Page 4 of 6 TFP962 <br /> SWITCH TERMINAL CONNECTIONS <br /> UNINSULATED CLAMPING SEVERED <br /> LOOPED SECTION CAUTION: PLATE STRIPPED <br /> SINGLE An uninsulated section of a TERMINAL ENDS <br /> CONDUCTOR single conductor is not %1,04 <br /> SEPARATE <br /> permitted to be looped arounCONDUCTORS <br /> CLAMPING . the terminal and serve as two <br /> PLATE separate connections.The , <br /> TERMINAL wire must be severed to serve ' INCOMING <br /> as two separate connections, >%10. <br /> thereby providing supervision <br /> of the connection in the event <br /> that the wire becomes <br /> dislodged from the terminal. <br /> OUTGOING <br /> IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD <br /> WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS <br /> CONTACTS SPDT(Form C) END OF LINE <br /> LOCAL RESISTOR <br /> CONTACT RATING .... 5A @ 125 VAC SIGNAL <br /> 2.5A @ 30 VDC DEVICE <br /> NC <br /> NO �1 NC yio_yr <br /> NO• NC --f// M <br /> COM <br /> COM CONTROL <br /> POWER PANEL <br /> NO FLOW NON-SUPERVISED STYLE B/CLASS B <br /> CONDITION CIRCUIT SUPERVISED CIRCUIT <br /> (SEE NOTE) <br /> NOTE: <br /> For supervised circuits,see"Switch Terminal Connections"above.The Waterflow Alarm <br /> Switch has two switches,one can be used to operate a central station,proprietary or remove <br /> signaling unit,while the other contact is used to operate a local audible or visual annunciator. <br /> COVER TAMPER SWITCH(ULC ASSEMBLIES ONLY) <br /> CONTACTS SPDT(Form C) <br /> CONTACT RATING .... 3A @ 250 VAC <br /> 5A @ 125 VAC <br /> 1mA@ 5 VDC min. <br /> NO • NC <br /> COM <br /> CONTACTS SHOWN <br /> WITH COVER IN PLACE <br /> FIGURE 3 <br /> WIRING GUIDANCE <br />