RECEIVED
<br /> DN-7070:K•A-10
<br /> NFS2-3030 MAY 31 2016
<br /> Intelligent Addressable!Cn OF ORONO
<br /> NOTIFIER
<br /> Fire Alarm System by Honeywell
<br /> Intelligent Fire Alarm Control Panels
<br /> General
<br /> The NFS2-3030 is an intelligent Fire Alarm Control Panel
<br /> (FACP) designed for medium- to large-scale facilities. Fire —emergency detection and evacuation are extremely critical to _
<br /> life safety,and the NFS2-3030 is ideally suited for these applis f
<br /> cations.The NFS2-3030 is part of the ONYX®Series of prod
<br /> ucts from NOTIFIER.The NFS2-3030 is ideal for virtually any —
<br /> application because it features a modular design that is config- - —ured per project requirements. With one to ten Signaling Line
<br /> Circuits SLCs the NFS2-3030 supports upto 3,180 intelli-
<br /> gent
<br /> PP
<br /> gent addressable devices.
<br /> Information is critical to fire evacuation personnel, and the
<br /> NFS2-3030's large 640-character Liquid Crystal Display(LCD)
<br /> presents vital information to operators concerning a fire situa-
<br /> tion,fire progression,and evacuation details.
<br /> A host of other options are available,including single-or multi-
<br /> channel voice;firefighter's telephone; LED, LCD,or PC-based
<br /> graphic annunciators; networking; advanced detection prod- 7070cov9.ia9
<br /> ucts for challenging environments, and many additional
<br /> options. NFS2-3030 (left)
<br /> Features and NFS2-3030 with DVC audio option (right)
<br /> • Certified for seismic applications when used with the appro-
<br /> priate seismic mounting kit. • History file with 4000-event capacity in nonvolatile memory,
<br /> • Approved for Marine applications when a marine-listed ver plus separate 1000 event alarm only file.
<br /> sion is used with marine-listed compatible equipment. See • Advanced history filters allow sorting by event, time, date,
<br /> DN-60688. or address.
<br /> • Complies with UL 2572 Mass Notification Systems (NFS2- • Alarm Verification selection per point, with automatic
<br /> 3030 version 20 or higher) counter.
<br /> • One to ten isolated intelligent Signaling Line Circuits(SLC) • Autoprogramming and Walk Test reports.
<br /> Style 4,6 or 7. • Multiple central station communication options:
<br /> • Up to 159 detectors and 159 modules per SLC,318 devices -Standard UDACT
<br /> per loop/3,180 per FACP or network node.Detectors can be -Internet
<br /> any mix of ion, photo, laser photo, thermal, or multi-sensor
<br /> -Internet/GSM
<br /> detectors; modules can be addressable pull stations, nor-
<br /> mally open contact devices, two-wire smoke detectors, • Positive Alarm Sequence(PAS) Presignal.
<br /> notification,or relay modules. • Silence Inhibit and Auto Silence timer options.
<br /> • Large 640-character LCD backlit display(16 lines x 40 char- • Field-programmable on panel or on PC,with VeriFire Tools
<br /> acters)or display-less(a node on a network). program,also check,compare.
<br /> • Network options: • Non-alarm points for lower priority functions.
<br /> -High-speed network for up to 200 nodes (NFS2-3030, • Remote ACK/Signal Silence/System Reset/Drill via monitor
<br /> NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, modules.
<br /> ONYXWorks,NFS-3030,NFS-640,and NCA). • Up to 1000 powerful Boolean logic equations.
<br /> -Standard network for up to 103 nodes (NFS2-3030, . Supports SCS Series smoke control system in both HVAC
<br /> NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, and FSCS modes.
<br /> ONYXWorks,NCS,NFS-3030,NFS-640,NCA,AFP 200, • FM6320 approved Gas Detection System with FMM-4-20
<br /> AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes module and any FM listed gas detector.
<br /> when DVC-EM is used in network paging.
<br /> •
<br /> • Built-in Alarm,Trouble,Security,and Supervisory relays. EIA 232 printer port.
<br /> •
<br /> • VeriFire®Tools online/offline program option. EIA 485 annunciator port.
<br /> • With built-in Degraded Mode operation,the system is capa- 640-CHARACTER DISPLAY FEATURES
<br /> ble of general alarm if a fire alarm condition is present even • Backlit,640-character display.
<br /> if the central processing unit(CPU)fails. • Program keypad:full QWERTY keypad.
<br /> • Weekly Occupancy Schedules allow changing sensitivity by
<br /> time of day and day of week. • Up to nine users, each with a password and selectable
<br /> access levels.
<br /> • EIA-485 annunciators,including custom graphics.
<br /> DN-7070:K•12/20/2013—Page 1 of 8