Laserfiche WebLink
yc rR ( nat Liglit'{tpltlEtlir+ ai H�11C L# da 613 8o'itw8ru,tJevelsfp{ITr�nt;,lf1+�; <br /> IElhe Supply Ind ' Egad-tirarto l�srliing <br /> r <br /> aro <br /> 'e{{ct Report <br /> Project Title: Easco-Orono Parking <br /> Project Date: Tuesday, February 06,2018 <br /> Client Name: Easco-Orono Parking <br /> Company Name: Easco-Orono Parking <br /> Reference City: Minneapolis/St. Paul AP, Minnesota <br /> Building Orientation: Front door faces North <br /> Daily Temperature Range: Medium <br /> Latitude: 44 Degrees <br /> Elevation: 834 ft. <br /> Altitude Factor: 0.970 <br /> Outdoor Outdoor Outdoor Indoor Indoor Grains <br /> Dry Bulb Wet Bulb ReLliutn ReLkLuID ry Bulb Difference <br /> Winter: 0.14 -11.42 n/a n/a 70 n/a <br /> Summer: 90 73 45% 50% 72 38 <br /> o� <br /> Total Building Supply CFM: 4,517 CFM Per Square ft.: 0.588 <br /> Square ft.of Room Area: 7,680 Square ft. Per Ton: 806 <br /> YVw�o«(lu�me(ft'): 135,680 <br /> rl3F ildlr� Fr <br /> Total HeatingRequired Including Ventilation Air: 332,170 Btuh 33 <br /> q 9 2.170 MBH <br /> Total Sensible Gain: 96,424 Btuh 84 % <br /> Total Latent Gain: 17,888 Btuh 16 % <br /> Total Cooling Required Including Ventilation Air. 114,312 Btuh 9.53 Tons(Based On Sensible+Latent) <br /> Rhvac is an ACCA approved Manual J and Manual D computer program. � <br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. <br /> All computed results are estimates as building use and weather may vary. <br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at <br /> your design conditions. <br /> C:\...\Easco-Orono Parking.rh9 Tuesday, February 06,2018,2:56 PM <br />