DN-7087:C1
<br /> SpectrAlert®,Advance
<br /> _ �J
<br /> Selectable Output; NOTIFIER
<br /> Notification Alliances by H o n eywe I I
<br /> AudioNisual Devices
<br /> General
<br /> System Sensor® SpectrAlert® Advance selectable-output
<br /> horns,strobes and horn/strobes are rich with features guaran-
<br /> teed to cut installation times and maximize profits.The Spec-
<br /> trAlert Advance series of notification appliances is designed to \`
<br /> simplify your installations, with features such as: plug-in e
<br /> designs,instant feedback messages to ensure correct instal- indoor Celling Outdoor Ceiling
<br /> tion of individual devices, and eleven field-selectable candela Horn/Strobe Strobe
<br /> settings for wall and ceiling strobes and horn/strobes.
<br /> More specifically, when installing Advance products, first
<br /> attach a universal mounting plate to a four-inch square, four-
<br /> inch octagon, or double-gang junction box. The two-wire $
<br /> mounting plate attaches to a single-gang junction box.
<br /> Then, connect the notification appliance circuit wiring to the
<br /> SEMS terminals on the mounting plate. Indoor Wall Indoor Coiling
<br /> Finally,attach the horn,strobe,or horn/strobe to the mounting Horn/Strobe Strobe
<br /> plate by inserting the product's tabs in the mounting plate's
<br /> grooves. The device will rotate into position, locking the prod-
<br /> ucts pins into the mounting plate's terminals. The device will
<br /> temporarily hold in place with a catch until it is secured with a
<br /> captured mounting screw. t
<br /> a A
<br /> SpectrAlert Advance products allow you to choose: m
<br /> e e
<br /> • 12 or 24 volts. Indoor Wall Outdoor Wall
<br /> • 15, 15/75,30,75,95, 110, 115, 135, 150, 177,or 185 can- Horn Strobe
<br /> dela by way of a rear-mounted slide switch and front view- • Outdoor products rated from-40°F and 151°F(-40°C and
<br /> ing window. 660C).
<br /> • Horn tones and volume by way of a rotary switch. • Outdoor products rainproof per UL50 (NEMA 3R) and
<br /> • The SpectrAlert Advance series includes outdoor notifica- weatherproof per NEMA 4X,IP56
<br /> tion appliances. Outdoor strobes and horn/strobes (two- • Minimal intrusion into the backbox.
<br /> wire and four-wire)are available for wall or ceiling.Outdoor • Horn rated at 88+dbA at 16 volts.
<br /> horns are available for wall only.All System Sensor outdoor . Rotary switch for tone selection.
<br /> products are rated between-40°F and 151°F (-40°C and . Three horn volume settings.
<br /> 66°C)in wet or dry applications.
<br /> Models available: • Electrically compatible with existing SpectrAlert products.
<br /> • Indoor wall-mount: horn, strobe,2-wire horn/strobe, 4-wire Engineering Specifications
<br /> horn/strobe.
<br /> • Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire SpectrAlert Advance horns, strobes, and horn/strobes shall
<br /> horn/strobe. mount to a standard 4.0° x 4.0" x 1.5• (10.16 x 10.16 x 3.81
<br /> • Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4- cm)backbox,4.0•(10.16 cm)octagonal backbox,or a double-
<br /> wire horn/strobe. gang backbox.Two-wire products shall also mount to a single-
<br /> gang 2.0•x 4.0•x 1.875°(5.08 x 10.16 x 4.763 cm)backbox.A
<br /> • Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire universal mounting plate shall be used for mounting ceiling
<br /> horn/strobe. and wall products. The notification appliance circuit wiring
<br /> shall terminate at the universal mounting plate. Also, Spec-
<br /> Features trAlert Advance products, when used with the Sync•CircuitTm
<br /> • Plug-in design. Module accessory, shall be powered from a non-coded notifl-
<br /> cation appliance circuit output and shall operate on a nominal
<br /> • Same mounting plate for wall-and ceiling-mount units. 12 or 24 volts. When used with the Sync•Circuit Module, 12-
<br /> • Shorting spring on mounting plate for continuity check volt rated notification appliance circuit outputs shall operate
<br /> before installation. between 9 and 17.5 volts; 24-volt rated notification appliance
<br /> • Captive mounting screw. circuit outputs shall operate between 17 and 33 volts. Indoor
<br /> Tamper-resistance capability. SpectrAlert Advance products shall operate between 32°F and
<br /> • 120°F(0°C and 49°C)from a regulated DC,or full-wave-recti-
<br /> • Field-selectable candela settings on wall and ceiling units: fled, unfiltered power supply. Strobes and horn/strobes shall
<br /> 15, 15!75,30,75,95, 110, 115, 135, 150,177, 185. have field-selectable candela settings including 15, 15/75,30,
<br /> • Automatic selection of 12 or 24 volt operation at 15 and 15/ 75,95, 110, 115, 135, 150, 177, 185.
<br /> 75 candela.
<br /> • Outdoor wall and ceiling products.
<br /> DN-7087:C1•11/9/11—Page 1 of 4