TFP161
<br /> Page 4 of 6
<br /> K SPRINKLER TEMPERATURE IQUIBD SPRINKLER FINISH 1101
<br /> TYPE RATING COLOR NATURAL CHROME POLYESTER*** LEAD WAX WAX-OVER-LEAD
<br /> BRASS PLATED COATED COATED COATED
<br /> 135°F(57°C) Orange
<br /> 155°F(68°C) Red
<br /> HORIZONTAL 175°F(79°C) Yellow 1,2,3,4,9 1,2,3,9 1,2,3,9
<br /> SIDEWALL 1,2,3,9
<br /> (TY3351) 200°F(93°C) Green
<br /> Figure 1
<br /> 5.6 286°F(141°C) Blue 1**,2**,3**,9**
<br /> 1/2"
<br /> NPT 360°F(182°C) Mauve 1,2,4,9 1,2,9 N/A
<br /> RECESSED 135°F(57°C) Orange
<br /> HORIZONTAL 155°F(68°C) Red
<br /> SIDEWALL 1,2,3,9 N/A
<br /> (TY3351)* 175°F(79°C) Yellow
<br /> Figure 3 200°F(93°C) Green
<br /> 135°F(57°C) Orange
<br /> VERTICAL 155°F(68°C) Red
<br /> SIDEWALL 5,6,7,9
<br /> 5.6 (TY3451) 175°F(79°C) Yellow 4,5,6,7,8,9
<br /> 1/2" PENDENT 5,6,7,9
<br /> NPT or 200°F(93°C) Green
<br /> UPRIGHT 286°F(141°C) Blue 5**,6**,7**,9**
<br /> Figure 2
<br /> 360°F(182°C) Mauve 4,5,6,8,9 N/A
<br /> Notes:
<br /> 1. UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector-to-ceiling distance
<br /> 2. C-UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector-to-ceiling distance
<br /> 3. FM Approved for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector-to-ceiling distance
<br /> 4. LPCB Approved(Ref.No.094a&007k)at a 4 to 6 inch(100 to 150 mm)deflector-to-ceiling distance
<br /> 5. UL Listed for use in Light and Ordinary Hazard Occupancies
<br /> 6. C-UL Listed for use in Light and Ordinary Hazard Occupancies
<br /> 7. FM Approved for use in Light Hazard Occupancies
<br /> 8. LPCB Approved(Ref.No.094a&007k)
<br /> 9. Approved by the City of New York under MEA 354-01-E
<br /> 10.Where Polyester Coated,Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as corro-
<br /> sion-resistant sprinklers.Where Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as corrosion-
<br /> resistant sprinklers.
<br /> Installed with Style 10(1/2-NPT)or Style 40(3/4°NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable
<br /> `• 150°F(66°C)maximum ceiling temperature
<br /> `•• Frame and deflector only
<br /> N/A-Not Applicable
<br /> TABLE A
<br /> SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
<br /> LABORATORY LISTINGS AND APPROVALS