•; I Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,ink
<br /> 11 Ferguson Enterprises j Plymout 3286 Navare Ln
<br /> I 1 Plymouth,MN 55441 Page 5
<br /> Total Building Summary Loads
<br /> Component Area Sen Let Sen Tota'
<br /> Description Quan Loss Gain Gain Gain
<br /> 1 D-cv-o: Glazing-Double pane, operable window, clear, 242.5 5,967 0 5,549 5,549
<br /> vinyl frame, u-value 0.3, SHGC 0.56
<br /> 1 D-cv-d: Glazing-Double pane, sliding glass door, clear, 30 738 0 444 444
<br /> vinyl frame, u-value 0.3, SHGC 0.56
<br /> 11K: Door-Metal- Fiberglass Core With Storm 63 1,860 0 567 567
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 2394.5 12,763 0 2,224 2,224
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 16A-56: Roof/Ceiling-Under Attic with Insulation on Attic 1952 2,881 0 2,424 2,424
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Unvented Attic, No Radiant Barrier, Any
<br /> Roofing Material, Any Roof Color, R-56 insulation
<br /> 22C-10pm: Floor-Slab on grade, Horizontal board 132 11,993 0 0 0
<br /> insulation extends 4' under slab, any floor cover, R-
<br /> 10 insulation, passive, heavy dry or light wet soil
<br /> Subtotals for structure: 36,202 0 11,208 11,208
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 0 0 0
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 162, Summer CFM: 0 14,162 0 0 0
<br /> Ventilation: Winter CFM: 320, Summer CFM: 320 28,005 7,082 4,781 11,863
<br /> AED Excursion: 0 0 71 71
<br /> Total Building Load Totals: 78,369 8,282 17,440 25,722
<br /> iOhecii Figures . • --- _ ---- - 1
<br /> Total Building Supply CFM: 674 CFM Per Square ft.: 0.231
<br /> Square ft. of Room Area: 2,920 Square ft. Per Ton: 1,362
<br /> Volume (ft3): 25,312
<br /> Bu if9 Loads -
<br /> Total Heating Required Including Ventilation Air: 78,369 Btuh 78.369 MBH
<br /> Total Sensible Gain: 17,440 Btuh 68 %
<br /> Total Latent Gain: 8,282 Btuh 32 %
<br /> Total Cooling Required Including Ventilation Air: 25,722 Btuh 2.14 Tons(Based On Sensible+Latent)
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\Users\AAN6658\Documents\HEAT LOSS CALC\3286 Navare Ln.rh9 Wednesday, December 20, 2017, 10:22 AM