^ ° <br /> PAGE 06 <br /> VIKING AUTOMATIC SPRINKLER CO. <br /> ORONO SCHOOL <br /> _______________________________________ <br /> | | DEMAND <br /> | | <br /> | | SYSTEM FLOW = 168. 16 GPM <br /> | * STATIC | INSIDE HOSE = 0.00 GPM <br /> | . | OUTSIDE HOSE = 100.00 GPM <br /> | . | RACK = 0.00 GPM <br /> | . <br /> It ----------- <br /> | . | TOTAL FLOW DEMAND = 268. 16 GPM <br /> | . | TOTAL PRESS DEMAND = 46.560 PSI <br /> | * RESIDUAL | ELEVATION = 0.000 FT. <br /> | . |--------------------------___________ <br /> | ~ | WATER SUPPLY DATA <br /> | . PRESS @ DEMAND | <br /> | ^ . | STATIC PRESS = 59.500 PSI <br /> | SYSTEM *P . | RESID. PRESS = 20.000 PSI <br /> | DEMAND v . | RESID FLOW = 2050.00 GPM <br /> | .-------------*< *Q > . FLOW @ |------------------------------------- <br /> | . TOTAL . DEMAND | CALCULATED DATA <br /> | . DEMAND . | <br /> | . . | PRESS @ DEMAND = 58.582 PSI <br /> | . . | FLOW @ DEMAND = 1121 .43 GPM <br /> | FLOW @ * | *P = 12.022 PSI <br /> |* ELEVATION 20 PSI '.| *Q = 853.27 GPM <br /> | | FLOW AVAIL @ <br /> | | 20.000 PSI = 2049.99 GPM <br /> -------------__--------------__________ <br /> ' <br />