Laserfiche WebLink
Ventilation Measurement Documentation <br /> b <br /> Bldg Address: 45XX N. shore Dr. Date: <br /> Ci Orono Zip Code: <br /> Completed By: Tony Lund Co. Name: Stonewood Design Build L.L.C. <br /> Path 0, Aggregate Alternative <br /> Ventilation: Measured Performance <br /> People Ventilation Supplemental Ventilation Total Ventilation <br /> Minimums---> 75 238 313 <br /> Measured Measured <br /> People Designed Intake Exhaust Supplemental Designed Intake Exhaust <br /> HRV or ERV 1 64 cfm. HRV or ERV 1 198 cfm. <br /> Kitchen Exhaust 0 cfm. Kitchen Exhaust 300 cfm. f <br /> Master Bathroom 80 cfm. `= Master Bathroom 0 cfm. <br /> 2nd FI Bathroom 0 cfm. u 2nd FI Bathroom 80 cfrn. <br /> People: 144 cfm. I Supplemental: 578 dm. <br /> Note: Air flow for balanced ventilation systems must be balanced within ten percent. <br /> Total Designed Ventilation: P722 cfm. Total Measured Ventilation(people+supplemental): <br /> Compliance Statement: Installed ventilation system is In compliance with the MN Energy Code and sized to provide the design air flow. <br /> Cu�uc� <br /> Applican print name) Sidnature <br /> Da Phone number <br />