<br /> Component Area Sen. Lat. Sen. Total
<br /> Description Quan Loss Gain Gain Gain
<br /> 4A Window Double Pane & Storm Clear Glass Wood Frame 307 9,629 0 7,730 7,730
<br /> 8M Glass Door pouble Clear Glass Wood Frame 143 7,249 0 4,290 4,290
<br /> 11 C Door Metal Polystyrene Core 40 1,298 0 363 363
<br /> 121 Wall R-19 + 1/2" Asphlt Board(R-1.3) 3,421 17,313 0 4,441 4,441
<br /> 131 Part R-19 + 1/2" Asphlt Board(R-1.3) 268 678 0 221 221
<br /> 15C Wall 2-5' Below Grade 8/12" BIk+R-11 928 4,355 0 0 0
<br /> 161 Ceiling R-44 Insulation 2,095 4,433 0 2,120 2,120
<br /> 20J Floor Over Open Crawl Carpet+ R-30 363 1,169 0 191 191
<br /> 21 A Basemt Floor 2' or More Below Grade 1,700 3,754 0 0 0
<br /> Subtotals for structure: 9,265 49,878 0 19,356 19,356
<br /> Active People: 8 0 1,840 2,400 4,240
<br /> Inactive People: 0 0 0 0 0
<br /> Appliances: 0 0 600 1,200 1,800
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 2,033 0 0 0
<br /> Infiltration: Winter CFM: 234.3, Summer CFM: 156.2 490 23,714 3,825 3,438 7,263
<br /> Ventilation: Winter CFM: 125.0, Summer CFM: 125.0 0 n/a n/a n/a n/a
<br /> Sensible Gain Total: 26,394
<br /> Temperature Swinq Multiplier: X1.00
<br /> Zone Load Totals: 75.625 6,265 26,394 32,659
<br /> . ;,.�;;.,�.;�:;>:r;., �. � ��.��.,�
<br /> .�� . .
<br /> < .. : . , .
<br /> ;:�.:.,.....::...::.. .:..:w�� :�:.. �.
<br /> ..��.:::...::.::.:�::.::.:.�::.:�.:..,.:,.:....:.... .. .. .---:-:� :.f .:.. ,:; `;"` �
<br /> .�
<br /> Supply CFM: 1,200 CFM per square foot: 0.232
<br /> Square feet of room area: 5,164 Square feet per ton: 1,882.307
<br /> . .........:j.w. �•:;::••.•.;^�"h�. •,�•,k�� �'ti\\'i\����\ `.E�'titi:�O \w
<br /> �. .. ..... • �,� � � ��i.�� • ��� �.
<br /> ���}�:ii�,:.,'�:4c;:: . �`' �:.�'.`n�..'\ `�:�.� ,:xcj},��n
<br /> �. y:., \• .;{. \�.4 \ \ x•'O'�y�
<br /> Total heating required with outside air: 75,625 Btuh 75.624 MBH
<br /> Total sensible gain: 26,394 Btuh 81 %
<br /> Total latent gain: 6,265 Btuh 19 %
<br /> Total cooling required with outside air: 32,659 Btuh 2.722 Tons (based on sensible + latent)
<br /> 2.743 Tons (based on 75% sensible capacity)