Laserfiche WebLink
0 <br /> Memorandum to Meeting Attendants <br /> Page Two <br /> 11. The Second and Third floors were reviewed by Bill and will be sufficiently <br /> covered with four horn/strobe devices each. <br /> 12. Smoke detectors will be installed throughout the corridors and common spaces. <br /> 13. Heat detectors will be installed in labs in lieu of smoke detectors. <br /> Intermediate/Elementary School <br /> 1. The existing fire alarm system will be replaced with a fully addressable system <br /> including horn/strobe devices installed throughout the building per ADA. <br /> 2. The new FACP will replace the existing panel located in the electrical room near <br /> the pool. The existing panels will be used as connection cabinets if required. <br /> 3. There will be(4)remote annunciator panels installed. There will be recessed <br /> FAA's located in the Link entry,the Elementary School entry,and the <br /> Intermediate School entry. A surface mounted FAA will be installed near the <br /> maintenance office in the basement of the Intermediate School. Bill reviewed and <br /> approved locations. <br /> 4. There will be manual pull stations installed near the basement boiler room,the <br /> Elementary boiler room,the Elementary office,the Link office,and the <br /> Intermediate office only. All existing pull stations will be removed. <br /> 5. The exterior fire alarm horn will be replaced with a horn/strobe device. <br /> 6. We will proceed with installing smoke detectors in the gymnasium unless directed <br /> otherwise per Bill. <br /> 7. Heat detectors are not required in sprinkled storage rooms. <br /> 8. The Elementary classrooms with windows at the corridor will not be required to <br /> have individual horn/strobe devices. <br /> 9. The existing addressable devices located in the media center will be reconnected to <br /> new FACP. Existing devices to be reprogrammed accordingly. <br /> 10. Smoke detectors will be installed throughout the corridors and common spaces. <br /> 11. Heat detectors will be installed in labs and art rooms in lieu of smoke detectors. <br /> cc: Attendants <br /> Scott McQueen,Wold <br /> kat/0 1 059/may0 1 <br />