Laserfiche WebLink
�� NOTIFIER Device Current D <br /> raw <br /> by Haneywe0 <br /> NFS-320 Fire Alarm Control Panel <br /> Quantity x[device current draw]=total current draw per device(in amps) <br /> Part Number Qty Primary Non-Alarm Primary Alarm Secondary Non-Alarm <br /> CPU-320 1 x 0.25000 =0.25000 x 0.25000 =0.25000 x 0.25000 =0.25000 <br /> CPS-24 1 x 0.00000 =0.00000 x 0.00000 =0.00000 x 0.04000 =0.04000 <br /> FCPS-24S8 Power Supplies 4 x 0.00000 =0.00000 x 0.00000 =0.00000 x 0.26000 =1.04000 <br /> FDU-80 1 x 10.064001=0.06400 x 0.06400 =0.06400 x 0.02500 =0.02500 <br /> UDACT-2 Communicator 1 x 0.05200 =0.05200 x 10.087001=0.08700 x 10.052001=0.05200 <br /> FSP-851 41 x 0.00030 =0.01230 x 0.00000 =0.00000 x 0.00030 =0.01230 <br /> NBG-12LX 8 x 0.00038 =0.00300 x 0.00000 =0.00000 x 0.00038 =0.00300 <br /> FRM-1 31 x 0.00026 =0.00791 x 0.00000 =0.00000 x 0.00026 =0.00791 <br /> FDM-1 6 x 0.00075 =0.00450 x 0.00000 =0.00000 x 0.00075 =0.00450 <br /> DNR 28 x 0.00000 =0.00000 x 0.00000 =0.00000 x 0.00000 =0.00000 <br /> SLC Loo Device Activation Current 1 x 0.00000 =0.00000 x 0.40000 =0.40000 x 0.00000 =0.00000 <br /> Total(Amperes): 0.3937 Al0.8010 Al1.4347 A <br /> SecondaryPart Number Qty <br /> Total Primary Alarm Load-C2 1 x 0.80100 =0.80100 <br /> CPS-24 1 x 0.04000 =0.04000 <br /> FCPS-2458 Power Supplies 1 x 27.50500 =27.50500 <br /> Total(Amperes):1 28.3460 A <br />