Laserfiche WebLink
MEMORANDUM <br /> T • R • A <br /> To: Mr. Lyle Oman, Building Official, City of Orono <br /> From: Victor Pechaty, Ted Rozeboom Architects <br /> Date: 23 December 1996 <br /> Subject: Orono Ice Arena: Code Issues <br /> Dear Mr. Oman, <br /> This memo outlines responses to the various code issues you raised in our meeting on December <br /> 4, 1996. <br /> 1. Handrails at Bleacher Aisles <br /> Section 1021.5.6 requires handrails located in the center of the aisles at aisles with seating on <br /> either side.The design will be revised to provide 48" wide aisles with a center handrail detailed <br /> to comply with section 1021.5.6. <br /> 2. Non-Slip Surface at Ramp ✓ <br /> The architect will issue a supplementary instruction for the concrete contractor to provide an <br /> ANSI compliant non-slip surface at the ramp at the south end of the arena. <br /> 3. Exits at Meeting Room✓ <br /> An exit light is to be provided at door#10B (the plans show an exit light at door#1 04 Panic <br /> hardware iE to be provided at door#1 OA (the specifications call for panic hardware at door <br /> #1OB). <br /> 4.Roof Assembly -✓ <br /> The roof acsembly specified meets a minimum Class B rating as required by code. <br /> 5.Roof Slc pe <br /> The roof st-ucture is sized and specified to support the additional loading associated with 1/8" <br /> per foot slope. The signed structural drawings provide adequate confirmation of the structural <br /> design. <br /> 6. Fare Ala-m - <br /> The fire alai in for this type of facility is to be monitored. This has been confirmed with Premier <br /> Electric, thy. electrical contractor. <br /> Tcd Rozcboom.-krchitects • 2965 Casco Point Road.Wayzata,Minnesota 55391 • Tel: (612)471-5780 Fax; (612)471-8740 <br /> Z:00 NODEBZOH (I3.L (ALS TLf gT9 Zvi et:uT 96-EZirT <br />