs
<br /> RJ R20 Closed Cell: Wall-Frame, Custom, Spray Foam R- 522 2,272 0 404 404
<br /> 20
<br /> R49- 16B-49: Roof/Ceiling-Under Attic with Insulation on 1733 3,468 0 1,913 1,913
<br /> Attic Floor(also use for Knee Walls and Partition
<br /> Ceilings), Custom, R49 Blown Insulation-vented
<br /> attic, asphalt shingles
<br /> 21A-20-c: Floor-Basement, Concrete slab, any thickness, 1386 3,256 0 0 0
<br /> 2 or more feet below grade, no insulation below floor,
<br /> carpet covering, shortest side of floor slab is 20'wide
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 350 1,066 0 98 98
<br /> R-30 blanket insulation anicover
<br /> Subtotals for structure: 45,020 0 18,000 18,000
<br /> People: 5 1,000 1,150 2,150
<br /> Equipment: 901 4,116 5,017
<br /> Lighting: 1250 4,263 4,263
<br /> Ductwork: 3,088 253 635 888
<br /> Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Ventilation: Winter CFM: 190, Summer CFM: 190 7,057 4,409 1,054 5,463
<br /> Humidification (Winter) 17.04 gal/day : 6,249 0 0 0
<br /> AED Excursion: 0 0 2148 2,148_
<br /> Total Building Load Totals: 61,414 6,562 31,366 37,929
<br /> Total Building Supply CFM: 1,416 CFM Per Square ft.: 0.314
<br /> Square ft. of Room Area: 4,505 Square ft. Per Ton: 1,425
<br /> Volume(ft3)of Cond. Space: 37,426
<br /> -x r
<br /> z '
<br /> Total Heating Required Including Ventilation Air: 61,414 Btuh 61.414 MBH
<br /> Total Sensible Gain: 31,366 Btuh 83 %
<br /> Total Latent Gain: 6,562 Btuh 17 %
<br /> Total Cooling Required Including Ventilation Air: 37,929 Btuh 3.16 Tons(Based On Sensible+ Latent)
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> M:\...\2320 Oliver Hill Orono.rh9 Wednesday, December 20, 2017, 3:26 PM